Skip to main content

Event Notification Report for January 11, 2007

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
01/10/2007 - 01/11/2007

EVENT NUMBERS
430904309243093430944309543286

Fuel Cycle Facility
Event Number: 43090
Facility: NUCLEAR FUEL SERVICES INC.
Region: 2     State: TN
Unit: [] [] []
RX Type: URANIUM FUEL FABRICATION
Comments: HEU CONVERSION & SCRAP RECOVERY
NAVAL REACTOR FUEL CYCLE
LEU SCRAP RECOVERY
NRC Notified By: NICHOLAS BROWN
HQ OPS Officer: MARK ABRAMOVITZ
Notification Date: 01/11/2007
Notification Time: 12:13 [ET]
Event Date: 01/11/2007
Event Time: 11:15 [EST]
Last Update Date: 05/11/2008
Emergency Class: NON EMERGENCY
10 CFR Section:
PART 70 APP A (a)(5) - ONLY ONE SAFETY ITEM AVAILABLE
Person (Organization):
MALCOLM WIDMANN (R2)
GREG MORELL (NMSS)
Event Text
* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *
THIS IS NOT A NEW REPORT.

This event report was originally withheld from public release under the NRC's policy for protecting sensitive unclassified information. The NRC has reevaluated this policy and is now making this event report available to the public with suitable redactions.
* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

FAILURE OF GAMMA SPECTROMETER WASTE MONITOR

"A routine-6-month calibration was performed on the [DELETED] condensate discharge inline monitor system. The calibration identified that the gamma spectrometer. Monitoring system was not functional. The system failed all calibration efforts including a self-check. This piece of equipment is an active engineered IROFS [Item Relied On For Safety] for discharge of low-level condensate waste. The failure of this IROFS leaves only one other IROFS in place but fails to meet the minimum performance criteria. This equipment may have been in a failed state for more than eight hours. The remaining IROFS that remains intact is sampling the waste prior to discharge.

"There were no actual safety consequences to the workers, the public, or the environment due to the low level of waste discharged through this system.

"All waste discharges have been suspended until equipment functionality can be demonstrated. A complete review of recent discharges through this system is underway to ensure that all discharges have been according to approved discard limits. The receiving tanks are also being sampled to confirm that the uranium concentration is within approved limits.

"All waste discharges from other plant facilities having similar monitoring equipment have been suspended until equipment functionality can be demonstrated."

* * * UPDATE ON 05/11/08 BY H. Crouch * * *

THIS IS NOT A NEW REPORT.

This event report was originally withheld from public release under the NRC's policy for protecting sensitive unclassified information. The NRC has reevaluated this policy and is now making this event report available to the public with suitable redactions.
* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *


Power Reactor
Event Number: 43092
Facility: BROWNS FERRY
Region: 2     State: AL
Unit: [] [2] []
RX Type: [1] GE-4,[2] GE-4,[3] GE-4
NRC Notified By: RODNEY NACOSTE
HQ OPS Officer: MARK ABRAMOVITZ
Notification Date: 01/11/2007
Notification Time: 13:16 [ET]
Event Date: 01/11/2007
Event Time: 08:16 [CST]
Last Update Date: 01/11/2007
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(iv)(B) - RPS ACTUATION - CRITICAL 50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION
Person (Organization):
MALCOLM WIDMANN (R2)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 A/R Y 100 Power Operation 0 Hot Shutdown
Event Text
REACTOR SCRAM WHEN TURBINE OUTPUT BREAKERS OPENED

"Unit 2 reactor scrammed due to a main turbine trip. PCIS [Primary Containment Isolation Signal] groups 2, 3,and 6 isolated, CREV [Control Room Emergency Ventilation] A, SBGT [Standby Gas Treatment] trains A, B, and C started as expected. All control rods fully inserted, eight main steam relief valves lifted and no ECCS actuations occurred. This event is reportable within four hours according to 10CFR50.72(b)(2)(iv)(B) and eight hours according to 10CFR50.72(b)(3)(iv)(A)."

The turbine trip was the result of the 500kV main output breaker opening causing the generator output breaker to open. All relief valves fully seated during the scram recovery. The reactor water level is being maintained using normal feedwater and decay heat is being removed using the steam dumps. The plant is using the startup transformer for electrical power.

The cause of the 500kV breaker opening is under investigation.

The licensee will notify the NRC Resident Inspector.


Power Reactor
Event Number: 43093
Facility: PILGRIM
Region: 1     State: MA
Unit: [1] [] []
RX Type: [1] GE-3
NRC Notified By: MICHAEL HETTWER
HQ OPS Officer: JOHN KNOKE
Notification Date: 01/11/2007
Notification Time: 16:59 [ET]
Event Date: 01/11/2007
Event Time: 10:00 [EST]
Last Update Date: 01/11/2007
Emergency Class: NON EMERGENCY
10 CFR Section:
26.73 - FITNESS FOR DUTY
Person (Organization):
RONALD BELLAMY (R1)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
Event Text
FITNESS FOR DUTY

A non-licensed contract employee supervisor had a confirmed positive result during the initial fitness-for-duty test. The employee's access to the plant has been denied. Contact the Headquarters Operations Officer for additional details.

The licensee notified the NRC Resident Inspector.


Power Reactor
Event Number: 43094
Facility: MILLSTONE
Region: 1     State: CT
Unit: [] [2] []
RX Type: [1] GE-3,[2] CE,[3] W-4-LP
NRC Notified By: CLIFFORD CHAPIN
HQ OPS Officer: JOHN KNOKE
Notification Date: 01/11/2007
Notification Time: 17:40 [ET]
Event Date: 01/11/2007
Event Time: 07:10 [EST]
Last Update Date: 01/11/2007
Emergency Class: NON EMERGENCY
10 CFR Section:
26.73 - FITNESS FOR DUTY
Person (Organization):
RONALD BELLAMY (R1)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 N Y 100 Power Operation 100 Power Operation
Event Text
FITNESS FOR DUTY

A licensed employee had a for cause fitness-for-duty test performed and was determined to be unfit for standing duty. The employee's access to the plant has been restricted pending review. Contact the Headquarters Operations Officer for additional details.

The licensee notified the NRC Resident Inspector.


Power Reactor
Event Number: 43095
Facility: MONTICELLO
Region: 3     State: MN
Unit: [1] [] []
RX Type: [1] GE-3
NRC Notified By: ROBERT SCHREIFELS
HQ OPS Officer: JOHN KNOKE
Notification Date: 01/11/2007
Notification Time: 19:09 [ET]
Event Date: 01/11/2007
Event Time: 17:30 [CST]
Last Update Date: 01/11/2007
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(xi) - OFFSITE NOTIFICATION
Person (Organization):
THOMAS KOZAK (R3)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N N 0 Cold Shutdown 0 Cold Shutdown
Event Text
OFFSITE NOTIFICATION TO STATE AGENCIES

"Notification to NRC following notification to the following government agencies:

State of Minnesota Pollution Control Agency
State of Minnesota Dept of Natural Resources Enforcement
State of Minnesota Dept of Natural Resources Area Fisheries Office
State of Minnesota Dept of Natural Resources Local Conservation Office

Notifications made to above government agencies in accordance with Monticello Nuclear Plant water appropriations permit for fish kill in Mississippi river following Rx scram on 1-10-07."

The licensee will notify the NRC Resident Inspector.


Power Reactor
Event Number: 43286
Facility: NINE MILE POINT
Region: 1     State: NY
Unit: [] [2] []
RX Type: [1] GE-2,[2] GE-5
NRC Notified By: CHRIS SKINNER
HQ OPS Officer: JOHN KNOKE
Notification Date: 04/06/2007
Notification Time: 14:50 [ET]
Event Date: 01/11/2007
Event Time: 12:11 [EDT]
Last Update Date: 04/06/2007
Emergency Class: NON EMERGENCY
10 CFR Section:
Person (Organization):
HAROLD GRAY (R1)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 N Y 100 Power Operation 100 Power Operation
Event Text
INITIATION OF INVALID PRIMARY CONTAINMENT ISOLATION SIGNALS

"This is not an L.E.R. The report is being made to the NRC under 10 CFR 50.73(a)(2)(iv)(A), and the 60 day telephone notification option under 10 CFR 50.73(a)(1). The event included invalid 'general containment isolation signals affecting containment isolation valves in more than one system' as discussed in 10 CFR 50.73(a)(2)(iv)(B).

"(a) 'The specific train(s) and systems that were actuated.'

"On January 11, 2007 at 12:11 hours, Unit 2 received invalid Primary Containment Isolation signals to both Group 5 (RHR Shutdown Cooling System Isolation valves) and Group 10 (Reactor Core Isolation System Isolation valves) during instrumentation surveillance testing. While performing testing of the Division I Group 5 and Group 10 isolation functions of the RHR ambient temperature instrumentation, Technicians omitted a procedural step, resulting in the invalid signal actuations.

"(b) 'Whether each train actuation was complete or partial.'

"The event resulted in closure of the RCIC steam supply header outboard containment isolation valve. The Division 1 RHR Shutdown Cooling System isolation valves were already closed at the time of the isolation signal.

"(c) 'Whether or not the system started and functioned as designed,'

"The Primary Containment Isolation instrumentation logic and associated valve closure function (for RCIC) actuated as designed. The reporting of this event exceeds the 60 day notification requirement as a result of initially not fully understanding the impact of the invalid signal actuation. This condition has been entered into the Corrective Action Program."

The licensee notified the NRC Resident Inspector.