Skip to main content

Event Notification Report for March 27, 2007

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
03/26/2007 - 03/27/2007

EVENT NUMBERS
432614325943296

General Information or Other
Event Number: 43261
Rep Org: GEORGIA RADIOACTIVE MATERIAL PGM
Licensee: NOVA ENGINEERING
Region: 1
City:   State: GA
County: Fayette
License #: GA-1323-1
Agreement: Y
Docket:
NRC Notified By: ERIC JAMESON
HQ OPS Officer: BILL HUFFMAN
Notification Date: 03/28/2007
Notification Time: 16:44 [ET]
Event Date: 03/27/2007
Event Time: 00:00 [EDT]
Last Update Date: 03/28/2007
Emergency Class: NON EMERGENCY
10 CFR Section:
Person (Organization):
ANTHONY DIMITRIADIS (R1)
LARRY CAMPER (FSME)
Event Text
AGREEMENT STATE - GEORGIA - DAMAGED DENSITY GAUGE

The State provided the following information via email:

"Nova personnel had placed the portable density gauge on the tailgate of the truck and drove off prior to secure the gauge to the truck bed. The Radiation Safety Officer (RSO) of Nova was notified of the incident and responded to the scene. The RSO stated the gauge case had broken apart and the circuit board on the gauge had been damaged. He had surveyed the source rod and source and based on the measurements determined the source rod to be intact and the source not leaking. The fire department and the County had the area secured until it was determined the gauge could be packed up and removed from the road. The RSO stated he would send the gauge to Regis [a gauge repair firm] for either disposal or repair. "

Georgia Report GA-2007-07


Power Reactor
Event Number: 43259
Facility: SALEM
Region: 1     State: NJ
Unit: [1] [] []
RX Type: [1] W-4-LP,[2] W-4-LP
NRC Notified By: JASON HANCOCK
HQ OPS Officer: JASON KOZAL
Notification Date: 03/28/2007
Notification Time: 01:51 [ET]
Event Date: 03/27/2007
Event Time: 20:50 [EDT]
Last Update Date: 03/28/2007
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION
Person (Organization):
ANTHONY DIMITRIADIS (R1)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N N 0 Hot Standby 0 Hot Standby
Event Text
LOW STEAM GENERATOR WATER LEVEL INITIATED AUXILIARY FEEDWATER SIGNAL AND A REACTOR TRIP SIGNAL

"This 8-hour notification is being made to report that an Auxiliary Feedwater (AFW) system actuation signal was generated and a Reactor Protective Signal (RPS) generated with the reactor subcritical.

"On March 27, 2007 at approximately 2050, Salem Unit 1 was in Mode 3 following a planned manual reactor trip to begin a scheduled refueling outage. Operators had established initial Reactor Coolant System cooldown using the steam dumps for heat removal and the 11, 12, and 13 AFW pumps for steam generator make-up. All three pumps had been previously placed in-service in accordance with plant procedures. As plant cooldown proceeded, narrow range levels in 11, 12, and 13 Steam Generators reached the low steam generator setpoint trip, resulting in a valid ESF actuation (i.e., start signal to the AFW pumps); however all AFW pumps were already in-service.

"The actuation signal also generated a reactor trip signal to be initiated by the reactor protection system; however, the plant was already in a shutdown condition with the reactor trip breakers open.

"The lowest level during this transient occurred in 13 Steam Generator and was 11.3% narrow range level. Steam generator water level was restored to a normal value and the RCS cooldown recommenced. There were no equipment failures that contributed to this event.

"The NRC Resident has been informed."


General Information or Other
Event Number: 43296
Rep Org: MA RADIATION CONTROL PROGRAM
Licensee: ALLEGHENY RODNEY
Region: 1
City: NEW BEDFORD   State: MA
County:
License #: 15-7052
Agreement: Y
Docket:
NRC Notified By: BRUCE PACKARD
HQ OPS Officer: JEFF ROTTON
Notification Date: 04/11/2007
Notification Time: 14:23 [ET]
Event Date: 03/27/2007
Event Time: 00:00 [EDT]
Last Update Date: 04/11/2007
Emergency Class: NON EMERGENCY
10 CFR Section:
Person (Organization):
NEIL PERRY (R1)
GREG MORELL (FSME)
Event Text
AGREEMENT STATE REPORT - MALFUNCTIONING SHUTTER

The State provided the following information via facsimile:

The licensee uses a Themo Electron Model SR-U2 device, serial number 1179BC, to measure thickness. The device contains a Sr-90 50 millicurie source. On 03/27/07 the gauge shutter stuck open. The unit was secured by restricting access to the one door that leads to the area where the gauge is located. The gauge vendor has been called. On 03/30/07, a contractor, RSI, came in to repair the broken spring on the gauge.