Skip to main content

Event Notification Report for May 22, 2010

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
05/21/2010 - 05/22/2010

EVENT NUMBERS
4594545946

Power Reactor
Event Number: 45945
Facility: MILLSTONE
Region: 1     State: CT
Unit: [] [2] []
RX Type: [1] GE-3,[2] CE,[3] W-4-LP
NRC Notified By: JOSHUA SPALTER
HQ OPS Officer: HOWIE CROUCH
Notification Date: 05/22/2010
Notification Time: 17:46 [ET]
Event Date: 05/22/2010
Event Time: 16:45 [EDT]
Last Update Date: 05/22/2010
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(iv)(B) - RPS ACTUATION - CRITICAL 50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION
Person (Organization):
MARIE MILLER (R1DO)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 M/R Y 100 Power Operation 0 Hot Standby
Event Text
MANUAL REACTOR TRIP DUE TO LOSS OF STEAM GENERATOR WATER LEVEL CONTROL

"The licensee experienced a feedwater transient which initiated the event. All safety systems are available. All control rods fully inserted. The electrical lineup is normal. The decay heat path is through the condenser steam dumps. No relief valves or safety valves lifted during the transient. Primary plant temperature is 533 degrees Fahrenheit and primary plant pressure is 2256 psia. The licensee is investigating the cause of the feed transient.

"The licensee notified the NRC Resident Inspector, the Waterford Dispatch, and the State Department of Environmental Protection."

Earlier, the licensee was experiencing oscillations in the feedwater regulating valve (FRV) for the #2 steam generator when the valve was in automatic control. Troubleshooting planning was underway but no troubleshooting activities were in progress at the time of the trip. When the operator placed the #2 steam generator FRV in manual control, the steam generator water level began to increase and could not be recovered. The operator then manually tripped the reactor prior to reaching the high steam generator level trip setpoint. An Auxiliary Feed Water system actuation did occur during the transient. The trip and plant response was considered uncomplicated.


Power Reactor
Event Number: 45946
Facility: FARLEY
Region: 2     State: AL
Unit: [] [2] []
RX Type: [1] W-3-LP,[2] W-3-LP
NRC Notified By: RICK LULLING
HQ OPS Officer: JOHN KNOKE
Notification Date: 05/22/2010
Notification Time: 19:10 [ET]
Event Date: 05/22/2010
Event Time: 16:34 [CDT]
Last Update Date: 05/22/2010
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(iv)(B) - RPS ACTUATION - CRITICAL 50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION
Person (Organization):
DEBORAH SEYMOUR (R2DO)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 M/R Y 100 Power Operation 0 Hot Standby
Event Text
MANUAL REACTOR TRIP DUE TO LOSS OF STEAM GENERATOR WATER LEVEL CONTROL

"Unit 2 was operating at 100% power in the normal operating procedure, FNP-2-UOP-3.1, Power Operation, when multiple alarms were received associated with 2C Steam Generator (S/G) level, and a process cabinet failure. The control room team noticed there was no power or control capability on the 2C S/G Feedwater Regulating Control Valve (FRV), and 2C S/G level was decreasing. The control room team attempted to take manual control of the 2C FRV, which did not respond. The reactor was manually tripped when 2C S/G narrow range level reached 40%. The automatic trip set point for S/G level is 28%. All systems responded properly for the reactor trip and there were no complications.

"The investigation indicates there was an Nuclear Controller Driver (NCD) card failure in Process Control Cabinet 8. The controller card controls the 2C S/G FRV controller, which prevented any automatic, or manual control of the 2C S/G FRV, or 2C S/G level."

There were no safety or relief valves that lifted and decay heat is being removed via steam dump control valves. Auxiliary feedwater pumps are maintaining level in the steam generators. Electrical lineup is normal.

The licensee has notified the NRC Resident Inspector.