Event Notification Report for August 11, 2007
U.S. Nuclear Regulatory Commission
Operations Center
EVENT REPORTS FOR
08/10/2007 - 08/11/2007
EVENT NUMBERS
43560
Power Reactor
Event Number: 43560
Facility: BROWNS FERRY
Region: 2 State: AL
Unit: [1] [] []
RX Type: [1] GE-4,[2] GE-4,[3] GE-4
NRC Notified By: TIM BOLAND
HQ OPS Officer: JOHN KNOKE
Region: 2 State: AL
Unit: [1] [] []
RX Type: [1] GE-4,[2] GE-4,[3] GE-4
NRC Notified By: TIM BOLAND
HQ OPS Officer: JOHN KNOKE
Notification Date: 08/11/2007
Notification Time: 21:25 [ET]
Event Date: 08/11/2007
Event Time: 17:51 [CDT]
Last Update Date: 08/11/2007
Notification Time: 21:25 [ET]
Event Date: 08/11/2007
Event Time: 17:51 [CDT]
Last Update Date: 08/11/2007
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(iv)(B) - RPS ACTUATION - CRITICAL 50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION
10 CFR Section:
50.72(b)(2)(iv)(B) - RPS ACTUATION - CRITICAL 50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION
Person (Organization):
RANDY MUSSER (R2)
RANDY MUSSER (R2)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 1 | A/R | Y | 100 | Power Operation | 0 | Hot Shutdown |
AUTOMATIC SCRAM DUE TO NEUTRON MONITORING TRIP SIGNAL
"On 08/11/2007 at 1751 CDT, Browns Ferry Unit 1 received an Automatic SCRAM due to a Neutron Monitoring (APRM) Trip Signal . Preliminary investigation indicates the trip signal was caused by a Recirculation System Flow Transmitter sensing line becoming separated giving an indicated low flow signal to the neutron monitoring system. With the indicated low flow and high (100%) power, the neutron monitoring system initiated an APRM Simulated Thermal Power Flow Biased Reactor Scram. All control rods inserted and all systems responded as required to the automatic SCRAM signal. No Emergency Core Cooling System (ECCS) initiations occurred as a result of the SCRAM. Reactor water level lowered below Level 3 (+2") (lowest indicated level reached -33") as a result of the SCRAM and was recovered to the normal level band by the Reactor Feed Pumps (RFPs). The expected Primary Containment Isolation System (PCIS) Groups 2, 3, 6, and 8 isolations were received due to Reactor Water Level lowering below Level 3 (+2") (lowest indicated level reached -33") with all systems isolating as required. Reactor pressure is being controlled using Main Steam Bypass Valves. Reactor Level is being maintained in band using Reactor Feed Pumps. Plant to remain in Mode 3 and initiate repairs to the failed sensing line. Investigation into the event is proceeding.
"This event is reportable under 10CFR50.72(b)(2)(iv)(B), any event or condition that results in a valid actuation of the Reactor Protection System; 10CFR50.72(b)(3)(iv)(A), any event that results in an actuation of the specified systems. This event also requires a 60 day written report in accordance with 10CFR50.73(a)(2)(iv)(A).
"The NRC Senior Resident Inspector has been informed of this event."
The sensing line had a flow limiter on it and the line was isolated locally. Amount of leakage not known at this time.
"On 08/11/2007 at 1751 CDT, Browns Ferry Unit 1 received an Automatic SCRAM due to a Neutron Monitoring (APRM) Trip Signal . Preliminary investigation indicates the trip signal was caused by a Recirculation System Flow Transmitter sensing line becoming separated giving an indicated low flow signal to the neutron monitoring system. With the indicated low flow and high (100%) power, the neutron monitoring system initiated an APRM Simulated Thermal Power Flow Biased Reactor Scram. All control rods inserted and all systems responded as required to the automatic SCRAM signal. No Emergency Core Cooling System (ECCS) initiations occurred as a result of the SCRAM. Reactor water level lowered below Level 3 (+2") (lowest indicated level reached -33") as a result of the SCRAM and was recovered to the normal level band by the Reactor Feed Pumps (RFPs). The expected Primary Containment Isolation System (PCIS) Groups 2, 3, 6, and 8 isolations were received due to Reactor Water Level lowering below Level 3 (+2") (lowest indicated level reached -33") with all systems isolating as required. Reactor pressure is being controlled using Main Steam Bypass Valves. Reactor Level is being maintained in band using Reactor Feed Pumps. Plant to remain in Mode 3 and initiate repairs to the failed sensing line. Investigation into the event is proceeding.
"This event is reportable under 10CFR50.72(b)(2)(iv)(B), any event or condition that results in a valid actuation of the Reactor Protection System; 10CFR50.72(b)(3)(iv)(A), any event that results in an actuation of the specified systems. This event also requires a 60 day written report in accordance with 10CFR50.73(a)(2)(iv)(A).
"The NRC Senior Resident Inspector has been informed of this event."
The sensing line had a flow limiter on it and the line was isolated locally. Amount of leakage not known at this time.