Event Notification Report for February 01, 2009

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
01/31/2009 - 02/01/2009

EVENT NUMBERS
448214482244829

Power Reactor
Event Number: 44821
Facility: DUANE ARNOLD
Region: 3     State: IA
Unit: [1] [] []
RX Type: [1] GE-4
NRC Notified By: JEFF MIELL
HQ OPS Officer: BILL HUFFMAN
Notification Date: 02/01/2009
Notification Time: 21:28 [ET]
Event Date: 02/01/2009
Event Time: 18:00 [CST]
Last Update Date: 02/01/2009
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(iv)(B) - RPS ACTUATION - CRITICAL 50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION
Person (Organization):
PATTY PELKE (R3)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 M/R Y 53 Power Operation 0 Hot Shutdown
Event Text
MANUAL REACTOR SCRAM DUE TO LOSS OF CONDENSER COOLING

"[The licensee manually inserted a reactor scram] due to imminent loss of heat sink (condenser). Circulating water to the condenser suffered an unisolable break resulting in loss of suction source to pumps with cavitation. [The] plant was stabilized per emergency operating procedures. Containment isolations signals operated per design with Groups 2, 3, and 4 received.

"Plant response [was] complicated with [an] unexpected loss of one 161 KV bus in the switchyard. This was caused by a breaker failure lockout of the bus caused by signal from the output breaker. This output breaker did open. Cause of the breaker failure being investigated.

"[The] power loss [of the 161 KV bus] had minor plant effect. One power supply to essential service offsite transformer 1X3 [was] lost due to the bus lockout. [The] transformer and offsite circuit remained available. [The] plant did sustain a temporary loss of spent fuel pool cooling system. Cooling has been restored with no level or temperature complications.

"Essential power [remained] available with both onsite SBDG's (Standby Diesel Generators) and offsite circuits (current source). All ECCS available. All safety related equipment operat[ed] as designed, except Reactor Core Isolation Cooling (RCIC) turbine which had difficulty in automatic control. Manual control [of RCIC] was effective. This is not unexpected during the conditions it was operating (low flow)."

The licensee was shutting down to enter a refueling outage as the time of the event. Circulating water to one cooling tower had been isolated when a riser on the second cooling tower ruptured and resulted in loss of supply to the circwater pumps. All systems functioned as required except for the lockout of the 161KV bus and RCIC automatic control. Rods fully inserted. The plant is in a normal electrical configuration except for the loss of the 161 KV bus which does not supply any safety related busses. No safety relief valves lifted during the transient. Cooling is currently via HPCI and RCIC to the torus with torus cooling via essential service water.

The plant is currently stable at 600 psi and being cooled-down to cold shutdown. The NRC Resident Inspector has been notified.


Power Reactor
Event Number: 44822
Facility: OYSTER CREEK
Region: 1     State: NJ
Unit: [1] [] []
RX Type: [1] GE-2
NRC Notified By: ANDREW ZUCHOWSKI
HQ OPS Officer: BILL HUFFMAN
Notification Date: 02/01/2009
Notification Time: 23:05 [ET]
Event Date: 02/01/2009
Event Time: 21:56 [EST]
Last Update Date: 02/02/2009
Emergency Class: UNUSUAL EVENT
10 CFR Section:
50.72(a) (1) (i) - EMERGENCY DECLARED 50.72(b)(2)(iv)(B) - RPS ACTUATION - CRITICAL
Person (Organization):
WAYNE SCHMIDT (R1)
THOMAS BLOUNT (NRR)
SAM COLLNS (R1RA)
JIM WIGGINS (NRR)
ANTHONY McMURTRAY (IRD)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 A/R Y 100 Power Operation 0 Hot Shutdown
Event Text
UNUSUAL EVENT AND REACTOR SCRAM DUE TO MAIN TRANSFORMER FIRE

At 2156 EST, a fire occurred on Main Transformer M1A. The loss of the main transformer resulted in a reactor scram from full power without complications. The transformer deluge system activated. The fire brigade responded and offsite assistance from the fire department was obtained to help extinguish the fire. The fire department has since departed the site. An Unusual Event was declared at 2211 EST based on the transformer fire lasting longer than 15 minutes. The fire was extinguished at 2227 EST. A fire reflash watch was established. There was no damage to any other equipment besides the main transformer.

During the reactor scram transient, the isolation condenser actuated as expected and was subsequently secured. Four electro-magnetic relief valves actuated and reseated normally. The plant is currently in hot standby with reactor pressure at 927 psi and water level at 150 inches with all conditions stable and a normal electrical configuration.

The licensee is assessing the criteria for exiting the UE at this time. The licensee has notified State and local government agencies and the NRC Resident Inspector.

* * * UPDATE FROM ZUCHOWSKI TO HUFFMAN AT 0001 EST ON 2/02/09 * * *

The licensee terminated the UE at 2337 EST due to stable plant conditions with all entry criteria for the UE exited and no concern of reflash. The licensee did note that there is an oil sheen on the water around the transformer and indication of a small amount of oil dripping from the transformer. The licensee is taking efforts to contain the spill with spill kits and barriers.

The NRC Resident has been notified. Notified R1DO (Schmidt), R1 (Bellamy), NRR EO (Blount), and IRD (McMurtray). Informed DHS (Banner) and FEMA (Barden).

* * * UPDATE FROM FLESHER TO HUFFMAN AT 1907 EST ON 2/02/09 * * *

Upon review of the electromagnetic relief valve performance during the reactor scram at 2156 EST on 2/1/09, two electromagnetic relief valves opened - not four (as originally reported). Due to subsequent seat leakage of one electromagnetic relief valve, the valve was cycled and was able to be reseated. At 0444 EST on 2/2/09 downstream relief temperatures confirmed that the valve had reseated.

The licensee has notified the NRC Resident Inspector. R1DO (Schmidt) notified.


General Information or Other
Event Number: 44829
Rep Org: OHIO BUREAU OF RADIATION PROTECTION
Licensee: TOLEDO EDISON COMPANY
Region: 3
City: OREGON   State: OH
County:
License #: 31201490021
Agreement: Y
Docket:
NRC Notified By: STEPHEN JAMES
HQ OPS Officer: DONALD NORWOOD
Notification Date: 02/05/2009
Notification Time: 09:26 [ET]
Event Date: 02/01/2009
Event Time: 00:00 [EST]
Last Update Date: 02/05/2009
Emergency Class: NON EMERGENCY
10 CFR Section:
Person (Organization):
MARK RING (R3)
ANGELA MCINTOSH (FSME)
Event Text
AGREEMENT STATE REPORT - STUCK SHUTTER ON FIXED GAUGE DEVICE

The following report was received from the State via E-mail:

"Licensee reported a stuck shutter on a fixed gauge, which was discovered during the leak test and shutter check maintenance activity. Licensee stated that shutter had been difficult to move on past checks, but had neglected to have unit serviced. Licensee has contacted service provider to repair shutter mechanism. Device normally operates in continuous mode, so no additional actions are required at this time.

"Ohio will leave this report open pending receipt of final written report from licensee, due in 30 days.

"Note: Licensee stated that they were making this report as a result of awareness of requirements found in Ohio Information Notice 2008-02 regarding fixed gauge stuck shutters and reporting requirements."

This was an Ohmart Corporation model number SH-1 fixed gauge device. There is 0.005 Ci Cs-137 in this device.

The Ohio State reference number for this report is OH 2009-003.