Skip to main content

Event Notification Report for April 09, 2008

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
04/08/2008 - 04/09/2008

EVENT NUMBERS
441304413644260

Power Reactor
Event Number: 44130
Facility: DRESDEN
Region: 3     State: IL
Unit: [] [2] [3]
RX Type: [1] GE-1,[2] GE-3,[3] GE-3
NRC Notified By: GLEN MORROW
HQ OPS Officer: JEFF ROTTON
Notification Date: 04/09/2008
Notification Time: 18:46 [ET]
Event Date: 04/09/2008
Event Time: 16:15 [CDT]
Last Update Date: 04/09/2008
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(xiii) - LOSS COMM/ASMT/RESPONSE
Person (Organization):
ANNE MARIE STONE (R3)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 N Y 98 Power Operation 98 Power Operation
3 N Y 98 Power Operation 98 Power Operation
Event Text
LOSS OF ALL ENS TELEPHONE LINES ON SITE AFTER MAINTENANCE

"Following maintenance on the FTS phone system and a successful test of the ENS phone, the ENS phone system failed. Normal commercial phone lines are still functioning and will be used for any required notifications. Repair personnel have been contacted and are expediting repairs."

The maintenance performed earlier affected the FTS lines inside the licensee's area of responsibility and the 942 commercial exchange.

The licensee notified the NRC Resident Inspector. The licensee will be notifying the state of Illinois.


General Information or Other
Event Number: 44136
Rep Org: MISSISSIPPI DIV OF RAD HEALTH
Licensee: CARDINAL HEALTH
Region: 4
City:   State: MS
County: HOLMES
License #: MS-493-01
Agreement: Y
Docket:
NRC Notified By: BOBBY SMITH
HQ OPS Officer: BILL HUFFMAN
Notification Date: 04/14/2008
Notification Time: 10:02 [ET]
Event Date: 04/09/2008
Event Time: 07:00 [CDT]
Last Update Date: 04/14/2008
Emergency Class: NON EMERGENCY
10 CFR Section:
Person (Organization):
JEFFREY CLARK (R4)
MICHELE BURGESS (FSME)
Event Text
AGREEMENT STATE - MISSISSIPPI - TRAFFIC ACCIDENT INVOLVING TRUCK CARRYING TC-99M

The State provided the following information via email:

"DRH [Mississippi Division of Radiological Health] received a phone call from Cardinal Health RSO on 4-9-08 about a transportation accident involving one of their transport vehicles and an 18 wheeler on Hwy 49 South near Tchula, MS. The accident happened around 7:00 AM. The Cardinal driver had already made his deliveries to the facilities and only had the return packages (used doses) from the day before. According to RSO, driver hit the rear of the 18 wheeler after he made a sudden stop on the highway. According to RSO, all packages stayed secured and braced and their was no contamination or contents spilled out of the packages. Another driver was in route to location to pick up the other driver and the radioactive packages to return them to the Flowood facility."

The material being transported was used doses of Tc-99m and there was no spillage or cleanup required.

MS Report No. MS-493-01


Power Reactor
Event Number: 44260
Facility: LIMERICK
Region: 1     State: PA
Unit: [1] [] []
RX Type: [1] GE-4,[2] GE-4
NRC Notified By: MARK ARNOSKY
HQ OPS Officer: HOWIE CROUCH
Notification Date: 06/03/2008
Notification Time: 12:50 [ET]
Event Date: 04/09/2008
Event Time: 04:16 [EDT]
Last Update Date: 06/03/2008
Emergency Class: NON EMERGENCY
10 CFR Section:
50.73(a)(1) - INVALID SPECIF SYSTEM ACTUATION
Person (Organization):
PAMELA HENDERSON (R1)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
Event Text
60-DAY OPTIONAL NOTIFICATION FOR INVALID SPECIFIED SYSTEM ACTUATION

"On Wednesday April 9, 2008 at 0416 hours, an invalid actuation of the 1B Refueling Floor Ventilation Exhaust Radiation Monitor occurred. The actuation caused a Division 2 Group 6C isolation signal, which caused primary containment isolation valves (PCIVs) to automatically close on the Containment Leak Detector Radiation Monitor (10-S182) and the Drywell Hydrogen/Oxygen Analyzer (10-S205). The 1A, 1C, and 1D channels were unaffected and indicated normal ventilation exhaust radiation levels during the event.

"The cause of the event was a failure of the K2 relay in the 1B Refueling Floor Ventilation Exhaust Radiation Monitor. The failed relay has been replaced and the radiation monitor was declared operable on Wednesday April 9, 2008 at 2024 hours.

"The portion of the primary containment isolation system that received an actuation signal functioned successfully. All of the affected open isolation valves automatically closed. The only equipment malfunction during the event was the failed K2 relay. The Division 2 Group 6C isolation was a partial actuation.

"This event is reportable per 10CFR50.73(a)(2)(iv)(A) since isolation valves for the Containment Leak Detector Radiation Monitor and Drywell Hydrogen/Oxygen Analyzer automatically closed due to an invalid signal."

The licensee has notified the NRC Resident Inspector.