Skip to main content

Event Notification Report for November 30, 2008

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
11/29/2008 - 11/30/2008

EVENT NUMBERS
4468944706

Power Reactor
Event Number: 44689
Facility: COOPER
Region: 4     State: NE
Unit: [1] [] []
RX Type: [1] GE-4
NRC Notified By: ROY GILES
HQ OPS Officer: JOHN KNOKE
Notification Date: 11/30/2008
Notification Time: 08:22 [ET]
Event Date: 11/30/2008
Event Time: 01:58 [CST]
Last Update Date: 11/30/2008
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(v)(D) - ACCIDENT MITIGATION
Person (Organization):
CLAUDE JOHNSON (R4)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
Event Text
ACCIDENT MITIGATION - CREFS INOPERABLE

"On 30 November 08 at 0158, the Control Room Emergency Filtration System (CREFS) was declared inoperable due to a degraded Control Room Envelope (CRE). A CRE boundary door was found to be stuck partially open. With this door not fully closed and latched, reasonable assurance that CREFS would fulfill its safety function could not be established.

"The CRE door is a support features for CREFS at CNS. This is a single train system and per 10CFR50.72(b)(3)(v)(D) an 8 hour report is required due to the fact that at the time of discovery this condition could have prevented the fulfillment of the safety function of an SSC [Structure, System & Components] that is required to mitigate the consequences of an accident.

"The door was returned to a fully closed and latched position at the time of discovery, and CREFS was returned to operable status. Administrative controls are in place to ensure the door closes and latches until repairs can be performed."

The licensee notified the NRC Resident Inspector.


General Information or Other
Event Number: 44706
Rep Org: NC DIV OF RADIATION PROTECTION
Licensee: UNIMIN CORPORTATION
Region: 1
City: SPRUCE PINE   State: NC
County:
License #: 061-0695-1
Agreement: Y
Docket:
NRC Notified By: CLIFF HARRIS
HQ OPS Officer: JASON KOZAL
Notification Date: 12/09/2008
Notification Time: 13:48 [ET]
Event Date: 11/30/2008
Event Time: 00:00 [EST]
Last Update Date: 12/09/2008
Emergency Class: NON EMERGENCY
10 CFR Section:
Person (Organization):
RONALD BELLAMY (R1)
ANGELA MCINTOSH (FSME)
Event Text
AGREEMENT STATE - FIRE IN MANUFACTURING FACILITY CONTAINING FIXED NUCLEAR GAUGES

"N.C. Radiation Protection Section has confirmed the N.C. Division of Emergency Management and local law enforcement were included in initial notifications and remain engaged in the ongoing event evaluation.

"N.C. Radiation Protection Section was notified on 30 November 08 by an unrecorded source from UNIMIN Corporation that there was a major fire in one of their mineral processing facilities in Spruce Pine, NC. Initial reports from the licensee indicate four industrial nuclear gauges containing Cs-137 sealed sources (3 gauges contain 2 mCi each and the fourth contains 50 mCi) were present in the facility at the time of the fire. The damage to the facility exceeds $200,000 and the facility will be out of operation for over one week, so this incident is a reportable event under NC Code 15A NCAC 11.1646(a)(3) & (4).

"Command of the site was taken by the Bureau of Alcohol, Tobacco and Firearms (for fire investigation). Preliminary radiation surveys of the exterior of the facility indicated radiation levels equivalent to background. An inspector from N.C. Radiation Protection was dispatched to the scene on 4 December 08, but was not allowed access to the interior of the facility or to any records maintained by the RSO of UNIMIN Corporation. The inspector was allowed to examine and survey the exterior of the affected facility; he found the structural damage to be significant and that radiation levels about the perimeter of the affected facility were background. The UNIMIN RSO has been able to visually identify three of the four gauges from a vantage point exterior to the facility. Security at this facility is adequate.

"The investigation will be continued on 12/9 or 12/10 by the inspector from the N.C. Radiation Protection Section."

North Carolina Report # NC-08-51.