Event Notification Report for October 31, 2008
U.S. Nuclear Regulatory Commission
Operations Center
EVENT REPORTS FOR
10/30/2008 - 10/31/2008
EVENT NUMBERS
44618
Power Reactor
Event Number: 44618
Facility: MCGUIRE
Region: 2 State: NC
Unit: [1] [] []
RX Type: [1] W-4-LP,[2] W-4-LP
NRC Notified By: MICHAEL RICHARDSON
HQ OPS Officer: JOHN KNOKE
Region: 2 State: NC
Unit: [1] [] []
RX Type: [1] W-4-LP,[2] W-4-LP
NRC Notified By: MICHAEL RICHARDSON
HQ OPS Officer: JOHN KNOKE
Notification Date: 10/31/2008
Notification Time: 13:45 [ET]
Event Date: 10/31/2008
Event Time: 12:52 [EDT]
Last Update Date: 10/31/2008
Notification Time: 13:45 [ET]
Event Date: 10/31/2008
Event Time: 12:52 [EDT]
Last Update Date: 10/31/2008
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION
10 CFR Section:
50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION
Person (Organization):
DEBORAH SEYMOUR (R2)
DEBORAH SEYMOUR (R2)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 1 | M/R | N | 0 | Hot Standby | 0 | Hot Standby |
MANUAL REACTOR TRIP DUE TO ROD CONTROL MALFUNCTION
"Initial conditions: Low Power Physics Testing after outage. Performing Dynamic Rod Worth measurements. Single dropped rod (K-2) on Control Bank B occurred after movement disagreement between rod groups. Entered AP-14, 'Rod Control Malfunction'. Performed a manual reactor trip and manual start of Auxiliary Feedwater as directed by Normal Operating Procedures for unit shutdown. Feedwater isolation occurred due to Low T-Ave concurrent with reactor trip."
All control rods were fully inserted.
Licensee has notified NRC Resident Inspector.
"Initial conditions: Low Power Physics Testing after outage. Performing Dynamic Rod Worth measurements. Single dropped rod (K-2) on Control Bank B occurred after movement disagreement between rod groups. Entered AP-14, 'Rod Control Malfunction'. Performed a manual reactor trip and manual start of Auxiliary Feedwater as directed by Normal Operating Procedures for unit shutdown. Feedwater isolation occurred due to Low T-Ave concurrent with reactor trip."
All control rods were fully inserted.
Licensee has notified NRC Resident Inspector.