Event Notification Report for January 23, 2008

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
01/22/2008 - 01/23/2008

EVENT NUMBERS
439244392543926439274392843929

Power Reactor
Event Number: 43924
Facility: TURKEY POINT
Region: 2     State: FL
Unit: [] [4] []
RX Type: [3] W-3-LP,[4] W-3-LP
NRC Notified By: EIRC JUERGENS
HQ OPS Officer: PETE SNYDER
Notification Date: 01/23/2008
Notification Time: 01:42 [ET]
Event Date: 01/23/2008
Event Time: 00:10 [EST]
Last Update Date: 01/23/2008
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(xiii) - LOSS COMM/ASMT/RESPONSE
Person (Organization):
BINOY DESAI (R2)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
4 N Y 100 Power Operation 100 Power Operation
Event Text
EMERGENCY RESPONSE DATA SYSTEM UNAVAILABLE

"On 1/23/08 at 0010 the Unit 4 Emergency Response Data Acquisition and Display System (ERDADS) was noted to be not functioning. Reboot was attempted several times prior to achieving success. During this timeframe a loss of the ability to supply Emergency Response Data System (ERDS) data existed for greater than 30 minutes. This is also an ERDADS failure that was not corrected within 30 minutes. These fall into a 'major loss of emergency assessment capability' 10 CFR 50.72 (b) (3) (xiii). The system was restored 1/23/08 at 0045."

The licensee notified the NRC Resident Inspector.


General Information or Other
Event Number: 43925
Rep Org: OR DEPT OF HEALTH RAD PROTECTION
Licensee: TUALITY COMMUNITY HOSPITAL
Region: 4
City: TUALATIN   State: OR
County:
License #: ORE-90283
Agreement: Y
Docket:
NRC Notified By: TERRY LINDSEY
HQ OPS Officer: JOHN KNOKE
Notification Date: 01/23/2008
Notification Time: 14:08 [ET]
Event Date: 01/23/2008
Event Time: 09:00 [PST]
Last Update Date: 01/23/2008
Emergency Class: NON EMERGENCY
10 CFR Section:
Person (Organization):
CLAUDE JOHNSON (R4)
JOSEPH HOLONICH (FSME)
Event Text
AGREEMENT STATE REPORT - THREE PATIENTS POSSIBLY EXPOSED TO ALPHA EMITTER

"Licensee notified state that Tuality Community Hospital had 3 patients with possible exposure through inhalation of Thorium, Selenium, Zinc Oxide, Zinc Hydrate, Hydrogen Seleniate. [Licensee is] concerned about potential for Alpha particle exposure and requested assistance contact information. [State] provided REAC/TS contact information."

The state will be providing additional information when licensee provides it.

Oregon Incident Report #08-0005


General Information or Other
Event Number: 43926
Rep Org: ARIZONA RADIATION REGULATORY AGENCY
Licensee: ACURA ENGINEERING ARIZONA, INC
Region: 4
City: PHOENIX   State: AZ
County:
License #: AZ-7550
Agreement: Y
Docket:
NRC Notified By: AUBREY GODWIN
HQ OPS Officer: JOHN KNOKE
Notification Date: 01/23/2008
Notification Time: 17:50 [ET]
Event Date: 01/23/2008
Event Time: 11:30 [MST]
Last Update Date: 02/19/2008
Emergency Class: NON EMERGENCY
10 CFR Section:
Person (Organization):
CLAUDE JOHNSON (R4)
JOSEPH HOLONICH (FSME)
ILTAB (EMAIL)
MEXICO (FAX)
Event Text
AGREEMENT STATE REPORT - STOLEN TROXLER GAUGE

The State provided the following information via email:

"At approximately 11:30 AM January 23, 2008, the Agency was informed that the Licensee had a Instro Tek Model 3500, SN 599, portable moisture/density gauge stolen from the back of a truck. The theft occurred at approximately 6:00 AM . The gauge was locked with a chain in the bed of the truck which was parked unattended at an employee's residence. The gauge contains 11 mCi (408 MBq) of Cesium-137 and 44 mCi (1.63 GBq) Am:Be-241. The Licensee is offering a $500.00 reward for the recovery of the source. A press release will be made.

"Glendale PD is investigating and has issued report number 08-8332.

"The Agency [State] continues to investigate the circumstances regarding this theft for the source. The states of CA, NV, CO, UT, and NM and Mexico and U.S. NRC and FBI are being notified of this event."

* * * UPDATE BY AUBREY GODWIN TO JASON KOZAL ON 02/19/08 AT 1103 EST * * *

"The device was recovered from a Pawn Shop in Phoenix, AZ after being advertised on e-Bay. The Pawn Shop Owner indicated the device was not opened but it was not secured. The investigation continues."

Notified R4DO (Miller), FSME (Burgess), ILTAB (e-mail), Mexico (Fax)

THIS MATERIAL EVENT CONTAINS A "LESS THAN CAT 3" LEVEL OF RADIOACTIVE MATERIAL

Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks.


Power Reactor
Event Number: 43927
Facility: RIVER BEND
Region: 4     State: LA
Unit: [1] [] []
RX Type: [1] GE-6
NRC Notified By: THOMAS LAPORTE
HQ OPS Officer: JOE O'HARA
Notification Date: 01/23/2008
Notification Time: 18:31 [ET]
Event Date: 01/23/2008
Event Time: 17:05 [CST]
Last Update Date: 01/24/2008
Emergency Class: UNUSUAL EVENT
10 CFR Section:
50.72(a) (1) (i) - EMERGENCY DECLARED
Person (Organization):
CLAUDE JOHNSON (R4)
MICHAEL CASE (NRR)
ELMO COLLINS (RA)
ROY ZIMMERMAN (NSIR)
THOMAS BLOUNT (IRD)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N N 0 Refueling 0 Refueling
Event Text
UNUSUAL EVENT - TOXIC GASES IN THE TURBINE BUILDING

"Detection of toxic gases (CO) inside the turbine building.

"Source not identified.

"Initial Readings were greater than 50 parts per million in turbine building lower elevations.

"EALHU5.1

"Detected by safety department random sampling.

"Turbine building has been evacuated, all personnel have been accounted for with no injures.

"Follow-up notification will be made with determination of cause of event.

"The unit is currently defueled. The carbon monoxide source is being investigated."

The NRC Resident Inspector as well as state and local authorities were notified.

* * * UPDATE FROM ERIC PICKRELL TO JOE O'HARA AT 1932 EST ON 1/23/08 * * *

"Notified J. O'Hara of termination of the declared NOUE. Termination is based on subsequent air monitoring sampling revealing normal Oxygen levels and no detectable Carbon Monoxide levels.

"(unknown) Source of abnormal sample readings is not yet determined. Believed to be result of Hydrogen Water Chemistry system purge which was in progress at the time of sampling."

Licensee terminated the declaration of notification of unusual event at 1827 CST following two subsequently satisfactory air samples.

Notified R4DO(Johnson), NRR(Case), and IRD(Blount)


* * UPDATE FROM TIM SCHENK TO JOHN KNOKE AT 1515 EST ON 01/24/08 * *

"It has been determined that hazardous levels of toxic gases (Carbon Monoxide) inside the turbine building did not exist at the time of emergency declaration. Actual carbon monoxide levels were less than detectable. Gas sensor cross contamination led to false readings of high carbon monoxide level (60 ppm), when actual gas measurements were reading hydrogen levels of 20 ppm. This level of hydrogen is well below the 40,000 ppm Lower Explosive Limit for hydrogen. The source of the hydrogen readings was attributed to a leaking ventilation rig for the Hydrogen Water Chemistry system during system purge with Nitrogen."


The licensee notified the NRC Resident Inspector. Notified R4DO (C. Johnson).


Power Reactor
Event Number: 43928
Facility: SAN ONOFRE
Region: 4     State: CA
Unit: [] [2] []
RX Type: [1] W-3-LP,[2] CE,[3] CE
NRC Notified By: SUSAN GARDNER
HQ OPS Officer: JOHN KNOKE
Notification Date: 01/23/2008
Notification Time: 21:34 [ET]
Event Date: 01/23/2008
Event Time: 14:15 [PST]
Last Update Date: 01/23/2008
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION
Person (Organization):
CLAUDE JOHNSON (R4)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 N Y 95 Power Operation 65 Power Operation
Event Text
ONE OF TWO MAIN FEEDWATER PUMPS TRIP

"On January 23, 2008, at about 1415 PST, SONGS Unit 2 was operating at approximately 95 percent power when one of two main feed water pumps (P063/K005), tripped on low oil pressure while an adjustment was being made to the pump's lubricating oil pressure regulator. Control room operators manually actuated the emergency feedwater system in accordance with Abnormal Operating Instructions. Control room operators reduced reactor power level to about 65 percent which can be sustained with one normal feedwater pump in operation. The cause of this event is currently under investigation.

"In compliance with 10CFR50.72(b)(3)(iv)(A), requiring licensees to report any event or condition that results in valid actuation of the emergency feedwater system, SCE is providing this notification to the NRC.

"At the time of this occurrence, Unit 3 was operating at about 100 percent power. SCE has notified the NRC resident inspectors about this occurrence and will provide them with a copy of this report."


Power Reactor
Event Number: 43929
Facility: SAINT LUCIE
Region: 2     State: FL
Unit: [1] [] []
RX Type: [1] CE,[2] CE
NRC Notified By: ALAN HALL
HQ OPS Officer: JOE O'HARA
Notification Date: 01/23/2008
Notification Time: 23:05 [ET]
Event Date: 01/23/2008
Event Time: 22:15 [EST]
Last Update Date: 01/23/2008
Emergency Class: UNUSUAL EVENT
10 CFR Section:
50.72(a) (1) (i) - EMERGENCY DECLARED
Person (Organization):
BINOY DESAI (R2)
MICHAEL CASE (NRR)
THOMAS BLOUNT (IRD)
KEVIN BISCOE (FEMA)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
Event Text
UNUSUAL EVENT - UNCONTROLLED HYDROGEN LEAK

"St. Lucie Plant made an Unusual Event notification to the Florida State Warning Point @ 2228 EST, 01/23/08 based on a Hydrogen Tube Trailer fitting failure, and subsequent leak of hydrogen gas. The emergency classification was Emergency Action Level #20. A., per St. Lucie Plant EPIP-01, 'Classification of Emergencies'. The hydrogen leak was terminated upon discovery, with no subsequent fire and no personnel injuries. The event (and declaration) was terminated @ 2228 EST, on 01/23/08."

The licensee notified the NRC Resident Inspector, and the Commonwealth of Florida Warning Point.