Event Notification Report for November 27, 2007
U.S. Nuclear Regulatory Commission
Operations Center
EVENT REPORTS FOR
11/26/2007 - 11/27/2007
Power Reactor
Event Number: 43807
Facility: BYRON
Region: 3 State: IL
Unit: [1] [] []
RX Type: [1] W-4-LP,[2] W-4-LP
NRC Notified By: JIM LYNDE
HQ OPS Officer: MARK ABRAMOVITZ
Region: 3 State: IL
Unit: [1] [] []
RX Type: [1] W-4-LP,[2] W-4-LP
NRC Notified By: JIM LYNDE
HQ OPS Officer: MARK ABRAMOVITZ
Notification Date: 11/27/2007
Notification Time: 10:30 [ET]
Event Date: 11/27/2007
Event Time: 09:15 [CST]
Last Update Date: 11/27/2007
Notification Time: 10:30 [ET]
Event Date: 11/27/2007
Event Time: 09:15 [CST]
Last Update Date: 11/27/2007
Emergency Class: ALERT
10 CFR Section:
50.72(a) (1) (i) - EMERGENCY DECLARED
10 CFR Section:
50.72(a) (1) (i) - EMERGENCY DECLARED
Person (Organization):
CHRISTINE LIPA (R3)
MARY JANE ROSS-LEE (NRR)
JIM DYER (NRR)
BRIAN McDERMOTT (IRD)
MARYANNE (DHS)
CHRISTINE LIPA (R3)
MARY JANE ROSS-LEE (NRR)
JIM DYER (NRR)
BRIAN McDERMOTT (IRD)
MARYANNE (DHS)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 1 | N | Y | 100 | Power Operation | 100 | Power Operation |
ALERT DECLARED DUE TO OXYGEN DEFICIENT ATMOSPHERE
An ALERT was declared at 0915 CST. A nitrogen freeze seal was being used on a 3 inch pipe in the 1B RHR and 1B Containment Spray pump room. A leak developed on the freeze seal jacket. This created an oxygen deficient atmosphere (less than 19.5 percent oxygen). The nitrogen supply was isolated. And the room was evacuated. The alert was declared in accordance with Emergency Action Level (EAL) "hazard alert #7 (HA7)." Additional ventilation was being placed in the area to restore normal oxygen levels.
EAL table entry HA7 is for "Release of toxic or flammable gases within or restricting access to a vital area which jeopardizes operation of systems required to maintain safe operations or establish or maintain safe shutdown."
No personnel injuries occurred. Oxygen levels were returned to acceptable levels at 0933 CST.
The licensee notified the NRC Resident Inspector.
* * * UPDATE AT 1205 ON 11/27/2007 FROM PAUL CANTWELL TO MARK ABRAMOVITZ * * *
The ALERT was terminated at 1103 CST.
Notified IRD (McDermott), R3DO (Lipa), DHS SWO (Mary Anne), FEMA (Dan Sullivan), DOE (Anthony Parsons), EPA (Ms Ross), USDA (Andrew Watts), and USDA (Rick Turner).
An ALERT was declared at 0915 CST. A nitrogen freeze seal was being used on a 3 inch pipe in the 1B RHR and 1B Containment Spray pump room. A leak developed on the freeze seal jacket. This created an oxygen deficient atmosphere (less than 19.5 percent oxygen). The nitrogen supply was isolated. And the room was evacuated. The alert was declared in accordance with Emergency Action Level (EAL) "hazard alert #7 (HA7)." Additional ventilation was being placed in the area to restore normal oxygen levels.
EAL table entry HA7 is for "Release of toxic or flammable gases within or restricting access to a vital area which jeopardizes operation of systems required to maintain safe operations or establish or maintain safe shutdown."
No personnel injuries occurred. Oxygen levels were returned to acceptable levels at 0933 CST.
The licensee notified the NRC Resident Inspector.
* * * UPDATE AT 1205 ON 11/27/2007 FROM PAUL CANTWELL TO MARK ABRAMOVITZ * * *
The ALERT was terminated at 1103 CST.
Notified IRD (McDermott), R3DO (Lipa), DHS SWO (Mary Anne), FEMA (Dan Sullivan), DOE (Anthony Parsons), EPA (Ms Ross), USDA (Andrew Watts), and USDA (Rick Turner).
General Information or Other
Event Number: 43818
Rep Org: NV DIV OF RAD HEALTH
Licensee: CITY OF HENDERSON, NV
Region: 4
City: HENDERSON State: NV
County:
License #: 03-14-0116-01
Agreement: Y
Docket:
NRC Notified By: ERIC MATUS
HQ OPS Officer: JEFF ROTTON
Licensee: CITY OF HENDERSON, NV
Region: 4
City: HENDERSON State: NV
County:
License #: 03-14-0116-01
Agreement: Y
Docket:
NRC Notified By: ERIC MATUS
HQ OPS Officer: JEFF ROTTON
Notification Date: 12/03/2007
Notification Time: 12:56 [ET]
Event Date: 11/27/2007
Event Time: 13:30 [PST]
Last Update Date: 12/03/2007
Notification Time: 12:56 [ET]
Event Date: 11/27/2007
Event Time: 13:30 [PST]
Last Update Date: 12/03/2007
Emergency Class: NON EMERGENCY
10 CFR Section:
10 CFR Section:
Person (Organization):
MICHAEL HAY (R4)
MICHELE BURGESS (FSME)
ILTAB (VIA EMAIL)
MICHAEL HAY (R4)
MICHELE BURGESS (FSME)
ILTAB (VIA EMAIL)
NEVADA AGREEMENT STATE REPORT - STOLEN TROXLER MOISTURE DENSITY GAUGE
"At approximately 1330 [PST] on Tuesday November 27, 2007, a technician and asst. RSO for the City of Henderson NV, drove away from a jobsite where he had been taking a backscatter density measurement with a Troxler 3440 Nuclear Density Gauge. He left the gauge sitting on the side of the road with the probe unlocked and not in a safe mode. At 1333, he returned to the site to find that the gauge had been removed. The RSO filed a report with Henderson PD [on 11/27/07] and phoned in a report to Nevada Radiological Health Section the following day [11/28/07] at 1010. The gauge [Serial #26655] contains [2] sealed sources: 8 milliCuries Cs-137, and 40 milliCuries Am-241/Be ."
The licensee issued a press release (print, radio, and TV) to notify the public of the incident, warn them of the potential danger and ask for the return of the gauge.
Nevada Item Number: NV070009
THIS MATERIAL EVENT CONTAINS A "LESS THAN CAT 3" LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks.
"At approximately 1330 [PST] on Tuesday November 27, 2007, a technician and asst. RSO for the City of Henderson NV, drove away from a jobsite where he had been taking a backscatter density measurement with a Troxler 3440 Nuclear Density Gauge. He left the gauge sitting on the side of the road with the probe unlocked and not in a safe mode. At 1333, he returned to the site to find that the gauge had been removed. The RSO filed a report with Henderson PD [on 11/27/07] and phoned in a report to Nevada Radiological Health Section the following day [11/28/07] at 1010. The gauge [Serial #26655] contains [2] sealed sources: 8 milliCuries Cs-137, and 40 milliCuries Am-241/Be ."
The licensee issued a press release (print, radio, and TV) to notify the public of the incident, warn them of the potential danger and ask for the return of the gauge.
Nevada Item Number: NV070009
THIS MATERIAL EVENT CONTAINS A "LESS THAN CAT 3" LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks.
General Information or Other
Event Number: 43811
Rep Org: ARIZONA RADIATION REGULATORY AGENCY
Licensee: UNKNOWN
Region: 4
City: GLENDALE State: AZ
County:
License #:
Agreement: Y
Docket:
NRC Notified By: AUBRY GODWIN
HQ OPS Officer: PETE SNYDER
Licensee: UNKNOWN
Region: 4
City: GLENDALE State: AZ
County:
License #:
Agreement: Y
Docket:
NRC Notified By: AUBRY GODWIN
HQ OPS Officer: PETE SNYDER
Notification Date: 11/28/2007
Notification Time: 15:22 [ET]
Event Date: 11/27/2007
Event Time: 18:11 [MST]
Last Update Date: 11/28/2007
Notification Time: 15:22 [ET]
Event Date: 11/27/2007
Event Time: 18:11 [MST]
Last Update Date: 11/28/2007
Emergency Class: NON EMERGENCY
10 CFR Section:
10 CFR Section:
Person (Organization):
GREG PICK (R4)
DENNIS RATHBUN (FSME)
ILTAB (e-mail)
MEXICO
GREG PICK (R4)
DENNIS RATHBUN (FSME)
ILTAB (e-mail)
MEXICO
AGREEMENT STATE REPORT - NATURALLY OCCURRING RADIOACTIVE MATERIAL FOUND AT A SCHOOL
The Agreement State submitted the following information via e-mail:
"At approximately 6:11 PM November 27, 2007, the Agency was informed that the Washington Elementary School District had found some radioactive material and had called the Glendale Fire Department. The material was found when the District was cleaning out some chemicals. The Glendale and Phoenix Fire Departments responded and they detected radiation with their instrumentation. At that point the Agency was contacted.
"The radioactive material was identified as radium 226 and read 220 microrad at 3 inches from the container. Wipes and alpha surveys checks made in field were negative. Laboratory results pending. Based on the radiation reading at 3 inches, we estimate that a total of between 0.5 to 5 microcuries of radium may be present. The material was secured until a waste broker can remove it. The form of the radium was not determined.
"The [Arizona Regulatory] Agency continues to investigate this event."
Arizona Report First Notice Number: 07-013
THIS MATERIAL EVENT CONTAINS A "LESS THAN CAT 3" LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks.
This source is not amongst those sources or devices identified by the IAEA Code of Conduct for the Safety & Security of Radioactive Sources to be of concern from a radiological standpoint. Therefore is it being categorized as a less than Category 3 source
The Agreement State submitted the following information via e-mail:
"At approximately 6:11 PM November 27, 2007, the Agency was informed that the Washington Elementary School District had found some radioactive material and had called the Glendale Fire Department. The material was found when the District was cleaning out some chemicals. The Glendale and Phoenix Fire Departments responded and they detected radiation with their instrumentation. At that point the Agency was contacted.
"The radioactive material was identified as radium 226 and read 220 microrad at 3 inches from the container. Wipes and alpha surveys checks made in field were negative. Laboratory results pending. Based on the radiation reading at 3 inches, we estimate that a total of between 0.5 to 5 microcuries of radium may be present. The material was secured until a waste broker can remove it. The form of the radium was not determined.
"The [Arizona Regulatory] Agency continues to investigate this event."
Arizona Report First Notice Number: 07-013
THIS MATERIAL EVENT CONTAINS A "LESS THAN CAT 3" LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks.
This source is not amongst those sources or devices identified by the IAEA Code of Conduct for the Safety & Security of Radioactive Sources to be of concern from a radiological standpoint. Therefore is it being categorized as a less than Category 3 source