Event Notification Report for May 04, 2007
U.S. Nuclear Regulatory Commission
Operations Center
EVENT REPORTS FOR
05/03/2007 - 05/04/2007
EVENT NUMBERS
4334543346433424334343352
Power Reactor
Event Number: 43345
Facility: RIVER BEND
Region: 4 State: LA
Unit: [1] [] []
RX Type: [1] GE-6
NRC Notified By: JIM SCHROEDER
HQ OPS Officer: JOHN MacKINNON
Region: 4 State: LA
Unit: [1] [] []
RX Type: [1] GE-6
NRC Notified By: JIM SCHROEDER
HQ OPS Officer: JOHN MacKINNON
Notification Date: 05/04/2007
Notification Time: 16:01 [ET]
Event Date: 05/04/2007
Event Time: 12:56 [CDT]
Last Update Date: 05/04/2007
Notification Time: 16:01 [ET]
Event Date: 05/04/2007
Event Time: 12:56 [CDT]
Last Update Date: 05/04/2007
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(iv)(B) - RPS ACTUATION - CRITICAL
10 CFR Section:
50.72(b)(2)(iv)(B) - RPS ACTUATION - CRITICAL
Person (Organization):
NEIL O'KEEFE (R4)
NEIL O'KEEFE (R4)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 1 | M/R | Y | 70 | Power Operation | 0 | Hot Shutdown |
MANUAL REACTOR SCRAM DUE TO LOSS OF COOLING TO NUMBER 2 MAIN TRANSFORMER
"At approximately 1256 CDT on May 4, 2007, a manual reactor scram was initiated following the loss of cooling to the no. 2 main transformer. Reactor power at the time of the scram was approximately 70 percent (initially 100% power). Following the scram, reactor water level briefly decreased below Level 3, resulting in the automatic closure of containment isolation valves in the suppression pool cooling system. This isolation was confirmed to have occurred as designed. Reactor pressure and water level control were promptly established. All control rods inserted, and no emergency injection system operation was required.
"This event is being reported in accordance with 10CFR50.72(b)(2)(iv)(B) as a condition resulting in a manual actuation of the reactor protection system."
The NRC Resident Inspector was notified of this event by the licensee.
"At approximately 1256 CDT on May 4, 2007, a manual reactor scram was initiated following the loss of cooling to the no. 2 main transformer. Reactor power at the time of the scram was approximately 70 percent (initially 100% power). Following the scram, reactor water level briefly decreased below Level 3, resulting in the automatic closure of containment isolation valves in the suppression pool cooling system. This isolation was confirmed to have occurred as designed. Reactor pressure and water level control were promptly established. All control rods inserted, and no emergency injection system operation was required.
"This event is being reported in accordance with 10CFR50.72(b)(2)(iv)(B) as a condition resulting in a manual actuation of the reactor protection system."
The NRC Resident Inspector was notified of this event by the licensee.
Power Reactor
Event Number: 43346
Facility: DRESDEN
Region: 3 State: IL
Unit: [] [2] []
RX Type: [1] GE-1,[2] GE-3,[3] GE-3
NRC Notified By: CHRIS KENT
HQ OPS Officer: MARK ABRAMOVITZ
Region: 3 State: IL
Unit: [] [2] []
RX Type: [1] GE-1,[2] GE-3,[3] GE-3
NRC Notified By: CHRIS KENT
HQ OPS Officer: MARK ABRAMOVITZ
Notification Date: 05/05/2007
Notification Time: 02:13 [ET]
Event Date: 05/04/2007
Event Time: 23:05 [CDT]
Last Update Date: 05/05/2007
Notification Time: 02:13 [ET]
Event Date: 05/04/2007
Event Time: 23:05 [CDT]
Last Update Date: 05/05/2007
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(iv)(A) - ECCS INJECTION 50.72(b)(2)(iv)(B) - RPS ACTUATION - CRITICAL 50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION
10 CFR Section:
50.72(b)(2)(iv)(A) - ECCS INJECTION 50.72(b)(2)(iv)(B) - RPS ACTUATION - CRITICAL 50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION
Person (Organization):
CHRISTINE LIPA (R3)
MICHAEL CASE (NRR)
CHRISTINE LIPA (R3)
MICHAEL CASE (NRR)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 2 | M/R | Y | 100 | Power Operation | 0 | Hot Shutdown |
MANUAL REACTOR SCRAM ON LOSS OF FEEDWATER
The condensate prefilters isolated earlier in the day and the bypass valve automatically opened. The computer controlling these valves was in the process of being replaced when the bypass valve shut.
"Unit experienced a loss of feedwater due to condensate pre-filter valves going closed. The reactor was manually scrammed and HPCI was used to restore reactor water level. MSIVs closed and the U2 and U2/3 EDGs auto started on low level."
All rods fully inserted on the manual scram. Minimum level was approximately -54 inches. Decay heat is being removed using the isolation condenser and level is being maintained with Control Rod Drive leak by. No safety or relief valves lifted during this event. The plant is in the normal shutdown electrical lineup.
The licensee notified the NRC Resident Inspector.
The condensate prefilters isolated earlier in the day and the bypass valve automatically opened. The computer controlling these valves was in the process of being replaced when the bypass valve shut.
"Unit experienced a loss of feedwater due to condensate pre-filter valves going closed. The reactor was manually scrammed and HPCI was used to restore reactor water level. MSIVs closed and the U2 and U2/3 EDGs auto started on low level."
All rods fully inserted on the manual scram. Minimum level was approximately -54 inches. Decay heat is being removed using the isolation condenser and level is being maintained with Control Rod Drive leak by. No safety or relief valves lifted during this event. The plant is in the normal shutdown electrical lineup.
The licensee notified the NRC Resident Inspector.
General Information or Other
Event Number: 43342
Rep Org: TEXAS DEPARTMENT OF HEALTH
Licensee: ALLIANCE LABORATORIES, INC
Region: 4
City: HOUSTON State: TX
County:
License #: L05586
Agreement: Y
Docket:
NRC Notified By: RAY JISHA
HQ OPS Officer: JOHN MacKINNON
Licensee: ALLIANCE LABORATORIES, INC
Region: 4
City: HOUSTON State: TX
County:
License #: L05586
Agreement: Y
Docket:
NRC Notified By: RAY JISHA
HQ OPS Officer: JOHN MacKINNON
Notification Date: 05/04/2007
Notification Time: 11:40 [ET]
Event Date: 05/04/2007
Event Time: 06:00 [CDT]
Last Update Date: 05/04/2007
Notification Time: 11:40 [ET]
Event Date: 05/04/2007
Event Time: 06:00 [CDT]
Last Update Date: 05/04/2007
Emergency Class: NON EMERGENCY
10 CFR Section:
10 CFR Section:
Person (Organization):
NEIL O'KEEFE (R4)
TIM HARRIS (FSME)
ILTAB (e-mailed)
MEXICO (e-mail)
NEIL O'KEEFE (R4)
TIM HARRIS (FSME)
ILTAB (e-mailed)
MEXICO (e-mail)
AGREEMENT STATE REPORT FROM TEXAS - STOLEN HUMBOLDT MOISTURE DENSITY GAUGE.
The following information was provided via e-mail:
"On Friday, May 4, 2007, around 10:20 a.m., the Agency received notification by Alliance Laboratories, Inc., that a 2002 metallic gray Dodge Ram 1500 pickup truck that was carrying a moisture/density gauge, Humboldt Scientific Inc, Model 5001, SN#4455, with two sources 11 mCi of Cs-137, SN 1654CM, and a 44 mCi Am-241, SN NJ04752, was stolen sometime between 0600-0800 hrs. from an apartment complex in Houston, Texas. Houston Police Department has been notified and the case number is 06-4781007B. The Agency also notified the [Headquarters] Operations Officer at the NRC, at 1040 hours, and the event number is 43342."
Texas Incident Number: I-8409.
THIS MATERIAL EVENT CONTAINS A "LESS THAN CAT 3" LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks.
The following information was provided via e-mail:
"On Friday, May 4, 2007, around 10:20 a.m., the Agency received notification by Alliance Laboratories, Inc., that a 2002 metallic gray Dodge Ram 1500 pickup truck that was carrying a moisture/density gauge, Humboldt Scientific Inc, Model 5001, SN#4455, with two sources 11 mCi of Cs-137, SN 1654CM, and a 44 mCi Am-241, SN NJ04752, was stolen sometime between 0600-0800 hrs. from an apartment complex in Houston, Texas. Houston Police Department has been notified and the case number is 06-4781007B. The Agency also notified the [Headquarters] Operations Officer at the NRC, at 1040 hours, and the event number is 43342."
Texas Incident Number: I-8409.
THIS MATERIAL EVENT CONTAINS A "LESS THAN CAT 3" LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks.
Power Reactor
Event Number: 43343
Facility: LASALLE
Region: 3 State: IL
Unit: [1] [2] []
RX Type: [1] GE-5,[2] GE-5
NRC Notified By: ALAN J. McLAUGHLIN
HQ OPS Officer: JOHN MacKINNON
Region: 3 State: IL
Unit: [1] [2] []
RX Type: [1] GE-5,[2] GE-5
NRC Notified By: ALAN J. McLAUGHLIN
HQ OPS Officer: JOHN MacKINNON
Notification Date: 05/04/2007
Notification Time: 12:40 [ET]
Event Date: 05/04/2007
Event Time: 08:53 [CDT]
Last Update Date: 05/04/2007
Notification Time: 12:40 [ET]
Event Date: 05/04/2007
Event Time: 08:53 [CDT]
Last Update Date: 05/04/2007
Emergency Class: NON EMERGENCY
10 CFR Section:
26.73 - FITNESS FOR DUTY
10 CFR Section:
26.73 - FITNESS FOR DUTY
Person (Organization):
CHRISTINE LIPA (R3)
CHRISTINE LIPA (R3)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 1 | N | Y | 100 | Power Operation | 100 | Power Operation |
| 2 | N | Y | 100 | Power Operation | 100 | Power Operation |
FITNESS-FOR-DUTY REPORT INVOLVING A NON-LICENSED SUPERVISOR
A non-licensed employee supervisor had a confirmed positive for alcohol during a random fitness-for-duty test. The employee's access has been suspended. Contact the Headquarters Operations Officer for additional details.
The licensee informed the NRC Resident Inspector.
A non-licensed employee supervisor had a confirmed positive for alcohol during a random fitness-for-duty test. The employee's access has been suspended. Contact the Headquarters Operations Officer for additional details.
The licensee informed the NRC Resident Inspector.
General Information or Other
Event Number: 43352
Rep Org: LOUISIANA RADIATION PROTECTION DIV
Licensee: NONDESTRUCTIVE AND VISUAL INSPECTION
Region: 4
City: State: LA
County:
License #: LA-5601-L01
Agreement: Y
Docket:
NRC Notified By: RICHARD PENROD
HQ OPS Officer: BILL HUFFMAN
Licensee: NONDESTRUCTIVE AND VISUAL INSPECTION
Region: 4
City: State: LA
County:
License #: LA-5601-L01
Agreement: Y
Docket:
NRC Notified By: RICHARD PENROD
HQ OPS Officer: BILL HUFFMAN
Notification Date: 05/08/2007
Notification Time: 15:40 [ET]
Event Date: 05/04/2007
Event Time: 00:00 [CDT]
Last Update Date: 05/16/2007
Notification Time: 15:40 [ET]
Event Date: 05/04/2007
Event Time: 00:00 [CDT]
Last Update Date: 05/16/2007
Emergency Class: NON EMERGENCY
10 CFR Section:
10 CFR Section:
Person (Organization):
VINCENT GADDY (R4)
GREG MORELL (FSME)
VINCENT GADDY (R4)
GREG MORELL (FSME)
AGREEMENT STATE REPORT - LOUISIANA - WORKER OVEREXPOSURE
The State provided the following information via facsimile:
"[A licensee representative] with Nondestructive and Visual inspection notified the Louisiana Department of Environmental Quality on May 4, 2007 of an overexposure. The indicated exposure from the badge reading is 5123 mrem. Additional information will be forwarded once it is received."
Louisiana Event Report ID No.: LA070011
* * * UPDATE FROM LOUISIANA (VIA E-MAIL) TO HUFFMAN AT 11:39 EDT ON 5/16/07 * * *
Upon further investigation, it has been determined that there were two separate incidents where employees of Nondestructive & Visual Inspections, LLC may have exceeded the annual dose limit of 5 rem.
The first incident was the original basis for the above initial notification. "The worker involved] is an industrial radiographer, certified by the State of Louisiana. [The worker] . . .was employed by NVI, LLC from April 30, 2005 until March 29, 2007, at which time he was terminated for violating company policies. [The worker] did not turn in his March 2007 TLD badge.
"In February 2007, [the worker's] lifetime dose equivalent, while employed at NVI, LLC was 5117 millirems. His year to date dose equivalent for 2007 at this time was 132 millirems. His year to date dose equivalent for 2006 was 2535 millirems. This dose includes a calculated dose for the month of December 2006 for a badge that according to [the worker] was lost. On May 1, 2007, NVI, LLC received an exposure notification from Landauer for [the worker's] December 2006 TLD badge of 3156 millirems. This put his year to date dose equivalent for 2006 at 5691 millirems, which exceeds the annual dose limit for radiographers. The lost badge was apparently found and returned to Landauer by mistake. There is no way to determine what dose the badge had been exposed to during the four months that it was unaccounted for.
"[NVI, LLC] has tried on numerous occasions to reach [the worker] by phone to discuss this matter with him. [NVI, LLC] has been unsuccessful in attempts [to reach him] so far.
"The second incident involves another [worker]. [The worker] is an industrial radiographer trainee, certified by the State of Louisiana.. . . .[The worker] has been employed by NVI, LLC, since April 1, 2005.
"On May 4, 2007, [NVI, LLC ] received an exposure notification from Landauer. [The worker's] dose for the month of March 2007 was 5363 millirems. His year to date dose equivalent for 2007 is 5514 millirems. [NVI, LLC] notified [the worker] immediately and informed him that he could not perform radiography. [NVI, LLC] met with [the worker] the same day and discussed the overexposure. [The worker] stated that there was no way possible that he could have receive such a dose. He stated that at no time did he ever go offscale or have any type of incident or accident while performing his duties during the month of March 2007. . . .[The worker] is still employed by NVI, LLC and has been reassigned to perform other NDT methods that do not include radiography."
R4DO (Bywater) and FSME (Morell) have been notified.
The State provided the following information via facsimile:
"[A licensee representative] with Nondestructive and Visual inspection notified the Louisiana Department of Environmental Quality on May 4, 2007 of an overexposure. The indicated exposure from the badge reading is 5123 mrem. Additional information will be forwarded once it is received."
Louisiana Event Report ID No.: LA070011
* * * UPDATE FROM LOUISIANA (VIA E-MAIL) TO HUFFMAN AT 11:39 EDT ON 5/16/07 * * *
Upon further investigation, it has been determined that there were two separate incidents where employees of Nondestructive & Visual Inspections, LLC may have exceeded the annual dose limit of 5 rem.
The first incident was the original basis for the above initial notification. "The worker involved] is an industrial radiographer, certified by the State of Louisiana. [The worker] . . .was employed by NVI, LLC from April 30, 2005 until March 29, 2007, at which time he was terminated for violating company policies. [The worker] did not turn in his March 2007 TLD badge.
"In February 2007, [the worker's] lifetime dose equivalent, while employed at NVI, LLC was 5117 millirems. His year to date dose equivalent for 2007 at this time was 132 millirems. His year to date dose equivalent for 2006 was 2535 millirems. This dose includes a calculated dose for the month of December 2006 for a badge that according to [the worker] was lost. On May 1, 2007, NVI, LLC received an exposure notification from Landauer for [the worker's] December 2006 TLD badge of 3156 millirems. This put his year to date dose equivalent for 2006 at 5691 millirems, which exceeds the annual dose limit for radiographers. The lost badge was apparently found and returned to Landauer by mistake. There is no way to determine what dose the badge had been exposed to during the four months that it was unaccounted for.
"[NVI, LLC] has tried on numerous occasions to reach [the worker] by phone to discuss this matter with him. [NVI, LLC] has been unsuccessful in attempts [to reach him] so far.
"The second incident involves another [worker]. [The worker] is an industrial radiographer trainee, certified by the State of Louisiana.. . . .[The worker] has been employed by NVI, LLC, since April 1, 2005.
"On May 4, 2007, [NVI, LLC ] received an exposure notification from Landauer. [The worker's] dose for the month of March 2007 was 5363 millirems. His year to date dose equivalent for 2007 is 5514 millirems. [NVI, LLC] notified [the worker] immediately and informed him that he could not perform radiography. [NVI, LLC] met with [the worker] the same day and discussed the overexposure. [The worker] stated that there was no way possible that he could have receive such a dose. He stated that at no time did he ever go offscale or have any type of incident or accident while performing his duties during the month of March 2007. . . .[The worker] is still employed by NVI, LLC and has been reassigned to perform other NDT methods that do not include radiography."
R4DO (Bywater) and FSME (Morell) have been notified.