Skip to main content

Event Notification Report for September 22, 2009

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
09/21/2009 - 09/22/2009

EVENT NUMBERS
453764537745471

Power Reactor
Event Number: 45376
Facility: ARKANSAS NUCLEAR
Region: 4     State: AR
Unit: [1] [2] []
RX Type: [1] B&W-L-LP,[2] CE
NRC Notified By: ERIC NICHOLSON
HQ OPS Officer: DONG HWA PARK
Notification Date: 09/22/2009
Notification Time: 13:46 [ET]
Event Date: 09/22/2009
Event Time: 05:11 [CDT]
Last Update Date: 09/22/2009
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(xiii) - LOSS COMM/ASMT/RESPONSE
Person (Organization):
GREG WERNER (R4DO)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
2 N N 0 Cold Shutdown 0 Cold Shutdown
Event Text
LOSS OF POWER TO THE EMERGENCY OPERATIONS FACILITY

"The normal power supply to the Emergency Operations Facility (EOF) was lost due to thunderstorms in the area. Support personnel were dispatched to assess the EOF. The facility has a diesel generator that should supply power to the facility. However, electricians discovered the generator degraded and non-functional. By 0511, 9/22/2009, electricians determined that they were unsuccessful at immediately restoring the generator. It is estimated that the EOF was degraded for approximately 5 1/2 hours.

"Following restoration of normal power, Computer Support personnel discovered that the Safety Parameter Display System (SPDS) at the EOF was not functioning. SPDS is a computer based system designed to monitor and display a concise set of parameters from which the safety status of the plant can be readily and reliably determined.

"The normal power supply was eventually returned [to service] by Entergy Arkansas Transmission and the EOF was restored at 0420 and SPDS terminals were subsequently restored at 0815, 9/22/2009. Due to the time that the EOF was degraded, this is considered a major loss of assessment, communications, and response capability."

The licensee informed the Arkansas Department of Health.

The licensee will notify the NRC Resident Inspector.


Power Reactor
Event Number: 45377
Facility: ARKANSAS NUCLEAR
Region: 4     State: AR
Unit: [1] [] []
RX Type: [1] B&W-L-LP,[2] CE
NRC Notified By: CRYSTAL GARBE
HQ OPS Officer: DONG HWA PARK
Notification Date: 09/22/2009
Notification Time: 15:11 [ET]
Event Date: 09/22/2009
Event Time: 13:29 [CDT]
Last Update Date: 09/22/2009
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(ii)(B) - UNANALYZED CONDITION
Person (Organization):
GREG WERNER (R4DO)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
Event Text
UNANALYZED CONDITION RESULTING FROM AN UNLATCHED DOOR SERVING AS A HIGH ENERGY LINE BREAK BARRIER

"Based on the results of a past operability evaluation completed on 1329 [CDT], 9/22/2009, it appears that an unanalyzed condition existed intermittently for short periods of time in which a door that serves as a High Energy Line Break (HELB) barrier may have been unlatched. With the door not latched, an engineering evaluation concluded that a critical crack (HELB) in the Main Feedwater pipe traversing the south penetration room would force the door (DR-19) open, creating a harsh environment in the adjoining Emergency Feedwater (EFW) pump room. Because the EFW pump room is not evaluated for harsh conditions, it must be conservatively assumed that both pumps may fail to operate following this HELB event. Therefore, this condition is being reported in accordance with 10CFR50.72(b)(3)(ii)(B) as an unanalyzed condition that significantly degrades plant safety."

The licensee informed the Arkansas Department of Health.

The licensee will be notifying the NRC Resident Inspector.


General Information or Other
Event Number: 45471
Rep Org: TEXAS DEPARTMENT OF HEALTH
Licensee: TICONA POLYMERS, INC
Region: 4
City: BISHOP   State: TX
County:
License #: L-02441
Agreement: Y
Docket:
NRC Notified By: ART TUCKER
HQ OPS Officer: JOHN KNOKE
Notification Date: 10/30/2009
Notification Time: 14:26 [ET]
Event Date: 09/22/2009
Event Time: 00:00 [CDT]
Last Update Date: 11/06/2009
Emergency Class: NON EMERGENCY
10 CFR Section:
Person (Organization):
DALE POWERS (R4DO)
ANGELA MCINTOSH (FSME)
Event Text
AGREEMENT STATE REPORT - STUCK SHUTTER ON GAUGE

The following was received via e-mail:

"On October 30, 2009, the Agency [Texas Department of State Health Services] was notified by the licensee that they were reporting a stuck gauge event. The licensee stated that they realized that they needed to report the event after they reviewed a letter sent out by this Agency regarding the reporting of stuck shutters on gauges. The stuck shutter was found during a routine inspection on September 22, 2009. The gauge is stuck in the open position, which is the normal operating position for this gauge. Dose rates in the area were measured and found to be normal. The gauge is a Thermo Fisher model SH-F2 containing a 100 millicurie Cesium (Cs) - 137. The gauge is installed on the side of a vessel and does not pose any additional risk to their workers. The Licensee has contacted a repair service to repair the shutter. This Agency will provide additional information as it is received."

Texas Incident number I-8683

* * * UPDATE AT 1116 EST ON 11/06/2009 TO SIMPSON FROM ART TUCKER * * *

The following update was provided by the State via e-mail:

"The gauge manufacturer was incorrectly identified as Thermo Fisher. The manufacturer is Ohmart/VEGA."

The R4DO (Hay) and FSME (McIntosh) were notified.