Event Notification Report for July 28, 2007

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
07/27/2007 - 07/28/2007

EVENT NUMBERS
43534

Power Reactor
Event Number: 43534
Facility: BEAVER VALLEY
Region: 1     State: PA
Unit: [1] [2] []
RX Type: [1] W-3-LP,[2] W-3-LP
NRC Notified By: DAVE HELD
HQ OPS Officer: JOE O'HARA
Notification Date: 07/28/2007
Notification Time: 19:24 [ET]
Event Date: 07/28/2007
Event Time: 16:57 [EDT]
Last Update Date: 07/28/2007
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(xi) - OFFSITE NOTIFICATION
Person (Organization):
JOHN WHITE (R1)
MICHAEL TSCHILTZ (NRR)
THOMAS BLOUNT (IRD)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
2 N Y 100 Power Operation 100 Power Operation
Event Text
OFFSITE NOTIFICATION TO FIRE DEPARTMENT

"At 1605 hours on 7/28/07, an offsite breaker in the Beaver Valley Power Station Switchyard developed a failed 'B' phase which resulted in a fire and a subsequent 'B' phase insulator failure. Station fire brigade personnel were dispatched. Offsite assistance was requested at 1657 hours. The fire was extinguished at 1747 hours. The offsite fire department left the site at 1806 hours.

"The circuit containing the failed breaker is associated with a local steel manufacturer and is not a feeder to Beaver Valley Power Station. This is a 4 hour reportable event per 10CFR50.72(b)(2)(xi), Notification to Offsite Governmental Agencies. The operation of BVPS Unit 1 plant systems are not affected by this event. At BVPS Unit 2, the non safety related station air compressors tripped during this event. A backup air compressor was manually started. These compressors were reset and restarted locally without impacting the operation of Beaver Valley Unit 2.

"No EAL criteria was met for this event."

The licensee intends to issue a press release. The NRC Resident Inspector has been notified