Skip to main content

Event Notification Report for April 05, 2010

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
04/04/2010 - 04/05/2010

EVENT NUMBERS
4581445815

Power Reactor
Event Number: 45814
Facility: SAINT LUCIE
Region: 2     State: FL
Unit: [1] [] []
RX Type: [1] CE,[2] CE
NRC Notified By: FRED POLLACK
HQ OPS Officer: VINCE KLCO
Notification Date: 04/06/2010
Notification Time: 02:42 [ET]
Event Date: 04/05/2010
Event Time: 23:02 [EDT]
Last Update Date: 04/06/2010
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(xii) - OFFSITE MEDICAL
Person (Organization):
JAMES MOORMAN (R2DO)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N N 0 Cold Shutdown 0 Cold Shutdown
Event Text
TRANSPORT OF A CONTAMINATED INDIVIDUAL OFFSITE

"On 4/5/2010, at 2244 [EDT], the Unit 1 Control Room was notified of an individual in the Unit 1 Containment Building complaining of chest pains. Offsite medical was contacted via 911 emergency call and the individual was transported, via ambulance, to Lawnwood Regional Medical Center at 2302. Radiation Protection personnel accompanied the individual to the hospital. The individual was admitted at 2335. Radiation Protection personnel determined that the individual was radioactively contaminated at a level of 3500 corrected counts per minute on his left ankle. The individual was successfully decontaminated. The transport of a radioactively contaminated individual to an offsite medical facility is reportable under 10CFR50.72(b)(3)(xii)."

The licensee notified the NRC Resident Inspector.


!!!!! THIS EVENT HAS BEEN RETRACTED !!!!!
!!!!! THIS EVENT HAS BEEN RETRACTED !!!!!
Power Reactor
Event Number: 45815
Facility: PERRY
Region: 3     State: OH
Unit: [1] [] []
RX Type: [1] GE-6
NRC Notified By: DOUGLAS SHORTER
HQ OPS Officer: HOWIE CROUCH
Notification Date: 04/06/2010
Notification Time: 06:11 [ET]
Event Date: 04/05/2010
Event Time: 22:50 [EDT]
Last Update Date: 06/04/2010
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(v)(C) - POT UNCNTRL RAD REL
Person (Organization):
HIRONORI PETERSON (R3DO)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
Event Text
LOSS OF SAFETY FUNCTION TO CONTROL THE RELEASE OF RADIOACTIVE MATERIAL

"At 2145 [EDT] hours on April 5, 2010, a loss of electrical power to the Division 1 Loss of Coolant Accident (LOCA) initiation logic occurred. Control room annunciators for 'Residual Heat Removal (RHR) Out of Service', 'Reactor Core Isolation Cooling (RCIC) Out of Service', and 'RCIC/RHR D2 to D1 00 File Power Loss' were received. At 2250 hours, the Control Room staff determined a loss of isolation function existed. The operators entered Technical Specification (TS) action statements for Emergency Core Cooling System Instrumentation (TS 3.3.5.1), RCIC Instrumentation (TS 3.3.5.2), and Primary Containment and Drywell Isolation Instrumentation (TS 3.3.6.1). The power loss was caused by a blown fuse which occurred during surveillance testing. The surveillance test was suspended and plant personnel commenced troubleshooting and investigation efforts. A recovery plan is being developed to back out of the surveillance test and replace the fuse to re-energize the logic, while ensuring the plant does not experience an undesirable actuation of the logic.

"The power loss caused five containment isolation valves to lose automatic isolation function. These valves have no associated inboard automatic isolation valve powered by Division 2. As a result of the power loss, the valves cannot automatically close on demand to isolate and therefore cannot perform their automatic function to isolate the containment.

"This event is being reported in accordance with 10 CFR 50.72(b)(3)(v)(C) as an event or condition that at the time of discovery could have prevented the fulfillment of the safety function of structures or systems that are needed to control the release of radioactive material.

"The NRC Resident Inspectors have been notified."

The licensee entered a 12-hour shutdown action statement for the loss of containment isolation function as a result of the power failure.

* * * RETRACTION FROM LLOYD ZERR TO PETE SNYDER ON 6/4/2010 AT 1126 * * *

"On April 6, 2010, at 0611 hours, notification was made to NRC Operations Center of an event that at the time of discovery, could have prevented the fulfillment of the safety function of structures or systems that are needed to control the release of radioactive material [10 CFR 50.72(b)(3)(v)(c)]. A blown fuse during surveillance testing caused a loss of electrical power to the Division 1 Loss of Coolant Accident initiation logic. The power loss caused five containment isolation valves to lose their automatic isolation function. These valves have no associated inboard automatic isolation valve powered by Division 2. As a result of the power loss, the valves could not automatically close on demand and therefore, could not perform their automatic function to isolate containment.

"Following further evaluation, it was determined that a loss of safety function of structures or systems that are needed to control the release of radioactive material did not occur. Based on review of valve leak rate test history and compliance with 10 CFR 50, Appendix A, General Design Criteria, the penetrations and Containment were capable of performing their intended design function. The associated inboard valves and/or water seals were capable of automatically isolating containment. Additionally, all required Technical Specifications Limiting Conditions for Operation were complied with for the identified issue, and therefore, no operation or condition prohibited by the plant's Technical Specifications existed.

"Since the event or condition reported in Event Notification 45815 would not have prevented the fulfillment of the safety function needed to control the release of radioactive material, this event or condition is not reportable and the notification is retracted. Additionally, based on not meeting any 10 CFR 50.73 reporting criteria, no Licensee Event Report is required. The evaluation (i.e., Reportability Determination) for this event or condition is documented in Condition Report 10-74904.

"The NRC Resident Inspector has been notified."

Notified the R3DO (Pelke).