Skip to main content

Event Notification Report for June 06, 2010

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
06/05/2010 - 06/06/2010

EVENT NUMBERS
4597945980

Power Reactor
Event Number: 45979
Facility: FERMI
Region: 3     State: MI
Unit: [2] [] []
RX Type: [2] GE-4
NRC Notified By: RUSSELL WARD
HQ OPS Officer: DONG HWA PARK
Notification Date: 06/06/2010
Notification Time: 03:10 [ET]
Event Date: 06/06/2010
Event Time: 02:38 [EDT]
Last Update Date: 06/07/2010
Emergency Class: ALERT
10 CFR Section:
50.72(a) (1) (i) - EMERGENCY DECLARED 50.72(b)(2)(iv)(B) - RPS ACTUATION - CRITICAL
Person (Organization):
PATTY PELKE (R3DO)
MELANIE GALLOWAY (NRR)
SCOTT MORRIS (IRD)
JACK GROBE (NRR)
MARK SATORIUS (R3)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 A/R Y 100 Power Operation 0 Hot Shutdown
Event Text
AUTOMATIC REACTOR SCRAM DUE TO PARTIAL LOSS OF OFFSITE POWER

"Reactor shutdown. All control rods inserted. Maintaining reactor vessel level with reactor core isolation cooling. Maintaining reactor vessel pressure with reactor core isolation cooling. [Automatic] Reactor scram due to loss of division 2 offsite power. Classification code: Unusual Event (HU1) Natural Destruction Phenomena Affecting the Protected Area."

The licensee declared a Notification of Unusual Event at 0253 EDT. All rods fully inserted and decay heat is being removed by the main condensers. Division 1 buses are being powered by 1 of 3 offsite feeds and division 2 buses are being powered by the Emergency Diesel Generators.

The licensee has notified the NRC Resident Inspector.

* * * UPDATE FROM JEFF GROFF TO DONG PARK AT 0425 EDT ON 6/6/2010 * * *

"Division 2 power provided by Emergency Diesel Generators number 13 and 14. Classification Alert Code: (HA1) Natural Destruction Phenomena Affecting the Plant Vital Area. Main condenser is the heat sink."

The licensee declared an Alert at 0417 EDT. The reactor remains stable in Mode 3. Physical damage to the auxiliary and the turbine buildings were noticed after an initial inspection.

The licensee has notified the NRC Resident Inspector. Notified R3RA (Satorius), NRR (Grobe), IRD (Morris), R3DO (Pelke), NRR EO (Galloway), DHS (Doyle), FEMA (Guy), DOE(Morrone), USDA (Ussery), HHS (Standifer), and CNSC (Gdesnryxrs).

* * * UPDATE FROM JEFF GROFF TO DONG PARK AT 0603 EDT ON 6/6/2010 * * *

"At 0238 [EDT], severe weather caused a loss of 345KV [switchyard power]. Reactor scrammed from a turbine trip. Plant is stabilized with RPV [Reactor Pressure Vessel] water level in normal band and RPV pressure at 820 psig. RPV Pressure is being controlled on turbine BPV [By Pass Valve]. Division 2 EDG's [Emergency Diesel Generator] are supplying power to division 2 buses. Plant is currently in Alert due to physical damage to plant due to severe weather."

The NRC Senior Resident Inspector is on-site. Notified IRD (Morris), R3DO (Pelke), NRR EO (Galloway).

* * * UPDATE FROM ED KOKOSKY TO DONG PARK AT 0247 EDT ON 6/7/2010 * * *

"There is no release of radiological materials. No further potential exists for uncontrolled release of radioactive materials to the environment. The Reactor is shut down. Reactor pressure and temperature are within normal bands. Offsite electrical feeds to the site have been restored. An overall damage assessment has been prepared and reviewed to ensure no conditions exist that would create an entry condition to the Emergency Plan. Plant repairs will be accomplished through site processes."

At 0220 EDT on 6/7/10, the licensee has terminated from the Alert classification.

The licensee has notified the NRC Resident Inspector. Notified R3RA (Satorius), NRR (Grobe), IRD (Grant), R3DO (Pelke), NRR EO (Galloway), DHS (Doyle), FEMA (Blankenship), DOE(Bailey), USDA (Ussery), HHS (Peagler), and CNSC (Gdesnryxrs).


Power Reactor
Event Number: 45980
Facility: BRUNSWICK
Region: 2     State: NC
Unit: [1] [2] []
RX Type: [1] GE-4,[2] GE-4
NRC Notified By: TIM STREET
HQ OPS Officer: BILL HUFFMAN
Notification Date: 06/06/2010
Notification Time: 12:37 [ET]
Event Date: 06/06/2010
Event Time: 11:37 [EDT]
Last Update Date: 06/06/2010
Emergency Class: ALERT
10 CFR Section:
50.72(a) (1) (i) - EMERGENCY DECLARED
Person (Organization):
STEVEN VIAS (R2DO)
MELANIE GALLOWAY (NRR)
JACK GROBE (NRR)
LUIS REYES (R2 R)
JEFFERY GRANT (IRD)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
2 N Y 100 Power Operation 100 Power Operation
Event Text
BRUNSWICK DECLARED ALERT DUE TO HALON DISCHARGE IN EMERGENCY DIESEL GENERATOR BUILDING

At 1137 EDT, Brunswick Units 1 & 2 declared an Alert condition due to a discharge of Halon gas into the basement of the emergency diesel generator building (EAL H.A.3.1 for toxic gas discharge into a vital area). Initial inspection indicates that there is no fire. No offsite assistance was required and no personnel injuries as a result of the discharge. Both reactors continue to operate at 100% power. The licensee is investigating the cause of the discharge and will terminate the Alert when the area is ventilated and can be reoccupied.

The licensee has notified State and local authorities and the NRC Resident Inspector.

* * * UPDATE TO ABRAMOVITZ FROM CINDRIC AT 1616 EDT ON 6/6/10 * * *

The licensee terminated the Alert at 1614 EDT based on restoring normal atmosphere conditions in the emergency diesel generator building. The initiating cause of this event is still being investigated. State and local authorities have been notified and the Resident Inspector will be notified.

The NRC Operations Center has notified the Federal Agencies initially notified of this event. R2DO (Vias), NRR EO (Galloway) and IRD (Grant) notified.