Event Notification Report for August 28, 2007
U.S. Nuclear Regulatory Commission
Operations Center
EVENT REPORTS FOR
08/27/2007 - 08/28/2007
EVENT NUMBERS
43605
Power Reactor
Event Number: 43605
Facility: COOK
Region: 3 State: MI
Unit: [1] [] []
RX Type: [1] W-4-LP,[2] W-4-LP
NRC Notified By: BRIAN BATES
HQ OPS Officer: MARK ABRAMOVITZ
Region: 3 State: MI
Unit: [1] [] []
RX Type: [1] W-4-LP,[2] W-4-LP
NRC Notified By: BRIAN BATES
HQ OPS Officer: MARK ABRAMOVITZ
Notification Date: 08/28/2007
Notification Time: 15:17 [ET]
Event Date: 08/28/2007
Event Time: 13:54 [EDT]
Last Update Date: 08/28/2007
Notification Time: 15:17 [ET]
Event Date: 08/28/2007
Event Time: 13:54 [EDT]
Last Update Date: 08/28/2007
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(iv)(B) - RPS ACTUATION - CRITICAL 50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION
10 CFR Section:
50.72(b)(2)(iv)(B) - RPS ACTUATION - CRITICAL 50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION
Person (Organization):
CHRISTINE LIPA (R3)
CHRISTINE LIPA (R3)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 1 | A/R | Y | 100 | Power Operation | 0 | Hot Standby |
AUTOMATIC REACTOR TRIP AFTER DIGITAL FEEDWATER SYSTEM FAILURE
"At 13:54 on 8/28/07, DC Cook Unit 1 experienced an automatic reactor trip due to low steam generator water level coincident with low feedwater flow on #11 steam generator. The cause was a malfunction of the Main Feedwater Pump Digital Control System, which remains under investigation. This requires a 4-hour report under 10CFR50.72(b)(2)(iv)(B).
"Both Motor-Driven Auxiliary Feedwater Pumps automatically started due to the reactor trip. The Turbine-Driven Auxiliary Feedwater Pump (TDAFP) started automatically due to low-low water levels in at least two steam generators, which is expected for a reactor trip from 100% power. The automatic actuation of the reactor protection system and the TDAFP start require an 8-hour report under 10CFR50.72(b)(3)(iv)(A).
"All systems functioned as expected after the trip, and no major components were out of service at the time of the trip. This is a non-complicated trip.
"The NRC resident has been notified."
The reactor tripped at 15% steam generator level and then level went off scale low as expected. All control rods fully inserted. No primary or secondary safeties or relief valves lifted with the exception of a feed heater relief valve. The plant is feeding steam generators with the motor driven auxiliary feed water pumps and dumping decay heat to the main condenser. The plant is in the normal shutdown electrical lineup.
"At 13:54 on 8/28/07, DC Cook Unit 1 experienced an automatic reactor trip due to low steam generator water level coincident with low feedwater flow on #11 steam generator. The cause was a malfunction of the Main Feedwater Pump Digital Control System, which remains under investigation. This requires a 4-hour report under 10CFR50.72(b)(2)(iv)(B).
"Both Motor-Driven Auxiliary Feedwater Pumps automatically started due to the reactor trip. The Turbine-Driven Auxiliary Feedwater Pump (TDAFP) started automatically due to low-low water levels in at least two steam generators, which is expected for a reactor trip from 100% power. The automatic actuation of the reactor protection system and the TDAFP start require an 8-hour report under 10CFR50.72(b)(3)(iv)(A).
"All systems functioned as expected after the trip, and no major components were out of service at the time of the trip. This is a non-complicated trip.
"The NRC resident has been notified."
The reactor tripped at 15% steam generator level and then level went off scale low as expected. All control rods fully inserted. No primary or secondary safeties or relief valves lifted with the exception of a feed heater relief valve. The plant is feeding steam generators with the motor driven auxiliary feed water pumps and dumping decay heat to the main condenser. The plant is in the normal shutdown electrical lineup.