Event Notification Report for October 19, 2009

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
10/18/2009 - 10/19/2009

EVENT NUMBERS
454454544745518

Power Reactor
Event Number: 45445
Facility: WATERFORD
Region: 4     State: LA
Unit: [3] [] []
RX Type: [3] CE
NRC Notified By: JOE WILLIAMS
HQ OPS Officer: PETE SNYDER
Notification Date: 10/19/2009
Notification Time: 14:13 [ET]
Event Date: 10/19/2009
Event Time: 09:44 [CDT]
Last Update Date: 10/19/2009
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(iv)(B) - RPS ACTUATION - CRITICAL 50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION
Person (Organization):
NEIL OKEEFE (R4DO)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
3 M/R Y 100 Power Operation 0 Hot Standby
Event Text
MANUAL REACTOR TRIP FOLLOWING STUCK OPEN MOISTURE SEPARATOR HEATER RELIEF VALVE

"At approximately 0915 CDT on 10/19/09 a Waterford 3 Moisture Separator Heater shell-slide relief valve (RS-203B) inadvertently opened, causing reactor power to increase from 100% to approximately 100.27% Rated Thermal Power (RTP). Operations reduced Main Turbine-Generator load by approximately 26 megawatts to restore reactor power to less than 100% RTP. At approximately 0942 CDT, Operations commenced a rapid plant shutdown because the relief valve would not re-close. At approximately 0944 CDT, Operations manually tripped the reactor due to a low condenser hot well level, just prior to reaching the Condensate Pumps Trip setpoint, to avoid a loss of Main Feedwater event. The Plant Protection System (PPS) responded as designed, resulting in an uncomplicated reactor trip.

"Emergency Feedwater Actuation Signal (EFAS) was received on low Steam Generator level as expected from reactor trip at or near full power. Steam Generator levels remained above the EFAS injection level setpoint so that actual injection of Emergency Feedwater did not occur. No other PPS actuation occurred. The plant is currently being maintained in Mode 3.

"Waterford 3 plans to commence refueling outage (RF16) at this time, approximately 1 - 2 days earlier than scheduled.

The licensee notified the NRC Resident Inspector.


General Information or Other
Event Number: 45447
Rep Org: BASIN ELECTRIC POWER COOPERATIVE
Licensee: BASIN ELECTRIC POWER COOPERATIVE
Region: 4
City: WHEATLAND   State: WY
County:
License #: 33-18224-01
Agreement: N
Docket:
NRC Notified By: DAVID CUMMINGS
HQ OPS Officer: DONG HWA PARK
Notification Date: 10/20/2009
Notification Time: 11:05 [ET]
Event Date: 10/19/2009
Event Time: 00:00 [MDT]
Last Update Date: 10/20/2009
Emergency Class: NON EMERGENCY
10 CFR Section:
30.50(b)(2) - SAFETY EQUIPMENT FAILURE
Person (Organization):
NEIL OKEEFE (R4DO)
ANGELA MCINTOSH (FSME)
Event Text
SHUTTER ON NUCLEAR GAUGE STUCK OPEN

During an inspection on October 19, 2009, a process nuclear gauge was found to have a stuck open shutter. The gauge is a Kay Ray Model 7062P, serial number 5757, containing 100 milliCurie Cs-137 source. It was mounted 20 feet above the floor and no exposure to personnel occurred.

"At this time it appears that Radiation Technology, Inc. of Austin, TX will provide repair service at a date yet to be determined. In the meantime, the crusher is in service and the gauge is in use with no plans to work on associated equipment. As the gauge is located about 20 feet above the floor with no immediate access, it is not likely to present a hazard. A notification of hazard will be placed in the operations log to prevent any unintentional access until the gauge can be repaired."


Power Reactor
Event Number: 45518
Facility: LIMERICK
Region: 1     State: PA
Unit: [1] [] []
RX Type: [1] GE-4,[2] GE-4
NRC Notified By: JEAN BROILLET
HQ OPS Officer: DONALD NORWOOD
Notification Date: 11/24/2009
Notification Time: 14:19 [ET]
Event Date: 10/19/2009
Event Time: 11:05 [EST]
Last Update Date: 11/24/2009
Emergency Class: NON EMERGENCY
10 CFR Section:
50.73(a)(1) - INVALID SPECIF SYSTEM ACTUATION
Person (Organization):
MARC FERDAS (R1DO)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
Event Text
AUTOMATIC CLOSURE OF PRIMARY CONTAINMENT ISOLATION VALVES DUE TO INVALID SIGNAL

"On Monday, October 19, 2009, Limerick Unit 1 was operating at 100% power. At 1105 hours, an invalid actuation of the 1B Reactor Enclosure Ventilation Exhaust Radiation Monitor occurred. The actuation caused a Division 2 Group 6C isolation signal, which caused primary containment isolation valves (PCIVs) to automatically close on the Containment Leak Detector Radiation Monitor (10-S182) and the Drywell Hydrogen/Oxygen Analyzer (10-S205). The 1A, 1C, and 1D channels were unaffected and indicated normal ventilation exhaust radiation levels during the event.

"The cause of the event was a failure of a fuse holder in the 1B Reactor Enclosure Ventilation Exhaust Radiation Monitor. The radiation monitor is designed to fail-safe on a loss of power. The automatic closure of the PCIVs placed them in their fail-safe position. The failed fuse holder has been replaced and the radiation monitor was declared operable on Tuesday, October 20, 2009 at 1348 hours.

"The portion of the primary containment isolation system that received an actuation signal functioned successfully. All of the affected open isolation valves automatically closed. The only equipment malfunction during the event was the failed fuse holder. The Division 2 Group 6C isolation was a partial actuation.

"This event is reportable per 10CFR50.73(a)(2)(iv)(A) since isolation valves for the Containment Leak Detector Radiation Monitor and Drywell Hydrogen/Oxygen Analyzer automatically closed due to an invalid signal."

The licensee notified the NRC Resident Inspector.