Skip to main content

Event Notification Report for January 04, 2008

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
01/03/2008 - 01/04/2008

EVENT NUMBERS
43880

Power Reactor
Event Number: 43880
Facility: DAVIS BESSE
Region: 3     State: OH
Unit: [1] [] []
RX Type: [1] B&W-R-LP
NRC Notified By: ANTHONY STALLARD
HQ OPS Officer: JASON KOZAL
Notification Date: 01/04/2008
Notification Time: 08:05 [ET]
Event Date: 01/04/2008
Event Time: 02:50 [EST]
Last Update Date: 01/04/2008
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(ii)(A) - DEGRADED CONDITION
Person (Organization):
PATRICK LOUDEN (R3)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N N 0 Refueling 0 Refueling
Event Text
PRESSURE BOUNDARY LEAKAGE DISCOVERED DURING REFUELING

"While in Mode 6 with the Reactor Head in place and fuel in the Reactor Vessel, weld overlay was in progress on the common Decay Heat Suction line from the Reactor Coolant System. The Reactor Coolant System is in a drained condition with RCS level approximately 24 inches above the Hot Leg Centerline. During the first weld pass on the suction line weld located in Containment, the welding operator noticed water seeping from the weld. Visual inspection revealed a small leak. The leakage is too small to quantify the leakrate. Surface examinations prior to welding revealed no abnormal conditions or leakage. Welding operations on this weld have been suspended. Planned Refueling activities continue to defuel the reactor vessel.

"One train of Decay Heat Removal remains in service providing core cooling. The second train is aligned in standby for Decay Heat Removal. Both Trains of Decay Heat Removal have been declared inoperable due to this leak, however both trains of Decay Heat Removal remain functional."

The licensee notified the NRC Resident Inspector.