Skip to main content

Event Notification Report for March 23, 2008

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
03/22/2008 - 03/23/2008

EVENT NUMBERS
44089

Power Reactor
Event Number: 44089
Facility: INDIAN POINT
Region: 1     State: NY
Unit: [2] [] []
RX Type: [2] W-4-LP,[3] W-4-LP
NRC Notified By: JOHN DIGNAM
HQ OPS Officer: JOHN KNOKE
Notification Date: 03/24/2008
Notification Time: 01:56 [ET]
Event Date: 03/23/2008
Event Time: 22:16 [EDT]
Last Update Date: 03/24/2008
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(iv)(B) - RPS ACTUATION - CRITICAL 50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION
Person (Organization):
NEIL PERRY (R1)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 M/R Y 94 Power Operation 0 Hot Standby
Event Text
MANUAL REACTOR TRIP - LOSS OF SPEED ON MBFP

"The Indian Point Unit 2 reactor was manually tripped from 94% power at 2216 on 3/23/08 due to a loss of speed on 22 main boiler feed pump (MBFP). Indian Point Unit 2 is currently in mode 3 with all automatic actions for a manual reactor trip occurring as required. Indian Point Unit 2 was in a coast down in advance of a scheduled refueling outage.

"The reactor was manually tripped as required by abnormal operating procedure 2-AOP-FW-001. All control rods inserted on the trip. No safety or relief valves lifted due to the trip. The motor driven aux feedwater pumps automatically started on low steam generator level and are being used to maintain steam generator level. Condenser steam dumps are maintaining reactor temperature. The Unit 2 electrical lineup is the normal shutdown electrical lineup. The licensee has notified the state Public Service Commission.

"Unit 3 was unaffected and remains in mode 1 at 100% power."

The licensee has notified the NRC Resident Inspector. The licensee expects to issue a media release.