Event Notification Report for January 13, 2008

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
01/12/2008 - 01/13/2008

EVENT NUMBERS
43900439014390243903

Power Reactor
Event Number: 43900
Facility: PALISADES
Region: 3     State: MI
Unit: [1] [] []
RX Type: [1] CE
NRC Notified By: MIKE MLYNAREK
HQ OPS Officer: HOWIE CROUCH
Notification Date: 01/13/2008
Notification Time: 09:11 [ET]
Event Date: 01/13/2008
Event Time: 05:21 [EST]
Last Update Date: 01/13/2008
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(iv)(B) - RPS ACTUATION - CRITICAL 50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION
Person (Organization):
DAVID HILLS (R3)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 M/R Y 100 Power Operation 0 Hot Standby
Event Text
MANUAL REACTOR TRIP AFTER LOSS OF MAIN FEEDWATER PUMP

Palisades Operations staff manually tripped the reactor in accordance with their station's Off-Normal Operating Procedure, after an automatic trip of the "B" Main Feedwater Pump (MFP). The cause of the MFP auto-trip is unknown and being investigated. During the trip, all systems performed as designed.

During the transient resulting from the trip, the atmospheric steam dump valves did open momentarily and properly reseated. There is no known primary-to-secondary leakage therefore no release was known to have occurred. All control rods inserted fully as a result of the trip. Auxiliary feedwater pump [AFW] 8A started, as expected, in response to low steam generator water levels experienced during the transient and supplied both steam generators. Decay heat is being removed via the main steam isolation valves to the condenser with the 8A AFW pump supplying feedwater to the steam generators. The plant is at normal temperatures and pressures for this mode. The electrical grid is stable with the station start-up transformer supplying station loads.

The licensee has notified the NRC Resident Inspector.


Power Reactor
Event Number: 43901
Facility: RIVER BEND
Region: 4     State: LA
Unit: [1] [] []
RX Type: [1] GE-6
NRC Notified By: GARY HUSTON
HQ OPS Officer: HOWIE CROUCH
Notification Date: 01/13/2008
Notification Time: 11:36 [ET]
Event Date: 01/13/2008
Event Time: 10:36 [CST]
Last Update Date: 01/13/2008
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(xiii) - LOSS COMM/ASMT/RESPONSE
Person (Organization):
RUSSELL BYWATER (R4)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N N 0 Refueling 0 Refueling
Event Text
LOSS OF EMERGENCY ASSESSMENT CAPABILITIES DUE TO PLANNED MAINTENANCE ACTIVITIES

"Planned Maintenance on Safety Parameter Display System (SPDS) and Emergency Response Data System (ERDS).

"At 1036 CST hours, on 1/13/2008, the SPDS and ERDS system will be removed from service to support activities for a planned maintenance outage at River Bend Station. The duration of work is expected to be approximately 8 hours.

"During this time, Control Room indications and alternate methods will be available to implement the Emergency Plan. Since the SPDS computer system will be unavailable for greater than 2 hours, this is considered a Loss of Emergency Assessment Capability and reportable under 10CFR50.72(b)(3)(xiii).

"A follow-up notification will be made to the NRC after the SPDS and ERDS are returned to service.

"The licensee notified the NRC Resident Inspector."

* * * UPDATE AT 1844 ON 1/13/08 FROM HUSTON TO SNYDER * * *

"The SPDS and ERDS systems have been returned to service at 1745."

The licensee will notify the NRC Resident Inspector.

Notified R4DO (Bywater).


Power Reactor
Event Number: 43902
Facility: TURKEY POINT
Region: 2     State: FL
Unit: [] [4] []
RX Type: [3] W-3-LP,[4] W-3-LP
NRC Notified By: ED BERTRAM
HQ OPS Officer: PETE SNYDER
Notification Date: 01/13/2008
Notification Time: 13:56 [ET]
Event Date: 01/13/2008
Event Time: 09:44 [EST]
Last Update Date: 01/13/2008
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(xiii) - LOSS COMM/ASMT/RESPONSE
Person (Organization):
MALCOLM WIDMANN (R2)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
4 N Y 100 Power Operation 100 Power Operation
Event Text
INTERMITTENT PLANT COMPUTER FAILURES

"At 0944, the Plant Computer (ERDADS) failed. Investigation revealed the ERDS link was also INOPERABLE due to the failure of the plant computer due [to] data corruption due to train failovers. Engineering has restored the plant computer by 1300. Called the plant computer and ERDS link OPERABLE at time 1330."

The licensee notified the NRC Resident Inspector.


!!!!! THIS EVENT HAS BEEN RETRACTED !!!!!
!!!!! THIS EVENT HAS BEEN RETRACTED !!!!!
Fuel Cycle Facility
Event Number: 43903
Facility: PADUCAH GASEOUS DIFFUSION PLANT
Region: 2     State: KY
Unit: [] [] []
RX Type: URANIUM ENRICHMENT FACILITY
Comments: 2 DEMOCRACY CENTER
6903 ROCKLEDGE DRIVE
BETHESDA, MD 20817 (301)564-3200
NRC Notified By: TONY HUDSON
HQ OPS Officer: JOE O'HARA
Notification Date: 01/14/2008
Notification Time: 15:36 [ET]
Event Date: 01/13/2008
Event Time: 15:12 [CST]
Last Update Date: 01/18/2008
Emergency Class: NON EMERGENCY
10 CFR Section:
76.120(c)(2) - SAFETY EQUIPMENT FAILURE
Person (Organization):
MALCOLM WIDMANN (R2)
ROBERT PIERSON (NMSS)
Event Text
FAILURE OF UF6 RELEASE DETECTION SYSTEM

"At 1512 CST, on 01-13-08 the Plant Shift Superintendent (PSS) was notified that the C-333 Unit 6 Cell 7 UF6 Release Detection (PGLD) System failed to function when performing the twice per shift test firing. Test firing of the PGLD detector heads is required per TSR SR 2.4.4.1-1. TSR 2.4.4.1 also requires that at least the minimum number (three) of detector heads in the cell and in each defined section of the cell bypass are operable where UF6 systems are above atmospheric pressure. The C-333 Unit 6 Cell 7 PGLD System contains detectors that covers the cell and Sections 3 and 4 of the cell bypass piping. At the time of this failure some areas of Section 3 of the cell bypass were operating above atmospheric pressure. Since Unit 6 Cell 7 was operating below atmosphere, the cell was not in an applicable TSR mode. However, Section 3 of the cell bypass was above atmosphere and in an applicable TSR mode which required at least three operable PGLD heads. With the Unit 6 Cell 7 PGLD system inoperable only two of the required three heads in Section 3 of the cell bypass were operable. This PGLD System was declared inoperable, and system pressure in the affected operating area was reduced to less than atmospheric pressure within one hour, thus placing the operating system in a non-applicable TSR mode. This event is being reported as a 24 hour event in accordance with 10CFR 76.120(c)(2)(i). This is an event in which equipment is disabled or fails to function as designed when: a.) the equipment is required by a TSR to prevent releases, prevent exposures to radiation and radioactive materials exceeding specified limits, mitigate the consequences of an accident, or restore this facility to a pre-established safe condition after an accident; b.) the equipment is required by a TSR to be available and operable and either should have been operating or should have operated on demand, and c.) no redundant equipment is available and operable to perform the required safety function.

"The NRC Resident Inspector has been notified of this event.

"PGDP Assessment and Tracking Report No. ATR-08-0122; PGDP Event Report No. PAD-2008-01; Worksheet No. 43903

"Responsible Division: Operations"

The licensee is investigating the cause of the event, and will make appropriate notifications to the Department of Energy.

* * * RETRACTION PROVIDED BY TONY HUDSON TO JASON KOZAL AT 1403 ON 1/18/08 * * *

"On January 13, 2008 the C-333 U/6 C/7 PGLD system failed during testing. This affected all the PGLD heads in the cell area and two of the four heads in section 3 of the cell by-pass. A review of operating pressures in the affected area determined that the cell was operating below atmospheric pressure, but that piping in section 3 of the cell by-pass was operating above atmosphere. Thus, three of four heads in section 3 of the Cell by-pass were required by the TSR to be operable. Given the recent failure in November and indications that the failure modes may be similar, the PSS reported the event to the NRC per 10CFR 76.120(c)(2)(i), In-Service Safety System Failure. Subsequent to the event, the pressures in C-333 U/6 CR, section 3 in the cell by-pass area associated with the event were reviewed. Using Engineering Notice EN-C-821-05-090, Rev, 3, it was determined that section 3 of the cell by-pass was actually not operating above atmosphere and thus, the PGLD system was not required to be operable at the time of the failure. Since the failure only affected detectors in an area operating in a non-TSR mode, the PGLD system is not required to be operable and reporting under 10 CFR 76.120(C)(2) is not required."

The licensee notified the NRC Resident Inspector. The licensee made appropriate notifications to the Department of Energy.

R2DO (Moorman) and NMSS EO (Kokajko) notified.