Skip to main content

Event Notification Report for October 05, 2008

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
10/04/2008 - 10/05/2008

EVENT NUMBERS
44541

Power Reactor
Event Number: 44541
Facility: HOPE CREEK
Region: 1     State: NJ
Unit: [1] [] []
RX Type: [1] GE-4
NRC Notified By: DAVID HALL
HQ OPS Officer: HOWIE CROUCH
Notification Date: 10/05/2008
Notification Time: 12:17 [ET]
Event Date: 10/05/2008
Event Time: 04:31 [EDT]
Last Update Date: 10/05/2008
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(v)(D) - ACCIDENT MITIGATION
Person (Organization):
JOHN WHITE (R1)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
Event Text
HIGH PRESSURE COOLANT INJECTION (HPCI) SYSTEM INOPERABLE

"During repair activities associated with the HPCI NUMAC [Nuclear Measurement Analysis And Control] display, the NUMAC drawer failed upon restoration of power. The drawer failure resulted in HPCI isolation signal and [HPCI] turbine trip signal. At the time the HPCI isolation valve was de-energized as planned so the isolation did not occur, but the failure mode resulted in a [HPCI] turbine trip signal, which resulted in an unavailability and inoperability of HPCI. The condition existed for 29 minutes during maintenance activities. Repair activities were unsuccessful and the NUMAC is still inoperable."

The event occurred during the restoration of the HPCI steam leak detection system.

The licensee will be notifying the NRC Resident Inspector.