Event Notification Report for December 15, 2008

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
12/14/2008 - 12/15/2008

EVENT NUMBERS
447214472344973

Power Reactor
Event Number: 44721
Facility: WATTS BAR
Region: 2     State: TN
Unit: [1] [] []
RX Type: [1] W-4-LP,[2] W-4-LP
NRC Notified By: KEVIN CASEY
HQ OPS Officer: HOWIE CROUCH
Notification Date: 12/15/2008
Notification Time: 15:40 [ET]
Event Date: 12/15/2008
Event Time: 13:33 [EST]
Last Update Date: 12/15/2008
Emergency Class: NON EMERGENCY
10 CFR Section:
26.719 - FITNESS FOR DUTY
Person (Organization):
MIKE ERNSTES (R2)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
Event Text
FITNESS FOR DUTY REPORT

A non-licensed employee supervisor had a confirmed positive for illegal drugs during a random fitness-for-duty test. The employee's access to the plant has been terminated. Contact the Headquarters Operations Officer for additional details.

The licensee has notified the NRC Resident Inspector.


!!!!! THIS EVENT HAS BEEN RETRACTED !!!!!
!!!!! THIS EVENT HAS BEEN RETRACTED !!!!!
Power Reactor
Event Number: 44723
Facility: MONTICELLO
Region: 3     State: MN
Unit: [1] [] []
RX Type: [1] GE-3
NRC Notified By: WILLIAM STANG
HQ OPS Officer: JASON KOZAL
Notification Date: 12/15/2008
Notification Time: 22:47 [ET]
Event Date: 12/15/2008
Event Time: 16:16 [CST]
Last Update Date: 02/06/2009
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(ii)(B) - UNANALYZED CONDITION
Person (Organization):
RICHARD SKOKOWSKI (R3)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
Event Text
UNANALYZED CONDITION DUE TO STEAM CHASE TEMPERATURE GREATER THAN 165F

"At 1616 on 12/15/08, a plant heating boiler trip resulted in a loss of a reactor building ventilation. The loss of reactor building ventilation resulted in maximum average main steam chase temperatures greater than or equal to 165F. High energy line break (HELB) analysis of piping in the steam chase assumes an initial average temperature prior to the break of 165F. Temperature greater than or equal to 165F in the steam chase challenges EQ qualification of the piping analysis. Abnormal procedures for loss heating boiler and ventilation system failure were entered. C.3 (Shutdown) and C.5-1300 (secondary containment control) were also entered. The plant heating boiler was restarted and ventilation restored prior to power reduction. All systems have been returned to normal."

The licensee notified the NRC Resident Inspector.

* * * RETRACTION PROVIDED FROM DAVID BARNETT TO JOE O'HARA AT 1158 ON 2/6/09 * * *

The licensee is retracting this report based on the following:

"Monticello is retracting the event reported based on further evaluation, which found that the issue was not an unanalyzed condition that seriously degraded plant safety. The investigation of the event found the peak temperature achieved was 167.2 degrees F and the condition lasted for approximately 11 minutes. Engineering review of Safety System Components found no impact on the equipment for the temperature reached, Additionally, revised High Energy Line Break (HELB) calculations performed with an initial average Steam Chase Room temperature of 180 degrees F before a HELB determined that Safety System components could perform their safety functions. The station has identified the cause for the event and corrective actions will be tracked in the station's corrective action program.

"Since there was no impact on the equipment in either Environmental Qualification (EQ) or safety function, the temperature of the event was less than the revised calculation temperature, and the unanalyzed condition that existed in the initial event notification report no longer exists and did not result in a condition that seriously degraded plant safety, this event can be retracted."

The licensee informed the NRC Resident Inspector. Notified R3DO (Ring).


General Information or Other
Event Number: 44973
Rep Org: OHIO BUREAU OF RADIATION PROTECTION
Licensee: UNIVERSITY HOSPITALS OF CLEVELAND
Region: 3
City: CLEVELAND   State: OH
County:
License #: 02110180077
Agreement: Y
Docket:
NRC Notified By: STEPHEN JAMES
HQ OPS Officer: JOE O'HARA
Notification Date: 04/06/2009
Notification Time: 13:00 [ET]
Event Date: 12/15/2008
Event Time: 00:00 [EDT]
Last Update Date: 04/06/2009
Emergency Class: NON EMERGENCY
10 CFR Section:
Person (Organization):
ROBERT DALEY (R3)
ANGELA MCINTOSH (FSME)
Event Text
INCIDENT INVOLVING CO-60 GAMMA KNIFE DURING PATIENT TREATMENT

The following information was provided by the state via e-mail:

"During an inspection on March 17 through 19, 2009, the ODH [Ohio Department of Health] inspector identified through the licensee's radiation safety committee meeting minutes an incident involving the Co-60 Gamma Knife that occurred on December 15, 2008, at approximately 2:15 pm. During a patient treatment, the couch moved out of treatment position. The emergency stop button was activated and the system did not respond. The licensee's staff had to manually pull out the couch from the Gamma Knife and manually close the doors to the Gamma Knife to shield the source.

"According to the licensee, radiation exposure to all individuals involved with the incident was minimal. The incident DID NOT result in a medical event for the patient. The manufacturer (Elekta) was immediately contacted and the Gamma Knife was repaired. Patient treatment was resumed and completed without incident. According to Elekta, the Gamma Knife system experienced an illegal couch sensor error due to a known software bug problem.

"The licensee failed to notify the Ohio Department of Health, Bureau of Radiation Protection of this device failure and therefore this is determined to be non-compliant with the provisions of rule 3701:1-40-20 (B)(2)(a,b,c) of the Ohio Administrative Code."

Ohio State Reference Number: OH 2009-008