Event Notification Report for May 15, 2007
U.S. Nuclear Regulatory Commission
Operations Center
EVENT REPORTS FOR
05/14/2007 - 05/15/2007
Power Reactor
Event Number: 43363
Facility: PERRY
Region: 3 State: OH
Unit: [1] [] []
RX Type: [1] GE-6
NRC Notified By: ROBERT KIDDER
HQ OPS Officer: MARK ABRAMOVITZ
Region: 3 State: OH
Unit: [1] [] []
RX Type: [1] GE-6
NRC Notified By: ROBERT KIDDER
HQ OPS Officer: MARK ABRAMOVITZ
Notification Date: 05/15/2007
Notification Time: 01:53 [ET]
Event Date: 05/15/2007
Event Time: 00:58 [EDT]
Last Update Date: 05/17/2007
Notification Time: 01:53 [ET]
Event Date: 05/15/2007
Event Time: 00:58 [EDT]
Last Update Date: 05/17/2007
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(iv)(B) - RPS ACTUATION - CRITICAL
10 CFR Section:
50.72(b)(2)(iv)(B) - RPS ACTUATION - CRITICAL
Person (Organization):
MARK RING (R3)
ELMO COLLINS (NRR)
MARK RING (R3)
ELMO COLLINS (NRR)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 1 | A/R | Y | 30 | Power Operation | 0 | Hot Shutdown |
REACTOR SCRAM DURING TESTING
"An automatic reactor scram occurred due to lowering reactor water level. Digital feedwater tuning activities were in progress at the time of the scram. All systems functioned as designed. The reactor water level has been restored to normal level band. The plant is stable in Hot Shutdown. There were no ECCS injections."
At the time of the scram, the feedwater pump was in manual control for feedwater tuning. When water level started going down quickly, the operator was not able to restore sufficient feedwater flow before the level 3 (water level low) actuation. All control rods fully inserted on the scram. No valves repositioned and no safety or relief valves lifted after the scram. Reactor water level is being maintained with the motor feed pump and decay heat is being removed to the main condenser. The plant is in the normal shutdown electrical lineup. Reactor pressure is 509 psi and stable.
The licensee notified the NRC Resident Inspector.
* * * UPDATE FROM FREDERICK SMITH TO FANGIE JONES ON 05/17/07 AT 1301 * * *
"This call is to clarify information provided in notification Event Number 43363 made by the Perry Nuclear Power Plant on May 15, 2007. The second paragraph, fourth sentence of the notification states: 'No valves repositioned and no safety or relief valves lifted after the scram.' The intent of the portion of the sentence 'No valves repositioned' was supposed to be in reference to the reporting requirement in 10 CFR 50.72(b)(3)(iv) to report any event or condition that results in valid actuation of general containment isolation signals affecting containment isolation valves in more than one system or multiple main steam isolation valves (MSIVs).
"The event on May 15, 2007, did not meet the 'containment isolation valves in more than one system / MSIVs criterion', however, subsequent review of the event identified that Residual Heat Removal 'B' Heat Exchanger Second Vent to Suppression Pool Containment Isolation Valve 1E12-F073B, closed, as designed, in response to the reactor coolant level 3 (water level low) condition that was present during the event. No additional reporting criteria have been identified and this update has been provided to clarify the earlier statement.
"The NRC Resident Inspector has been notified."
Notified R3 RDO, (Ring), and NRR EO, (Ross Lee).
"An automatic reactor scram occurred due to lowering reactor water level. Digital feedwater tuning activities were in progress at the time of the scram. All systems functioned as designed. The reactor water level has been restored to normal level band. The plant is stable in Hot Shutdown. There were no ECCS injections."
At the time of the scram, the feedwater pump was in manual control for feedwater tuning. When water level started going down quickly, the operator was not able to restore sufficient feedwater flow before the level 3 (water level low) actuation. All control rods fully inserted on the scram. No valves repositioned and no safety or relief valves lifted after the scram. Reactor water level is being maintained with the motor feed pump and decay heat is being removed to the main condenser. The plant is in the normal shutdown electrical lineup. Reactor pressure is 509 psi and stable.
The licensee notified the NRC Resident Inspector.
* * * UPDATE FROM FREDERICK SMITH TO FANGIE JONES ON 05/17/07 AT 1301 * * *
"This call is to clarify information provided in notification Event Number 43363 made by the Perry Nuclear Power Plant on May 15, 2007. The second paragraph, fourth sentence of the notification states: 'No valves repositioned and no safety or relief valves lifted after the scram.' The intent of the portion of the sentence 'No valves repositioned' was supposed to be in reference to the reporting requirement in 10 CFR 50.72(b)(3)(iv) to report any event or condition that results in valid actuation of general containment isolation signals affecting containment isolation valves in more than one system or multiple main steam isolation valves (MSIVs).
"The event on May 15, 2007, did not meet the 'containment isolation valves in more than one system / MSIVs criterion', however, subsequent review of the event identified that Residual Heat Removal 'B' Heat Exchanger Second Vent to Suppression Pool Containment Isolation Valve 1E12-F073B, closed, as designed, in response to the reactor coolant level 3 (water level low) condition that was present during the event. No additional reporting criteria have been identified and this update has been provided to clarify the earlier statement.
"The NRC Resident Inspector has been notified."
Notified R3 RDO, (Ring), and NRR EO, (Ross Lee).
Power Reactor
Event Number: 43364
Facility: ROBINSON
Region: 2 State: SC
Unit: [2] [] []
RX Type: [2] W-3-LP
NRC Notified By: GARRETT SANDERS
HQ OPS Officer: STEVE SANDIN
Region: 2 State: SC
Unit: [2] [] []
RX Type: [2] W-3-LP
NRC Notified By: GARRETT SANDERS
HQ OPS Officer: STEVE SANDIN
Notification Date: 05/15/2007
Notification Time: 14:46 [ET]
Event Date: 05/15/2007
Event Time: 11:16 [EDT]
Last Update Date: 05/15/2007
Notification Time: 14:46 [ET]
Event Date: 05/15/2007
Event Time: 11:16 [EDT]
Last Update Date: 05/15/2007
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(iv)(B) - RPS ACTUATION - CRITICAL 50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION
10 CFR Section:
50.72(b)(2)(iv)(B) - RPS ACTUATION - CRITICAL 50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION
Person (Organization):
MIKE ERNSTES (R2)
MIKE ERNSTES (R2)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 2 | A/R | Y | 82 | Power Operation | 0 | Hot Standby |
AUTOMATIC REACTOR TRIP ON TURBINE TRIP DUE TO DIFFERENTIAL GENERATOR PROTECTION
"At 11:16 am Eastern Daylight Time, a reactor trip occurred at the H. B. Robinson Steam Electric Plant, Unit No. 2. The unit was at approximately 82% reactor power and power level was being increased after restart from a refueling outage that had ended on May 13, 2007. The reactor protection system actuation was identified as a turbine trip signal that caused the reactor trip. The turbine trip signal appears to have been caused by the generator differential protection circuitry. The reactor is currently stable in MODE 3. All control rods indicated fully inserted following the reactor trip. The Auxiliary Feedwater (AFW) System actuated as expected in response to plant conditions, except the 'A' motor-driven AFW pump did not start. The plant operators manually started the 'A' motor-driven AFW pump. The cause of the 'A' AFW pump failure and the cause of the reactor trip are being investigated. The primary system and steam generator power operated relief valves and safety valves did not actuate during this event.
"The normal post-trip electrical lineup is providing power to the plant and the electrical system is stable at this time. Decay heat is currently being removed by use of the normal feedwater system and the condenser steam dumps. The 'B' Main Feedwater Pump also tripped during this event. The 'A' Main Feedwater Pump continued to operate and is being used to supply main feedwater to the steam generators."
The licensee informed the NRC Resident Inspector.
"At 11:16 am Eastern Daylight Time, a reactor trip occurred at the H. B. Robinson Steam Electric Plant, Unit No. 2. The unit was at approximately 82% reactor power and power level was being increased after restart from a refueling outage that had ended on May 13, 2007. The reactor protection system actuation was identified as a turbine trip signal that caused the reactor trip. The turbine trip signal appears to have been caused by the generator differential protection circuitry. The reactor is currently stable in MODE 3. All control rods indicated fully inserted following the reactor trip. The Auxiliary Feedwater (AFW) System actuated as expected in response to plant conditions, except the 'A' motor-driven AFW pump did not start. The plant operators manually started the 'A' motor-driven AFW pump. The cause of the 'A' AFW pump failure and the cause of the reactor trip are being investigated. The primary system and steam generator power operated relief valves and safety valves did not actuate during this event.
"The normal post-trip electrical lineup is providing power to the plant and the electrical system is stable at this time. Decay heat is currently being removed by use of the normal feedwater system and the condenser steam dumps. The 'B' Main Feedwater Pump also tripped during this event. The 'A' Main Feedwater Pump continued to operate and is being used to supply main feedwater to the steam generators."
The licensee informed the NRC Resident Inspector.
General Information or Other
Event Number: 43638
Rep Org: IOWA DEPARTMENT OF PUBLIC HEALTH
Licensee: MIDWEST INDUSTRIAL X-RAY, INC
Region: 3
City: COUNCIL BLUFFS State: IA
County:
License #: IA-0075178IR1
Agreement: Y
Docket:
NRC Notified By: RANDAL DAHLIN
HQ OPS Officer: JASON KOZAL
Licensee: MIDWEST INDUSTRIAL X-RAY, INC
Region: 3
City: COUNCIL BLUFFS State: IA
County:
License #: IA-0075178IR1
Agreement: Y
Docket:
NRC Notified By: RANDAL DAHLIN
HQ OPS Officer: JASON KOZAL
Notification Date: 09/13/2007
Notification Time: 13:41 [ET]
Event Date: 05/15/2007
Event Time: 00:00 [CDT]
Last Update Date: 09/13/2007
Notification Time: 13:41 [ET]
Event Date: 05/15/2007
Event Time: 00:00 [CDT]
Last Update Date: 09/13/2007
Emergency Class: NON EMERGENCY
10 CFR Section:
10 CFR Section:
Person (Organization):
SONIA BURGESS (R3)
MICHELE BURGESS (FSME)
SONIA BURGESS (R3)
MICHELE BURGESS (FSME)
AGREEMENT STATE REPORT - INABILITY TO RETRACT RADIOGRAPHY CAMERA SOURCE
The State provided the following information via email:
"The licensee reported the inability to retract an Ir-192 radiography source (model G-60, serial #OA2910) that contained an activity of 1.45 TBq (39.12 Ci) into a SPEC exposure device (model 150, serial #456). The radiographers had attached the guide tube to a ladder within a tank at the Absolute Energy Ethanol Plant located on the Iowa/Minnesota border. Halfway through a shot, a gust of wind blew the ladder over, which crimped the guide tube such that the source could not be retracted. The radiographers located the source in the guide tube and covered it with sandbags. The crimped guide tube was then reformed using a hammer and the source was successfully retracted. A new guide tube was shipped to the jobsite and the damaged guide tube was destroyed. The two radiographers received exposures of 1.1 and 1 mSv (110 and 100 mrem) from the incident. The licensee submitted a written report to the Iowa Department of Public Health on 6/13/2007, but failed to provide the required 24-hour notification. The State of Minnesota performed an audit of the licensee on 7/12/2007 and it was determined that the incident occurred in Iowa. The root cause of the incident is the failure to properly secure the ladder per company policy. Corrective actions taken by the licensee included terminating the lead radiographer involved and providing additional instruction to all radiographers on the policy to secure ladders used as guide tube stands."
Iowa report number: IA070002
The State provided the following information via email:
"The licensee reported the inability to retract an Ir-192 radiography source (model G-60, serial #OA2910) that contained an activity of 1.45 TBq (39.12 Ci) into a SPEC exposure device (model 150, serial #456). The radiographers had attached the guide tube to a ladder within a tank at the Absolute Energy Ethanol Plant located on the Iowa/Minnesota border. Halfway through a shot, a gust of wind blew the ladder over, which crimped the guide tube such that the source could not be retracted. The radiographers located the source in the guide tube and covered it with sandbags. The crimped guide tube was then reformed using a hammer and the source was successfully retracted. A new guide tube was shipped to the jobsite and the damaged guide tube was destroyed. The two radiographers received exposures of 1.1 and 1 mSv (110 and 100 mrem) from the incident. The licensee submitted a written report to the Iowa Department of Public Health on 6/13/2007, but failed to provide the required 24-hour notification. The State of Minnesota performed an audit of the licensee on 7/12/2007 and it was determined that the incident occurred in Iowa. The root cause of the incident is the failure to properly secure the ladder per company policy. Corrective actions taken by the licensee included terminating the lead radiographer involved and providing additional instruction to all radiographers on the policy to secure ladders used as guide tube stands."
Iowa report number: IA070002