Skip to main content

Event Notification Report for October 31, 2008

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
10/30/2008 - 10/31/2008

EVENT NUMBERS
44618

Power Reactor
Event Number: 44618
Facility: MCGUIRE
Region: 2     State: NC
Unit: [1] [] []
RX Type: [1] W-4-LP,[2] W-4-LP
NRC Notified By: MICHAEL RICHARDSON
HQ OPS Officer: JOHN KNOKE
Notification Date: 10/31/2008
Notification Time: 13:45 [ET]
Event Date: 10/31/2008
Event Time: 12:52 [EDT]
Last Update Date: 10/31/2008
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION
Person (Organization):
DEBORAH SEYMOUR (R2)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 M/R N 0 Hot Standby 0 Hot Standby
Event Text
MANUAL REACTOR TRIP DUE TO ROD CONTROL MALFUNCTION

"Initial conditions: Low Power Physics Testing after outage. Performing Dynamic Rod Worth measurements. Single dropped rod (K-2) on Control Bank B occurred after movement disagreement between rod groups. Entered AP-14, 'Rod Control Malfunction'. Performed a manual reactor trip and manual start of Auxiliary Feedwater as directed by Normal Operating Procedures for unit shutdown. Feedwater isolation occurred due to Low T-Ave concurrent with reactor trip."

All control rods were fully inserted.

Licensee has notified NRC Resident Inspector.