Event Number: 44238
Facility: MILLSTONE
Region: 1     State: CT
Unit: [] [2] []
RX Type: [1] GE-3,[2] CE,[3] W-4-LP
NRC Notified By: MARIA GHARAKHANIAN
HQ OPS Officer: PETE SNYDER
Notification Date: 05/24/2008
Notification Time: 10:03 [ET]
Event Date: 05/24/2008
Event Time: 09:54 [EDT]
Last Update Date: 05/25/2008
Emergency Class: UNUSUAL EVENT
10 CFR Section:
50.72(a) (1) (i) - EMERGENCY DECLARED 50.72(b)(2)(iv)(B) - RPS ACTUATION - CRITICAL
Person (Organization):
MEL GRAY (R1)
WILLIAM GOTT (IRD)
FREDERICK BROWN (NRR)
ERIC LEEDS (NRR)
MARC DAPAS (R1)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 N Y 1 Startup 0 Hot Standby
Event Text
LOSS OF OFFSITE POWER

The licensee entered an Unusual Event after an automatic reactor trip due to a loss of offsite power per EAL Designation PU-1. Currently the plant is stable in Mode 3 with power being supplied to the "A" & "B" Emergency Diesel Generators (EDG) running supplying power to the safety buses. Decay heat is being removed by the motor driven Auxiliary Feedwater Pump supplying water to the steam generators exhausting to atmosphere via atmospheric relief valves. There are no primary to secondary tube leaks.

NRC Resident Inspector has been notified.

* * * UPDATE FROM SKIP JORDAN TO JOHN KNOKE AT1252 EDT ON 05/25/08 * * *

At 1252 EDT the licensee terminated from their Unusual Event. After the loss of offsite power due to a failure of the Reserve Station Service Transformer (RSST) the licensee began to troubleshoot the problem as well as beginning to restore offsite power. At 1106 on 5/24/08 a cross-tie from Unit 3 was connected to Unit 2 and "A" EDG was secured. At 0950 on 5/25/08 the RSST was powered up and the non-vital busses were energized. At 1136 the "B" and "D" Reactor Coolant Pumps were started. At 1230 the vital bus was energized and the "A" EDG was secured.

The licensee notified the NRC Resident Inspector. Notifications to: R1 (Marc Dupas, David Lew), R1DO (Mel Gray), NRR EO (Fred Brown), IRD MOC (William Gott), DHS (Fred Hill), FEMA (Dan Sullivan), USDA (Amanda Jimenez,), HHS (Mason Pyle), DOE (Julia Muse).

The NRC Resident Inspector was notified.


Power Reactor
Event Number: 44239
Facility: BEAVER VALLEY
Region: 1     State: PA
Unit: [] [2] []
RX Type: [1] W-3-LP,[2] W-3-LP
NRC Notified By: MICHAEL MOUSER
HQ OPS Officer: JOE O'HARA
Notification Date: 05/24/2008
Notification Time: 15:06 [ET]
Event Date: 05/24/2008
Event Time: 09:38 [EDT]
Last Update Date: 05/28/2008
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION
Person (Organization):
MEL GRAY (R1)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 N Y 15 Power Operation 15 Power Operation
Event Text
STEAM GENERATOR LEVEL EXCURSION

"On 5/24/2008 at 0938, with Beaver Valley Power Station Unit 2 (BVPS U2) in Mode 1 at 15% power during preparations for turbine startup, the unit experienced a steam generator level excursion. Attempts to manually control steam generator water level were unsuccessful.

"Steam Generator narrow range levels exceeded the setpoint for P-14, Steam Generator Level High High Turbine Trip. The actuation of P-14 automatically actuated the following: trip of the running Main Feedwater pump, closure of the Main and Bypass Feedwater regulating valves, and closure of the Feedwater Containment isolation valves. In addition to these signals, a turbine trip signal is generated but the turbine was not yet on-line.

"The feedwater isolation signal has been reset and normal feedwater flow has been established. Preliminary investigation has revealed that a broken air line caused the 'A' Main Feedwater pump recirculation flow control valve to fail open. This initiated the steam generator level transient. Additional investigation is in progress.

"The trip of the Main Feedwater pumps automatically started both Motor Driven Auxiliary Feedwater pumps (MDAFW). The automatic start of the MDAFW pumps from this valid system actuation is reportable under 10CFR50.72(b)(3)(iv)(A).

"The plant is currently stable in Mode 1 at 15% reactor power." AFW injected into the core.

The licensee notified the NRC Resident Inspector.

* * * UPDATE FROM MORGAN TO SNYDER ON 5/28/08 * * *

The last sentence of the original report text should read "AFW injected into the Steam Generators" since AFW does not inject into the core.