Skip to main content

Event Notification Report for March 31, 2009

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
03/30/2009 - 03/31/2009

EVENT NUMBERS
4494644947449484494944990

General Information or Other
Event Number: 44946
Rep Org: NC DIV OF RADIATION PROTECTION
Licensee: FLETCHER HOSPITAL
Region: 1
City: FLETCHER   State: NC
County:
License #: 045-0370-1
Agreement: Y
Docket:
NRC Notified By: CLIFF HARRIS
HQ OPS Officer: JOE O'HARA
Notification Date: 03/31/2009
Notification Time: 14:41 [ET]
Event Date: 03/31/2009
Event Time: 08:30 [EDT]
Last Update Date: 03/31/2009
Emergency Class: NON EMERGENCY
10 CFR Section:
Person (Organization):
MEL GRAY (R1)
ANGELA MCINTOSH (FSME)
Event Text
AGREEMENT STATE REPORT - CONTAMINATION FOUND ON NUCLEAR MEDICINE PACKAGING

The following was received from the state via e-mail:

"N.C. Radiation Protection Section was notified on March 31, 2009 by the hospital about a nuclear medicine package received from a nuclear pharmacy in excess of the loose contamination limits.

"The swipes performed on the package read 2890 dpm vs the limit of 2200 dpm. The package was placed in hot storage and will be stored for decay.

"Licensee notified the carrier and the pharmacy."

NC Event Report ID Number is NC-09-20.


Power Reactor
Event Number: 44947
Facility: PRAIRIE ISLAND
Region: 3     State: MN
Unit: [1] [2] []
RX Type: [1] W-2-LP,[2] W-2-LP
NRC Notified By: STEVE INGALLS
HQ OPS Officer: STEVE SANDIN
Notification Date: 03/31/2009
Notification Time: 16:43 [ET]
Event Date: 03/31/2009
Event Time: 12:00 [CDT]
Last Update Date: 03/31/2009
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(xi) - OFFSITE NOTIFICATION
Person (Organization):
STEVE ORTH (R3)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
2 N Y 100 Power Operation 100 Power Operation
Event Text
EMERGENCY SIREN ACTIVATED FOR REASONS UNKNOWN

"On 3/31/2009 at 1323 CDT Prairie Island Nuclear Generating Plant was notified by the site's siren contractor (NELCOM) that Pierce County siren P-20 had falsely activated at around 1200 CDT. Pierce County notified NELCOM of the siren activation after receiving several calls from the public. No press release is planned for this event.

"Siren P-20 (1 of 52 sirens) has been removed from service and backup route alerting will be used in the event siren activation is required. The cause of the false activation is being investigated and will be repaired.

"The NRC Resident Inspector has been notified."

At 1544 CDT siren P-20 was repaired and returned to service.


Power Reactor
Event Number: 44948
Facility: LIMERICK
Region: 1     State: PA
Unit: [] [2] []
RX Type: [1] GE-4,[2] GE-4
NRC Notified By: NORA GRANETO
HQ OPS Officer: BILL HUFFMAN
Notification Date: 04/01/2009
Notification Time: 00:10 [ET]
Event Date: 03/31/2009
Event Time: 18:50 [EDT]
Last Update Date: 04/01/2009
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION
Person (Organization):
MEL GRAY (R1)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 N N 0 Refueling 0 Refueling
Event Text
VALID DIESEL START SIGNAL RECEIVED DURING MAINTENANCE TESTING OF DIESEL

"A valid actuation of the D23 Emergency Diesel Generator bus undervoltage minimum actuation logic occurred following manual operator action to mitigate a bus overvoltage condition during emergency diesel generator post maintenance testing . Due to the output breaker being opened, the D23 EDG experienced a undervoltage start signal. EDG undervoltage actuation instrumentation actuated, however, the EDG was in PTL (Pull-to-Lock) EDG shutdown. The event was caused by a failure of the emergency diesel generator voltage regulator most likely due to an intermittent failure of the #1 rectifier bank."

The licensee stated that the D23 EDG was powering an isolated safety related bus for a post-maintenance test when the overvoltage condition occurred. The operator opened the EDG output breaker and placed the EDG in PTL. With the bus de-energized, a valid start signal was sent to EDG D23. However, EDG D23 did not actually start because it was in PTL. No safety related equipment was lost when the bus was de-energized because the bus had been unloaded prior to the test.

The licensee has notified the NRC Resident Inspector.


General Information or Other
Event Number: 44949
Rep Org: FLORIDA BUREAU OF RADIATION CONTROL
Licensee: MAYO CLINIC
Region: 1
City: JACKSONVILLE   State: FL
County:
License #: 1812-3
Agreement: Y
Docket:
NRC Notified By: STEVE FURNACE
HQ OPS Officer: DONALD NORWOOD
Notification Date: 04/01/2009
Notification Time: 08:48 [ET]
Event Date: 03/31/2009
Event Time: 00:00 [EDT]
Last Update Date: 04/01/2009
Emergency Class: NON EMERGENCY
10 CFR Section:
Person (Organization):
MEL GRAY (R1)
ANGELA McINTOSH (FSME)
ILTAB (email)
Event Text
AGREEMENT STATE REPORT - LOST I-125 SEED

The following information was received from the State of Florida via fax:

"Cardinal Health working under Mayo Clinic license lost one I-125 seed. Sterilization room and adjoining spaces and personnel were surveyed. It is speculated that the source entered the internal plumbing of the sterilizer. The pipes are of sufficient thickness to prevent external detection. It is surmised by Mayo RSO that Cardinal Health personnel did not follow procedure. RSO estimates that remaining activity as of 31 Mar 2009 is 150 micro Ci's [original activity 300 micro Ci's], with no increased exposure to Cardinal Health staff. Mayo Clinic will work with Cardinal Health staff to modify procedure to ensure source cannot escape vial or tray during sterilization. In addition, retraining will be conducted with all Cardinal health staff involved. Any further investigation is referred to Materials and Licensing. This office will take no further action on this incident."

The Florida Incident Number for this event is FL09-030.

THIS MATERIAL EVENT CONTAINS A "LESS THAN CAT 3" LEVEL OF RADIOACTIVE MATERIAL

Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks.

This source is not amongst those sources or devices identified by the IAEA Code of Conduct for the Safety & Security of Radioactive Sources to be of concern from a radiological standpoint. Therefore is it being categorized as a less than Category 3 source


General Information or Other
Event Number: 44990
Rep Org: UTAH DIVISION OF RADIATION CONTROL
Licensee: ENERGY SOLUTIONS, LLC
Region: 4
City: HELPER   State: UT
County:
License #: UT 2300249
Agreement: Y
Docket:
NRC Notified By: JULE FAUSTO
HQ OPS Officer: JOHN KNOKE
Notification Date: 04/14/2009
Notification Time: 15:40 [ET]
Event Date: 03/31/2009
Event Time: 16:45 [MDT]
Last Update Date: 04/14/2009
Emergency Class: NON EMERGENCY
10 CFR Section:
Person (Organization):
JACK WHITTEN (R4)
ANGELA MCINTOSH (FSME)
Event Text
AGREEMENT STATE REPORT - LEAKING TANK TRAILER WITH TOTAL ACTIVITY OF VARIOUS RADIONUCLIDES OF 20 MILLICURIES

The State submitted the following report via fax:

"This event involved a leaking Tank Trailer containing a total activity of radionuclides of 742.88 MBq (20 mCi), primarily of H-3 (738 MBq) and Tc-99 (3.88 MBq). Small contribution from U-233, U234, U235, U236 and U238. The licensee filled the tank trailer and classed the material as an RQ, of UN 1992, Waste, Flammable Liquids, toxic, nos., (n-butyl alcohol, penol), 3 (6.1), PGIII, Marine Pollutant, (PCB's benzene).

"Tank Trailer number E-112178, total gross weight of 46,765 pounds of flammable liquids, toxic, nos, with radioactive condensate.

"This incident is still under investigation, a written report is pending."

Event Report ID No: UT 090003