Event Notification Report for November 18, 2008

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
11/17/2008 - 11/18/2008

EVENT NUMBERS
4467844664

Other Nuclear Material
Event Number: 44678
Rep Org: NOAA
Licensee: NOAA
Region: 4
City: IDAHO FALLS   State: ID
County:
License #: 05-11997-01
Agreement: N
Docket:
NRC Notified By: RHONDA CARPENTER
HQ OPS Officer: MARK ABRAMOVITZ
Notification Date: 11/21/2008
Notification Time: 18:04 [ET]
Event Date: 11/18/2008
Event Time: 00:00 [MST]
Last Update Date: 11/21/2008
Emergency Class: NON EMERGENCY
10 CFR Section:
20.1906(d)(1) - SURFACE CONTAM LEVELS > LIMITS
Person (Organization):
CHUCK CAIN (R4)
TERRENCE REIS (FSME)
Event Text
LEAKING SEALED SOURCE

"On the morning of Nov. 18, 2008, routine semiannual ECD [Electron Capture Device] leak tests were conducted in the FRD [Field Research Division] laboratory at 1750 Foote Dr., Idaho Falls, ID. A wipe test on the inlets and outlets of the above source showed the presence of 0.011 microcuries of contamination. The wipe was counted on a Ludlum 3030 Alpha Beta Sample Counter that was specifically calibrated for Ni-63 by the Idaho National Laboratory Health Physics Instrumentation Laboratory. Annual calibration was completed on Nov. 12, 2008. The limit of detection for the instrument was calculated as 0.00031 microcurie of Ni-63.

"When the high count was observed, the smear was immediately sealed in a ziplock plastic bag. The work area where the wipe was done was immediately checked for contamination. Tools (tweezers, pens, notepad) used, table tops, gloves, and the Ludlum instrument itself were wiped with smears and each one counted. The counts on all smears were much less than the instrument limit of detection indicating zero activity.

"Once it was established that no measurable contamination was present in the environment, steps were taken to isolate the detector. Immediately after the wipe test was completed, all inlets and outlets were recapped and the detector replaced in the locked cabinet where it had been stored. The detector was then removed from the cabinet again and all six sides of the rectangular housing were wiped with a smear. This was counted and showed zero activity indicating that no contamination was on the outside of the detector housing. The detector was placed in a plastic ziplock bag and put in a paint can. The plastic bag containing the smear that counted high was also placed in the can. The can was closed and the outside wiped and counted, again showing zero activity. Further wipe tests were then conducted on the inside of the storage cabinet where the detector was stored, the tables around the gas chromatograph (GC) where the detector was last used and the interior surfaces of the GC. All counts indicated zero activity. Based on these contamination tests, we believe that all leakage is contained within the device which is isolated in the paint can. There was no exposure to the public and neglible exposure to the personnel conducting the leak tests.

"The detector had been taken out of service on August 23, 2007. It had passed all wipe tests prior to that date. The detector remains in the paint can in a locked metal cabinet inside the FRD laboratory. It will remain out of service until it can be repaired. We have contacted the manufacturer and other companies and are investigating options for repair of the unit.

"Source identification: Valco model 140BN Electron Capture Detector (ECD), serial number N206 (General License device, Sealed Source Registry No. TX-658-D-102-G, 5 millicuries Ni-63)"


!!!!! THIS EVENT HAS BEEN RETRACTED !!!!!
!!!!! THIS EVENT HAS BEEN RETRACTED !!!!!
Fuel Cycle Facility
Event Number: 44664
Facility: PADUCAH GASEOUS DIFFUSION PLANT
Region: 2     State: KY
Unit: [] [] []
RX Type: URANIUM ENRICHMENT FACILITY
Comments: 2 DEMOCRACY CENTER
6903 ROCKLEDGE DRIVE
BETHESDA, MD 20817 (301)564-3200
NRC Notified By: KEVIN BEASLEY
HQ OPS Officer: MARK ABRAMOVITZ
Notification Date: 11/18/2008
Notification Time: 13:19 [ET]
Event Date: 11/18/2008
Event Time: 03:08 [CST]
Last Update Date: 11/21/2008
Emergency Class: NON EMERGENCY
10 CFR Section:
76.120(c)(2) - SAFETY EQUIPMENT FAILURE
Person (Organization):
BRIAN BONSER (R2)
BRIAN SMITH (NMSS)
Event Text
FIRE WATER SPRINKLER SYSTEM OUT OF SERVICE

"At 0308 CST, on 11/18/2008, the Plant Shift Superintendent was notified that the C-337 High Pressure Fire Water (HPFW) Sprinkler System D-9 had been inspected by Fire Services and six sprinkler heads had visible corrosion on them. The system configuration was evaluated using EN-C-822-99-047, 'Effects of Impaired Sprinkler Heads on System Operability' and determined that with these heads impaired, a portion of the building would not have sufficient sprinkler coverage. The HPFW system is required to be operable according to TSR LCO 2.4.4.5. HPFW system D-9 was declared inoperable and TSR LCO 2.4.4.5 Required Action B was implemented for the area without sprinkler coverage. Based on past testing results, there is a possibility that the heads would have been able to perform their specified safety function. Once the heads are removed from the system, testing will be performed to determine the true affect on operability.

"This event is reportable under 10 CFR 76.120(c)(2) as an event in which equipment required by the TSR is disabled or fails to function as designed.

"The NRC Senior Resident Inspector has been notified of this event."

The site has implemented hourly fire patrols while this impairment is in affect.

* * * RETRACTION FROM TONY HUDSON TO HOWIE CROUCH @1536 EST ON 11/21/08 * * *

"The affected sprinkler heads were removed and subjected to testing in the plant laboratory. A total of nine heads (three of these heads were previously identified with corrosion) were removed and tested with five of the nine actuating as designed. Using these results, the plant's fire protection engineer concluded that adequate sprinkler coverage existed prior to the discovery and the system would have performed as designed to a fire demand."

The licensee has notified the NRC Resident Inspector. Notified R2DO (Guthrie) and NMSS EO (Smith).