Skip to main content

Event Notification Report for March 16, 2007

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
03/15/2007 - 03/16/2007

EVENT NUMBERS
432484324343244

Other Nuclear Material
Event Number: 43248
Rep Org: KAMPNER IRON AND STEEL
Licensee: UNKNOWN
Region: 1
City: HOOVERSVILLE   State: PA
County:
License #: UNKNOWN
Agreement: N
Docket:
NRC Notified By: ANTHONY HULL
HQ OPS Officer: BILL HUFFMAN
Notification Date: 03/19/2007
Notification Time: 12:31 [ET]
Event Date: 03/16/2007
Event Time: 00:00 [EDT]
Last Update Date: 03/19/2007
Emergency Class: NON EMERGENCY
10 CFR Section:
Person (Organization):
MEL GRAY (R1)
GREG MORELL (FSME)
Event Text
ORPHAN SOURCE FOUND IN STATE OF PENNSYLVANIA DURING SCRAP METAL RECYCLING

A truck carrying a load of scrap metal set off a rad alarm at a metal recycling facility. The truck returned to its origin (Kampner Iron and Steel) where the source of the radioactivity was found to be a TN Technologies gauge Model 5191 (Serial number B927) containing a 200 millicurie source of Cs-137. TN Technologies was contacted and it was determined that the gauge was purchase under a general license by Rapco Inc of Tennessee in 1977. It is believed that the gauge was used for process measurements of fluidized coal flow.

A health physics contractor for Kampner Iron and Steel (Applied Health Physics) and a representative for the State of Pennsylvania were present when the gauge was recovered. Field testing indicated that the source was intact and no contamination present. The gauge was place in a drum and locked in a secured location at Kampner Iron and Steel and posted per regulations.

Based on radiation measurements, the health physics contractor does not believe that the source resulted in any personnel exposures. Kampner Steel has been in contact with TN Technologies on options for retrieval of the gauge. Investigation into the status of Rapco Inc and how the gauge wound up as scrap are also in progress.

The NRC Region 1 Office (Lodhi) has been notified.

THIS MATERIAL EVENT CONTAINS A "LESS THAN CAT 3" LEVEL OF RADIOACTIVE MATERIAL

Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks.

Although IAEA categorization of this event is typically based on device type, the staff has been made aware of the actual activity of the source, and after calculation determines that it is a Less than Cat 3 event.

Note: the value assigned by device type "Category 3" is different than the calculated value "Less than Cat 3"


Power Reactor
Event Number: 43243
Facility: GINNA
Region: 1     State: NY
Unit: [1] [] []
RX Type: [1] W-2-LP
NRC Notified By: KYLE GARNISH
HQ OPS Officer: PETE SNYDER
Notification Date: 03/17/2007
Notification Time: 02:13 [ET]
Event Date: 03/16/2007
Event Time: 22:09 [EDT]
Last Update Date: 03/17/2007
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(iv)(B) - RPS ACTUATION - CRITICAL 50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION
Person (Organization):
CHRIS HOTT (R1)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 A/R Y 100 Power Operation 0 Hot Standby
Event Text
AUTOMATIC REACTOR TRIP CAUSED BY SAFETY INJECTION SIGNAL

At 2209 on 3/16/07, the plant tripped on a Safety Injection (SI) signal initiated because of low main steam line pressure in the 'A' main steam loop. The licensee is currently conducting a post trip review but believes that the low main steam line pressure in 'A' loop was caused by a spurious isolation of the 'B' Main Steam Line Isolation Valve (MSIV). The isolation in the 'B' main steam loop lead to high main steam flow and low main steam line pressure in the 'A' main steam loop. The 'A' MSIV then also auto-closed on the SI signal.

The plant is currently stable in Mode 3 at about 2235 psig pressure and 547 degrees average Reactor Coolant System (RCS) temperature. All control rods fully inserted on the trip. Decay heat is currently being removed by auxiliary feedwater feeding the steam generators and steaming out the plant atmospheric steam valves. Since plant pressure did not decrease below 1500 psig, SI did not actually inject into the RCS. The licensee secured SI. No primary PORV's or safety valves lifted. No main steam safeties lifted according to plant closure indicators. There are no primary to secondary steam generator tube leaks.

All electrical safeguards buses are powered by offsite power. The Emergency Diesel Generators (EDG) started but did not load and were shut down. The EDGs are operable and available if needed.

The licensee notified the NRC Resident Inspector.


Fuel Cycle Facility
Event Number: 43244
Facility: BWX TECHNOLOGIES, INC.
Region: 2     State: VA
Unit: [] [] []
RX Type: URANIUM FUEL FABRICATION
NRC Notified By: BARRY COLE
HQ OPS Officer: BILL HUFFMAN
Notification Date: 03/17/2007
Notification Time: 13:20 [ET]
Event Date: 03/16/2007
Event Time: 21:00 [EDT]
Last Update Date: 05/11/2008
Emergency Class: NON EMERGENCY
10 CFR Section:
74.57 - ALARM RESOLUTION
Person (Organization):
JOSEPH GIITTER (FSME)
JAMES MOORMAN (R2)
FUEL-OUO GROUP EMAIL
Event Text
* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *
THIS IS NOT A NEW REPORT.

This event report was originally withheld from public release under the NRC's policy for protecting sensitive unclassified information. The NRC has reevaluated this policy and is now making this event report available to the public with suitable redactions.
* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

MATERIAL CONTROL AND ACCOUNTING PROCESS MONITORING ALARM RESOLUTION

"In accordance with 10CFR74.57(f)(2), a report to NRC is required for the following event. On March 16, 2007 the Alarm Threshold Limit was exceeded for [DELETED] Extraction (Column Based) System. This was officially reported to the Measurement Control Unit Manager on March 16, 2007 at approximately 21:00. The time in which the potential alarm situation was initially reported to Measurement Control personnel was approximately 12:00 on March 16, 2007. A re-analysis of the process material cleared the alarm at approximately 13:00 on March 17, 2007. The initial test difference exceeded the Alarm Threshold Limit. The final difference after re-analysis was below the Alarm Threshold Limit.

"Per E41-116 and the Fundamental Nuclear Material Control Plan (FNMCP), an Alarm Investigation Team was established since a process monitoring test exceeded its Alarm Threshold Limit."

The licensee secured the process while investigating the alarm condition but subsequently restarted once the alarm was verified cleared.

The licensee notified the NRC Resident Inspector and the NRC Project Manager.

* * * UPDATE 05/11/08 BY P. SNYDER * * *

THIS IS NOT A NEW REPORT.

This event report was originally withheld from public release under the NRC's policy for protecting sensitive unclassified information. The NRC has reevaluated this policy and is now making this event report available to the public with suitable redactions.