General Information or Other
Event Number: 43681
Rep Org: WISCONSIN RADIATION PROTECTION
Licensee: UNKNOWN
Region: 3
City: FOND DU LAC   State: WI
County:
License #:
Agreement: Y
Docket:
NRC Notified By: CHERYL K. ROGERS
HQ OPS Officer: JOHN MacKINNON
Notification Date: 10/02/2007
Notification Time: 09:55 [ET]
Event Date: 09/28/2007
Event Time: 12:00 [CDT]
Last Update Date: 10/02/2007
Emergency Class: NON EMERGENCY
10 CFR Section:
Person (Organization):
LAURA KOZAK (R3)
MICHELE BURGESS (FSME)
Event Text
WISCONSIN AGREEMENT STATE REPORT - NDC GAUGE FOUND IN SCRAP YARD


The following Agreement State report from Wisconsin was received via Facsimile:

"License No.: Non-licensee

"Licensee: Non-licensee

"Event Location: Gorden Schneider Property

"Event Type: Scrap Yard Detector

"Notifications: Phone call from Sadoff yard on 9/28/07.


"DHFS was contacted on 9/28/07 concerning a rejected load from Sadoff scrap yard in Fond du Lac. The yard made the initial contact and had the individual with the load talk to DHFS before leaving the yard. A hand monitor (survey) gave radiation reading of 200 microR/hr on the outside of the trailer. A metal tank was observed where the reading was noted. He was told to off load and cover it with plastic until DHFS responds. The individual with the rejected load contacted DHFS on 10/01/07 requesting what to do about the load. Evidently, the individual had made a second attempt to sell the material to Sadoff. When contacted, he reported there were CRM labels on the device. It was reported to be about a foot long, with 8 prongs and 3 fins. A label stated that it was sold under Gen. Lic. No. CL 1933-70. The label for NDC listed Duarte, CA, 91010. The individual was requested to not handle the device and to place it in a secure location.

"No information on this device was in the DHFS GL database. DHFS contacted NDC and was informed that it was a Model 103 with 150 mCi of AM-241. The gauge had been sold to Sabee Co, 1718 West Eighth St, Appleton, WI on 12/12/85. The last contact that NDC had with the gauge was 11/20/95. A call was made to Sabee Co in Appleton. An individual there reported that the company was divided in 2002 and management changed in 2003. The company used to do film extrusion. The individual promised to follow up with someone who had been there for a long time and might remember more about the film extrusion process. Contact nos. were given to two former owners. DHFS plans to investigate on October 3, 2007."

Media attention: None


Event Report ID No.: WI070026.

THIS MATERIAL EVENT CONTAINS A "LESS THAN CAT 3" LEVEL OF RADIOACTIVE MATERIAL

Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks.


General Information or Other
Event Number: 43682
Rep Org: WA DIVISION OF RADIATION PROTECTION
Licensee: WASHINGTON STATE DEPARTMENT OF TRANSPORTATION
Region: 4
City: SPOKANE   State: WA
County:
License #: WN-L035-1
Agreement: Y
Docket:
NRC Notified By: ARDEN SCROGGS
HQ OPS Officer: MARK ABRAMOVITZ
Notification Date: 10/02/2007
Notification Time: 11:55 [ET]
Event Date: 09/28/2007
Event Time: 00:00 [PDT]
Last Update Date: 10/02/2007
Emergency Class: NON EMERGENCY
10 CFR Section:
Person (Organization):
REBECCA NEASE (R4)
MICHELE BURGESS (FSME)
Event Text
AGREEMENT STATE REPORT INVOLVING A DAMAGED TROXLER MOISTURE DENSITY GAUGE

The following information was received via email:

"Subject: Event Report Number WA-07-084

"This is notification of an event in Washington State as reported to or investigated by the WA Department of Health, Office of Radiation Protection.

"STATUS: new

"Licensee: Washington State Department of Transportation Eastern Region
"City and State: Spokane, Washington
"License Number: WN-L035-1
"Type of License: Portable Gauge Licensee

"Date of Event: 28 September 2007
"Location of Event: Spokane, Washington

"ABSTRACT: (where, when, how, why; cause, contributing factors, corrective actions, consequences, Dept. of Health (DOH) on-site investigation; media attention):

"The licensee's radiation safety officer notified Washington Department of Health (DOH) on 01 October 2007 their Troxler portable gauge, model 3430, serial number 36039 (containing maximum of 8 millicuries Cs-137 and 40 millicuries Am-241:Be) was run over on 28 September 2007 by a small roller during road repair. The gauge did not have the probe extended when struck. The gauge user immediately notified their radiation safety officer and the RSO's supervisor; radiation surveys detected no elevated radiation levels, so the licensee decided to transport the device to their storage area and inform Washington DOH the following workday, Monday 01 October 2007. It was reported that only superficial damage was done to the plastic case of the gauge. The gauge was put back in the transport case and sent back to its secured storage location. Department staff are investigating.


"Washington (DOH) on-site investigation underway.

"No known media attention.

"Notification Reporting Criteria:

"Per WAC 246-221-250 (2) (d) ~ Twenty-four (24) hour notice required for equipment failure or inability to function as designed.

"Isotope and Activity involved: one Troxler model 3430, serial 36039 portable gauge, containing two radioactive sealed sources, one 8 millicuries Cs-137 maximum, & one 40 millicuries Am-241:Be maximum.

"Overexposures? (number of workers/members of the public; dose estimate; body part receiving dose; consequence): Unknown but most likely not. The unit was functioning properly on 28 September 2007. Dose rate measurements by the licensee after the gauge was rolled over detected no elevated radiation fields.

"Lost, Stolen or Damaged? (mfg., model, serial number): one Troxler model 3430, serial 36039 portable gauge, containing two radioactive sealed sources, one 8 millicuries Cs-137 maximum, & one 40 millicuries Am-241:Be maximum.

"Disposition/recovery: NA

"Leak test? Most recent leak test was collected on 18 January 2007 (no contamination, < 0.000002 microcuries).

"Vehicle: (description; placards; Shipper; package type; Pkg. ID number) NA
"Release of activity? NA
"Activity and pharmaceutical compound intended: NA
"Device (HDR, etc.) Mfg., Model; computer program: NA Exposure (intended/actual); consequences: NA
"Was patient or responsible relative notified? NA
"Was written report provided? NA
"Was referring physician notified? NA

"Consultant used? No."


Power Reactor
Event Number: 43675
Facility: MILLSTONE
Region: 1     State: CT
Unit: [] [] [3]
RX Type: [1] GE-3,[2] CE,[3] W-4-LP
NRC Notified By: BRIEN STRIZZI
HQ OPS Officer: MARK ABRAMOVITZ
Notification Date: 09/28/2007
Notification Time: 18:45 [ET]
Event Date: 09/28/2007
Event Time: 17:00 [EDT]
Last Update Date: 09/28/2007
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(ii)(B) - UNANALYZED CONDITION
Person (Organization):
MEL GRAY (R1)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
3 N Y 100 Power Operation 100 Power Operation
Event Text
REACTOR VESSEL HEAD VENT MAY NOT BE ISOLABLE DURING A FIRE

Plant engineering determined that in a postulated fire in the Control Room or Cable Spreading Room which required Control Room evacuation, that "hot shorts" may prevent the reactor vessel head vents from performing their emergency functions in accordance with the plant Emergency Operating Procedures (EOPs). Several relays in the letdown system are not isolated at the Auxiliary Shutdown Panel and have the potential for shorting during a fire. This letdown path can be aligned from the reactor vessel head vents during certain EOP scenarios.

The affected reactor vessel head vent isolation transfer switches are: 3RCS*SV8095A & B and 3RCS*SV8096A & B.

The site has implemented an hourly fire watch in the affected areas.

The licensee notified the NRC Resident Inspector.


Power Reactor
Event Number: 43676
Facility: HARRIS
Region: 2     State: NC
Unit: [1] [] []
RX Type: [1] W-3-LP
NRC Notified By: M. HINMAN
HQ OPS Officer: JOHN MacKINNON
Notification Date: 09/29/2007
Notification Time: 02:19 [ET]
Event Date: 09/28/2007
Event Time: 22:32 [EDT]
Last Update Date: 09/29/2007
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(iv)(B) - RPS ACTUATION - CRITICAL 50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION
Person (Organization):
MALCOLM WIDMANN (R2)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 A/R Y 30 Power Operation 0 Hot Standby
Event Text
AUTOMATIC REACTOR TRIP DUE TO LOSS OF A STARTUP TRANSFORMER

"On September 28, 2007, while reducing power for a planned refueling outage with the reactor at approximately 30 percent power in MODE 1, an unplanned actuation of the reactor protection system occurred. At 2232 a fault pressure trip signal was received on the A Startup Transformer (SUT), causing a loss of power to Aux Buses D, A & C electrical buses as well as the A-SA safety bus. The loss of A & C buses initiated the RCP underfrequency trip which tripped the Reactor and all three RCPs as designed. The A Diesel Generator automatically started and reenergized bus A-SA as designed. The auxiliary feedwater system actuated as expected due to undervoltage on the A-SA safety bus and loss of the main feedwater pumps. All control rods inserted on the reactor trip. The operations staff responded to the event in accordance with applicable plant procedures. The plant stabilized at normal operating no-load reactor coolant system temperature and pressure following the reactor trip. Steam generator water levels are being maintained using auxiliary feedwater. All emergency core cooling system equipment is available. The plant electrical system is being restored at this time. The A SUT remains out of service. The cause of the loss of power from A SUT is under investigation.

"This condition is being reported as an unplanned reactor protection system actuation and specified system actuation in accordance with 10 CFR 50.72(b)(2)(iv)(B) and 10 CFR 50.72(b)(3)(iv)(A)."

The NRC Resident Inspector was notified of this event by the licensee.

The plant was in natural circulation for approximately 1 hour. The Main Steam Isolation Valves (MSIVs) were manually isolated per procedure due to loss of EHC indication. Presently the B RCP has been restored to service, MSIVs are still closed, and the motor driven auxiliary feedwater pumps are feeding the Main Steam Generators. There are not any leaking steam generator tubes. The A EDG will be secured after backfeeding of the deenergized buses have been established.


Fuel Cycle Facility
Event Number: 43671
Facility: PORTSMOUTH GASEOUS DIFFUSION PLANT
Region: 2     State: OH
Unit: [] [] []
RX Type: URANIUM ENRICHMENT FACILITY
Comments: 2 DEMOCRACY CENTER
6903 ROCKLEDGE DRIVE
BETHESDA, MD 20817 (301)564-3200
NRC Notified By: RON CRABTREE
HQ OPS Officer: MARK ABRAMOVITZ
Notification Date: 09/28/2007
Notification Time: 14:35 [ET]
Event Date: 09/28/2007
Event Time: 11:16 [EDT]
Last Update Date: 09/28/2007
Emergency Class: NON EMERGENCY
10 CFR Section:
Person (Organization):
MALCOLM WIDMANN (R2)
ROBERT PIERSON (FSME)
Event Text
SMOKE FROM STEAM PLANT STARTUP REQUIRING STATE NOTIFICATION

"At 0930 hours, 09/28/07, the PORTS Plant Shift Superintendent's (PSS) Office was notified of an opacity exceedance, which had occurred at the X-600 Steam Plant on 09/18/07. The PORTS PSS Office notified the Ohio Environmental Protection Agency (OEPA) of this incident, at 1116 hours, 09/28/07. This notification to another government agency is reportable to the NRC as a 4-Hour Event per the United States Enrichment Corporation (USEC) Nuclear Regulatory Event Reporting Procedure UE2-RA-RE1030, Appendix D, Section P (Miscellaneous) which states: 'USEC shall notify NRC of any event or situation, related to the health and safety of the public or on-site personnel, or protection of the environment, for which a news release is planned or notification to other government agencies has been or will be made. Such an event may include an on-site fatality or inadvertent release of radioactively contaminated materials.'"

The start-up of the steam boiler was completed however, problems were encountered which created smoke after the state mandated time limit for startup smoke had expired.

The licensee notified the NRC Resident Inspector and the Department of Energy.


Power Reactor
Event Number: 43672
Facility: FITZPATRICK
Region: 1     State: NY
Unit: [1] [] []
RX Type: [1] GE-4
NRC Notified By: AVRAKOTOS
HQ OPS Officer: MARK ABRAMOVITZ
Notification Date: 09/28/2007
Notification Time: 14:40 [ET]
Event Date: 09/28/2007
Event Time: 13:00 [EDT]
Last Update Date: 09/28/2007
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(xi) - OFFSITE NOTIFICATION
Person (Organization):
MEL GRAY (R1)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
Event Text
EMERGENCY SIREN ACTIVATED INADVERTENTLY DURING A THUNDERSTORM

"A single siren in the Nine Mile/FitzPatrick EPZ was inadvertently activated coincident with a thunderstorm and lightning strikes in the area of the siren. Oswego Co (New York) Emergency management officials are issuing a press release regarding the storm related siren activation. Attempts to silence the siren were not effective using the systems remote activation system further indicating that lightning affected the siren.

"A work crew has been dispatched to the siren to investigate and has silenced the siren. Notification is being provided to the NRC in regards to the potential for media inquiry."

The licensee informed the NRC Resident Inspector.


Power Reactor
Event Number: 43673
Facility: NINE MILE POINT
Region: 1     State: NY
Unit: [1] [2] []
RX Type: [1] GE-2,[2] GE-5
NRC Notified By: BRIAN FINCH
HQ OPS Officer: MARK ABRAMOVITZ
Notification Date: 09/28/2007
Notification Time: 16:12 [ET]
Event Date: 09/28/2007
Event Time: 13:10 [EDT]
Last Update Date: 09/28/2007
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(xi) - OFFSITE NOTIFICATION
Person (Organization):
MEL GRAY (R1)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
2 N Y 100 Power Operation 100 Power Operation
Event Text
EMERGENCY SIREN ACTIVATED INADVERTENTLY DURING A THUNDERSTORM

"A single siren in the Nine Mile/FitzPatrick EPZ was inadvertently activated coincident with a thunderstorm and lightning strikes in the area of the siren. Oswego Co (New York) Emergency management officials are issuing a press release regarding the storm related siren activation. Attempts to silence the siren were not effective using the systems remote activation system further indicating that lightning affected the siren.

"A work crew has been dispatched to the siren to investigate and has silenced the siren. Notification is being provided to the NRC in regards to the potential for media inquiry."

The licensee informed the NRC Resident Inspector.