Skip to main content

Event Notification Report for November 26, 2009

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
11/25/2009 - 11/26/2009

EVENT NUMBERS
45520455214552245582

Power Reactor
Event Number: 45520
Facility: SEQUOYAH
Region: 2     State: TN
Unit: [] [2] []
RX Type: [1] W-4-LP,[2] W-4-LP
NRC Notified By: JEFF EPPERSON
HQ OPS Officer: JOHN KNOKE
Notification Date: 11/26/2009
Notification Time: 04:00 [ET]
Event Date: 11/26/2009
Event Time: 02:42 [EST]
Last Update Date: 11/26/2009
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(iv)(B) - RPS ACTUATION - CRITICAL 50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION
Person (Organization):
MARVIN SYKES (R2DO)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 M/R Y 30 Power Operation 0 Hot Standby
Event Text
MANUAL TRIP DUE TO LOSS OF VACUUM ON TURBINE DRIVEN FEEDWATER PUMP

"At 0242 EST, 11/26/2009 Unit 2 reactor was manually tripped based upon indications that the 2A Main Feedwater Pump Turbine was losing vacuum. Prior to the trip, the reactor was at 30% RTP and ascending following completion of a scheduled refueling outage. 2A Main Feedwater Pump was in service; preparations were in progress to start 2B Main Feedwater Pump to support continued power ascension. Subsequent to the trip, the Auxiliary Feedwater Pumps (motor-driven and turbine-driven) started as expected in response to the trip of both main feedwater pumps following receipt of a normal feedwater isolation signal. No primary or secondary plant safety valves operated during the transient. All plant system responses to the trip were as expected. An investigation will be conducted to identify the cause of the indicated loss of vacuum and the required corrective actions. Expected restart date to be determined."

All control rods fully inserted. The licensee has notified the NRC Resident Inspector.


Power Reactor
Event Number: 45521
Facility: TURKEY POINT
Region: 2     State: FL
Unit: [3] [4] []
RX Type: [3] W-3-LP,[4] W-3-LP
NRC Notified By: MARK JONES
HQ OPS Officer: DONG HWA PARK
Notification Date: 11/26/2009
Notification Time: 14:52 [ET]
Event Date: 11/26/2009
Event Time: 13:28 [EST]
Last Update Date: 11/26/2009
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(xi) - OFFSITE NOTIFICATION
Person (Organization):
MARVIN SYKES (R2DO)
ROBERT NELSON (NRR)
WILLIAM GOTT (IRD)
MATTHEW HAHN (ILTA)
MICHAEL ERNSTES (R2 I)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
3 N Y 100 Power Operation 100 Power Operation
4 N N 0 Hot Standby 0 Hot Standby
Event Text
OFFSITE NOTIFICATION DUE TO CUBAN NATIONALS LANDING ON OWNERS CONTROLLED AREA

"At 1328 [EST] on 11/26/09, the Turkey Point Nuclear Power Station Control Room received a call from an individual stating that he was a member of a group of Cuban nationals that had landed in the Turkey Point cooling canals. The individual reported that 33 Cuban nationals total (29 adults and 4 children) were in the cooling canal system. The Turkey Point Nuclear control room notified Turkey Point Nuclear Security, who located and assumed control over the Cuban nationals without incident. Turkey Point Nuclear Security notified local law enforcement agency (Miami-Dade Police), requesting assistance. At 1425 [EST], Miami-Dade Police arrived on site. United States Border Patrol and Immigration and Customs Enforcement (ICE) were notified by Miami-Dade Police.

"This event is being reported under 10CFR50.72(b)(2)(xi), for an event requiring notification to a government agency."

The licensee has informed the NRC Resident Inspector.


Power Reactor
Event Number: 45522
Facility: TURKEY POINT
Region: 2     State: FL
Unit: [] [4] []
RX Type: [3] W-3-LP,[4] W-3-LP
NRC Notified By: ROGER MONTGOMERY
HQ OPS Officer: JOHN KNOKE
Notification Date: 11/27/2009
Notification Time: 05:00 [ET]
Event Date: 11/26/2009
Event Time: 23:40 [EST]
Last Update Date: 11/27/2009
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION
Person (Organization):
MARVIN SYKES (R2DO)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
4 N N 0 Hot Standby 0 Hot Standby
Event Text
TWO SHUTDOWN BANK RODS WERE DROPPED FROM FULLY WITHDRAWN POSITION

"With Unit 4 borated to a cold shutdown condition following the Unit 4 Cycle 25 refueling outage, post-modification acceptance testing was being performed on the Rod Position Indication System prior to reactor startup. While performing this test, two shutdown bank rods showed indication of being fully inserted from a fully withdrawn position. Off-normal procedures were entered and the Reactor Protection System (RPS) was subsequently manually actuated. All remaining rods were fully inserted in accordance with plant procedures. Investigations are in progress to determine and repair the cause of the dropped rods."

The licensee has notified the NRC Resident Inspector.


General Information or Other
Event Number: 45582
Rep Org: OHIO BUREAU OF RADIATION PROTECTION
Licensee: MARS PETCARE US, INC
Region: 3
City: COLUMBUS   State: OH
County:
License #: 00006GL0138
Agreement: Y
Docket:
NRC Notified By: STEPHEN JAMES
HQ OPS Officer: CHARLES TEAL
Notification Date: 12/18/2009
Notification Time: 13:47 [ET]
Event Date: 11/26/2009
Event Time: 00:00 [EST]
Last Update Date: 12/18/2009
Emergency Class: NON EMERGENCY
10 CFR Section:
Person (Organization):
TAMARA BLOOMER (R3DO)
GLENDA VILLAMAR (FSME)
CNCNS - CANADA (FAX)
Event Text
AGREEMENT STATE - LOST LEVEL INDICATOR

The following was received via email:

"General licensee (GL) reported to BRP (Bureau of Radiation Protection) on 12/18/09 that a generally licensed device was unaccounted for. The device has been identified as an Industrial Dynamics FilTech FT-50 [fixed gauge] level indicator, serial number 113216, containing 100 mCi of Am-241.

"The licensee last reported that the device was in their possession with the annual GL registration to BRP on 10/11/02. The device was not listed on the next GL registration submitted by the licensee on 11/26/03. During an internal audit by the licensee it was determined that a report of disposition of the device had not been submitted to BRP. The device had been installed in a process line which was decommissioned and dismantled in June 2003. As the licensee investigated the matter they determined that they could not account for the current location of the device. The manufacturer had no record of receipt of the device and the licensee could not locate the device anywhere within their facility.

Additional investigation and information is being requested by BRP. "

Ohio Report #: OH090012

Source Model #: 06110

THIS MATERIAL EVENT CONTAINS A "LESS THAN CAT 3" LEVEL OF RADIOACTIVE MATERIAL

Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf