Event Notification Report for March 13, 2010

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
03/12/2010 - 03/13/2010

EVENT NUMBERS
45765

Power Reactor
Event Number: 45765
Facility: INDIAN POINT
Region: 1     State: NY
Unit: [2] [] []
RX Type: [2] W-4-LP,[3] W-4-LP
NRC Notified By: PHIL SANTINI
HQ OPS Officer: STEVE SANDIN
Notification Date: 03/13/2010
Notification Time: 21:38 [ET]
Event Date: 03/13/2010
Event Time: 18:25 [EST]
Last Update Date: 03/13/2010
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(v)(B) - POT RHR INOP
Person (Organization):
CHRISTOPHER CAHILL (R1DO)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 N N 0 Cold Shutdown 0 Cold Shutdown
Event Text
EMERGENCY DIESEL GENERATORS (EDGs) DECLARED INOPERABLE DUE TO SERVICE WATER TAGOUT

"At 1825 EST service water to '22' and '23' EDGs was isolated while applying a protective tagout to the service water '1-2-3' header. Previously, the supply from the other service water header '4-5-6' was also isolated. '21' EDG was out of service on a tagout.

"This resulted in a condition where no service water flow to the Emergency Diesel Generators was available for approximately three minutes. Service water flow was restored by opening the supply from the '1-2-3' service water header. During this condition, LCO 3.8.2 was not met. All required actions for LCO 3.8.2 were performed. LCO 3.8.2 was met when service water flow was restored to the Emergency Diesel Generators.

"The Emergency Diesel Generators were required to support residual heat removal in the event of a loss of offsite power. At no time was residual heat removal lost."

The licensee will inform the NRC Resident Inspector.