Event Notification Report for February 10, 2009
U.S. Nuclear Regulatory Commission
Operations Center
EVENT REPORTS FOR
02/09/2009 - 02/10/2009
EVENT NUMBERS
44843448454487044875
Power Reactor
Event Number: 44843
Facility: PERRY
Region: 3 State: OH
Unit: [1] [] []
RX Type: [1] GE-6
NRC Notified By: DAN STANLEY
HQ OPS Officer: DONALD NORWOOD
Region: 3 State: OH
Unit: [1] [] []
RX Type: [1] GE-6
NRC Notified By: DAN STANLEY
HQ OPS Officer: DONALD NORWOOD
Notification Date: 02/10/2009
Notification Time: 09:45 [ET]
Event Date: 02/10/2009
Event Time: 08:10 [EST]
Last Update Date: 02/10/2009
Notification Time: 09:45 [ET]
Event Date: 02/10/2009
Event Time: 08:10 [EST]
Last Update Date: 02/10/2009
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(xiii) - LOSS COMM/ASMT/RESPONSE
10 CFR Section:
50.72(b)(3)(xiii) - LOSS COMM/ASMT/RESPONSE
Person (Organization):
SONIA BURGESS (R3)
SONIA BURGESS (R3)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 1 | N | Y | 100 | Power Operation | 100 | Power Operation |
PLANT COMPUTER OOS FOR SCHEDULED MAINTENANCE TAKING ERDS OOS
"The Perry Nuclear Power Plant took the Plant Computer out of service for scheduled maintenance which took ERDS out of service. From 0810 hours EST on February 10, 2009 for approximately 6 hours, personnel will be performing maintenance activities on the Plant Computer. During this planned maintenance, the Safety Parameter Display System (SPDS) and the automatic mode calculation of the Computer Aided Dose Assessment Program (CADAP) will be unavailable.
"In the event of an emergency, plant parameter data will be orally transmitted to the facilities through the Status Board Ring Down circuit with back-up by the Private Branch Exchange, Off Premise Exchange, and various redundant intra-facility circuits throughout the emergency facilities. The dose assessment function will be maintained during the out of service time period by manual input of data into CADAP and, if required, by manual calculation. The ability to open and maintain an 'open line' using the Emergency Notification System will not be affected and will be the primary means of transferring plant data to the NRC as a contingency until the ERDS can be returned to service during the period of unavailability.
"This event is being reported in accordance with 10CFR50.72(b)(3)(xiii), as a condition that results in a major loss of offsite communication capability. A follow-up notification will be made when the maintenance activities are completed and the equipment is restored. The [NRC] Resident Inspector has been notified."
* * * UPDATE AT 1250 EST ON 2/10/09 FROM STANLEY TO HUFFMAN * * *
At 1240 EST the licensee returned the plant computer to service. ERDS, CADAP, and SPDS have been restored to operable status. The licensee has notified the NRC Resident Inspector.
R3DO (Burgess) has been informed.
"The Perry Nuclear Power Plant took the Plant Computer out of service for scheduled maintenance which took ERDS out of service. From 0810 hours EST on February 10, 2009 for approximately 6 hours, personnel will be performing maintenance activities on the Plant Computer. During this planned maintenance, the Safety Parameter Display System (SPDS) and the automatic mode calculation of the Computer Aided Dose Assessment Program (CADAP) will be unavailable.
"In the event of an emergency, plant parameter data will be orally transmitted to the facilities through the Status Board Ring Down circuit with back-up by the Private Branch Exchange, Off Premise Exchange, and various redundant intra-facility circuits throughout the emergency facilities. The dose assessment function will be maintained during the out of service time period by manual input of data into CADAP and, if required, by manual calculation. The ability to open and maintain an 'open line' using the Emergency Notification System will not be affected and will be the primary means of transferring plant data to the NRC as a contingency until the ERDS can be returned to service during the period of unavailability.
"This event is being reported in accordance with 10CFR50.72(b)(3)(xiii), as a condition that results in a major loss of offsite communication capability. A follow-up notification will be made when the maintenance activities are completed and the equipment is restored. The [NRC] Resident Inspector has been notified."
* * * UPDATE AT 1250 EST ON 2/10/09 FROM STANLEY TO HUFFMAN * * *
At 1240 EST the licensee returned the plant computer to service. ERDS, CADAP, and SPDS have been restored to operable status. The licensee has notified the NRC Resident Inspector.
R3DO (Burgess) has been informed.
Other Nuclear Material
Event Number: 44845
Rep Org: WAYNE STATE UNIVERSITY
Licensee: WAYNE STATE UNIVERSITY
Region: 3
City: DETROIT State: MI
County:
License #: 21-00741-08
Agreement: N
Docket:
NRC Notified By: MAHA SRINIVASAN
HQ OPS Officer: BILL HUFFMAN
Licensee: WAYNE STATE UNIVERSITY
Region: 3
City: DETROIT State: MI
County:
License #: 21-00741-08
Agreement: N
Docket:
NRC Notified By: MAHA SRINIVASAN
HQ OPS Officer: BILL HUFFMAN
Notification Date: 02/11/2009
Notification Time: 15:40 [ET]
Event Date: 02/10/2009
Event Time: 19:00 [EST]
Last Update Date: 02/11/2009
Notification Time: 15:40 [ET]
Event Date: 02/10/2009
Event Time: 19:00 [EST]
Last Update Date: 02/11/2009
Emergency Class: NON EMERGENCY
10 CFR Section:
10 CFR Section:
Person (Organization):
SONIA BURGESS (R3)
REBECCA TADESSE (FSME)
ILTAB VIA E-MAIL
SONIA BURGESS (R3)
REBECCA TADESSE (FSME)
ILTAB VIA E-MAIL
MISSING VIAL CONTAINING 5 MILLICURIES OF CHROMIUM - 51
The RSO for the Wayne State University's School of Pharmacy reported a missing vial containing 5 millicuries of Chromium-51 in a saline solution. The vial was received at the licensee's laboratory on February 6 along with two cartons of tritium. The tritium was removed from its shipping cartons and placed in a lab storage refrigerator. The Chromium was left on a desk in the carton to be leak tested prior to being placed in the refrigerator.
Apparently, the lab student did not perform the leak test on the Chromium before leaving the lab. The carton with the Chromium vial was left on the desk near the trash can with the empty tritium containers. The facility custodian came in later that day and put the empty tritium containers in the trash as well as the Chromium container (not realizing it still had the radioactive material inside).
On February 10 around 1900 EST it was discovered that the Chromium vial was missing. The licensee performed a search of the facility including radiological surveys and has concluded that the vial was likely thrown out in the trash. The trash dumpster had already been emptied by the waste management firm used by the university. The waste management firm has been notified.
It should be noted that the amount of Chromium-51 in the vial is only 5 times the 10 CFR Part 20, Appendix C limit.
THIS MATERIAL EVENT CONTAINS A "LESS THAN CAT 3" LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks.
This source is not amongst those sources or devices identified by the IAEA Code of Conduct for the Safety & Security of Radioactive Sources to be of concern from a radiological standpoint. Therefore is it being categorized as a less than Category 3 source
The RSO for the Wayne State University's School of Pharmacy reported a missing vial containing 5 millicuries of Chromium-51 in a saline solution. The vial was received at the licensee's laboratory on February 6 along with two cartons of tritium. The tritium was removed from its shipping cartons and placed in a lab storage refrigerator. The Chromium was left on a desk in the carton to be leak tested prior to being placed in the refrigerator.
Apparently, the lab student did not perform the leak test on the Chromium before leaving the lab. The carton with the Chromium vial was left on the desk near the trash can with the empty tritium containers. The facility custodian came in later that day and put the empty tritium containers in the trash as well as the Chromium container (not realizing it still had the radioactive material inside).
On February 10 around 1900 EST it was discovered that the Chromium vial was missing. The licensee performed a search of the facility including radiological surveys and has concluded that the vial was likely thrown out in the trash. The trash dumpster had already been emptied by the waste management firm used by the university. The waste management firm has been notified.
It should be noted that the amount of Chromium-51 in the vial is only 5 times the 10 CFR Part 20, Appendix C limit.
THIS MATERIAL EVENT CONTAINS A "LESS THAN CAT 3" LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks.
This source is not amongst those sources or devices identified by the IAEA Code of Conduct for the Safety & Security of Radioactive Sources to be of concern from a radiological standpoint. Therefore is it being categorized as a less than Category 3 source
Other Nuclear Material
Event Number: 44870
Rep Org: BAYER CROPSCIENCE
Licensee: BAYER CROPSCIENCE
Region: 3
City: KANSAS CITY State: MO
County: JACKSON
License #: 24-03830-01
Agreement: N
Docket: 30-05089
NRC Notified By: MARK MOENNIG
HQ OPS Officer: KARL DIEDERICH
Licensee: BAYER CROPSCIENCE
Region: 3
City: KANSAS CITY State: MO
County: JACKSON
License #: 24-03830-01
Agreement: N
Docket: 30-05089
NRC Notified By: MARK MOENNIG
HQ OPS Officer: KARL DIEDERICH
Notification Date: 02/23/2009
Notification Time: 14:56 [ET]
Event Date: 02/10/2009
Event Time: 12:00 [CST]
Last Update Date: 02/23/2009
Notification Time: 14:56 [ET]
Event Date: 02/10/2009
Event Time: 12:00 [CST]
Last Update Date: 02/23/2009
Emergency Class: NON EMERGENCY
10 CFR Section:
20.2201(a)(1)(ii) - LOST/STOLEN LNM>10X
10 CFR Section:
20.2201(a)(1)(ii) - LOST/STOLEN LNM>10X
Person (Organization):
HIRONORI PETERSON (R3)
BILL VONTILL (FSME)
THOMAS HILTZ (NMSS)
ILTAB via e-mail
HIRONORI PETERSON (R3)
BILL VONTILL (FSME)
THOMAS HILTZ (NMSS)
ILTAB via e-mail
PROBABLE LOSS OF 3.3 mCi C-14 IN TRANSIT
A package of 3.3 mCi of solid form C-14 was picked up at the Kansas City, MO facility by courier Towne Air on February 6, 2009, for shipment to Held & Associates, in Chicago, IL, for further shipping to Bayer Cropscience's research site in Wuppertal, Germany. It has not been received by Held & Associates. On February 10, the licensee inquired with Town Air regarding tracking information. Recent response indicates that recovery of the shipment and its material is considered unlikely.
This quantity is more than five orders of magnitude less than the IAEA D value.
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks.
This source is not amongst those sources or devices identified by the IAEA Code of Conduct for the Safety & Security of Radioactive Sources to be of concern from a radiological standpoint. Therefore is it being categorized as a less than Category 3 source
A package of 3.3 mCi of solid form C-14 was picked up at the Kansas City, MO facility by courier Towne Air on February 6, 2009, for shipment to Held & Associates, in Chicago, IL, for further shipping to Bayer Cropscience's research site in Wuppertal, Germany. It has not been received by Held & Associates. On February 10, the licensee inquired with Town Air regarding tracking information. Recent response indicates that recovery of the shipment and its material is considered unlikely.
This quantity is more than five orders of magnitude less than the IAEA D value.
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks.
This source is not amongst those sources or devices identified by the IAEA Code of Conduct for the Safety & Security of Radioactive Sources to be of concern from a radiological standpoint. Therefore is it being categorized as a less than Category 3 source
Hospital
Event Number: 44875
Rep Org: VA NATIONAL HEALTH PHYSICS PROGRAM
Licensee: EDWARD HINES JR VA HOSPITAL
Region: 3
City: HINES State: IL
County:
License #: 03-23853-01VA
Agreement: Y
Docket:
NRC Notified By: THOMAS HUSTON
HQ OPS Officer: BILL HUFFMAN
Licensee: EDWARD HINES JR VA HOSPITAL
Region: 3
City: HINES State: IL
County:
License #: 03-23853-01VA
Agreement: Y
Docket:
NRC Notified By: THOMAS HUSTON
HQ OPS Officer: BILL HUFFMAN
Notification Date: 02/25/2009
Notification Time: 09:50 [ET]
Event Date: 02/10/2009
Event Time: 00:00 [CST]
Last Update Date: 02/25/2009
Notification Time: 09:50 [ET]
Event Date: 02/10/2009
Event Time: 00:00 [CST]
Last Update Date: 02/25/2009
Emergency Class: NON EMERGENCY
10 CFR Section:
20.2201(a)(1)(ii) - LOST/STOLEN LNM>10X
10 CFR Section:
20.2201(a)(1)(ii) - LOST/STOLEN LNM>10X
Person (Organization):
HIRONORI PETERSON (R3)
ANGELA MCINTOSH (FSME)
HIRONORI PETERSON (R3)
ANGELA MCINTOSH (FSME)
UNPLANNED TRITIUM RELEASE DURING INCINERATION
"This report is made under 10 CFR 20.2201(a)(1)(ii). A loss of permitted material by Edward Hines Jr. VA Hospital in Hines, Illinois, became known on February 10, 2009. Approximately 54.6 millicuries of hydrogen-3 were released in animal research wastes handled as non-radioactive over a period of 15 years (1994-2008). The maximum amount released in any one year was 12.8 millicuries. These wastes were processed by incineration at off-site facilities. The activities that generated the affected wastes ended in March 2008. Hospital staff will review disposal practices for compliance before allowing similar activities.
"A written report for this event will be submitted to NRC Region III within 30 days of making this telephone notification. We have discussed with event with our NRC Project Manager (Cassandra Frazier, NRC Region III).
"Additional information:
"Department of Veterans Affairs holds NRC License No. 03-23853-01VA, a master materials license. Permits are issued under the license to Veterans Health Administration facilities. The permit number for the facility involved in these medical events is VHA Permit No. 12-01087-07. National Health Physics Program makes required notifications to NRC."
THIS MATERIAL EVENT CONTAINS A "LESS THAN CAT 3" LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks.
This source is not amongst those sources or devices identified by the IAEA Code of Conduct for the Safety & Security of Radioactive Sources to be of concern from a radiological standpoint. Therefore is it being categorized as a less than Category 3 source
"This report is made under 10 CFR 20.2201(a)(1)(ii). A loss of permitted material by Edward Hines Jr. VA Hospital in Hines, Illinois, became known on February 10, 2009. Approximately 54.6 millicuries of hydrogen-3 were released in animal research wastes handled as non-radioactive over a period of 15 years (1994-2008). The maximum amount released in any one year was 12.8 millicuries. These wastes were processed by incineration at off-site facilities. The activities that generated the affected wastes ended in March 2008. Hospital staff will review disposal practices for compliance before allowing similar activities.
"A written report for this event will be submitted to NRC Region III within 30 days of making this telephone notification. We have discussed with event with our NRC Project Manager (Cassandra Frazier, NRC Region III).
"Additional information:
"Department of Veterans Affairs holds NRC License No. 03-23853-01VA, a master materials license. Permits are issued under the license to Veterans Health Administration facilities. The permit number for the facility involved in these medical events is VHA Permit No. 12-01087-07. National Health Physics Program makes required notifications to NRC."
THIS MATERIAL EVENT CONTAINS A "LESS THAN CAT 3" LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks.
This source is not amongst those sources or devices identified by the IAEA Code of Conduct for the Safety & Security of Radioactive Sources to be of concern from a radiological standpoint. Therefore is it being categorized as a less than Category 3 source