Event Notification Report for January 19, 2008

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
01/18/2008 - 01/19/2008

EVENT NUMBERS
4392043921

Power Reactor
Event Number: 43920
Facility: HOPE CREEK
Region: 1     State: NJ
Unit: [1] [] []
RX Type: [1] GE-4
NRC Notified By: MICHAEL REED
HQ OPS Officer: JASON KOZAL
Notification Date: 01/19/2008
Notification Time: 16:13 [ET]
Event Date: 01/19/2008
Event Time: 11:52 [EST]
Last Update Date: 01/19/2008
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(v)(D) - ACCIDENT MITIGATION
Person (Organization):
EUGENE COBEY (R1)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
Event Text
'A' AND 'B' RECIRCULATION PUMP MOTOR GENERATOR OVERSPEED STOPS FOUND SET HIGH (NON-CONSERVATIVE) DURING SURVEILLANCE TESTING

"During the Performance of the 18 month surveillance requirement to demonstrate operability of the reactor recirc pump motor set scoop tube mechanical and electrical stop over-speed set points to be less than or equal to 109 percent and 107 percent, respectively, the 'A' and 'B' MG set stops were found non-conservatively high. The electrical and mechanical stops have been adjusted to meet surveillance requirements as of 1538 [on] 1/19/2008.

"The potential impact of this condition would be a function of the reactor recirc 'run-out' transient. If that analyzed transient were to have occurred, the potential existed for the flow dependent Minimum Critical Power Ratio to have been exceeded. This could result in exceeding the safety limit (MCPR) under the most limiting postulated conditions.

"Evaluation of the potential cause of the improper settings is underway.

"The 'A' Recirc Pump and Motor were replaced during the last refueling outage. [November 2007]"

The licensee notified the NRC Resident Inspector. The licensee will notify Lower Alloways Creek Township.


Power Reactor
Event Number: 43921
Facility: SEABROOK
Region: 1     State: NH
Unit: [1] [] []
RX Type: [1] W-4-LP
NRC Notified By: MATT FORREST
HQ OPS Officer: PETE SNYDER
Notification Date: 01/20/2008
Notification Time: 02:55 [ET]
Event Date: 01/19/2008
Event Time: 23:02 [EST]
Last Update Date: 01/20/2008
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(iv)(B) - RPS ACTUATION - CRITICAL 50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION
Person (Organization):
EUGENE COBEY (R1)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 A/R Y 100 Power Operation 0 Hot Standby
Event Text
AUTOMATIC REACTOR TRIP FOLLOWING TURBINE TRIP

"Initiating alarm received was a Turbine Trip. All on site buses 1, 2, 4, 5 and 6 swapped to the Reserve Auxiliary Transformer power supplies. Bus 3 did not swap as expected. The station has entered a Technical Specification 3.8.1.1 (a) 72 hour action statement for offsite power distribution with 345 kV Bus 3 unavailable.

"All safety systems operated correctly. The station continues to troubleshoot the initiating cause of the Turbine Trip. The plant is stable in Mode 3."

During the swap of non safety buses to the Reserve Auxiliary Transformer the Reactor Coolant Pumps (RCP) tripped. Following the loss of power to the RCPs the reactor stabilized in natural circulation. A Pressurizer PORV cycled following the trip. One RCP was restarted to restore forced circulation. Auxiliary Feedwater Pumps started as expected on the trip and were subsequently secured.

All control rods fully inserted on the trip. The current decay heat removal path is Start-up Feedwater supplying water to the Steam Generators steaming to the Condenser Steam Dumps.

The licensee notified the NRC Resident Inspector.

* * * UPDATE AT 0348 ON 1/20/08 FROM FORREST TO HUFFMAN * * *

The licensee has indication of a differential voltage fault on the C phase of the 345 kV line that feeds the Unit Auxiliary Transformer and the generator step-up transformers. The licensee also wanted to ensure that the report reflected the specified system actuation of Auxiliary Feedwater.