Skip to main content

Event Notification Report for December 07, 2006

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
12/06/2006 - 12/07/2006

EVENT NUMBERS
4303743038

!!!!! THIS EVENT HAS BEEN RETRACTED !!!!!
!!!!! THIS EVENT HAS BEEN RETRACTED !!!!!
Hospital
Event Number: 43037
Rep Org: ST. JOHNS MERCY MEDICAL CENTER
Licensee: ST. JOHNS MERCY MEDICAL CENTER
Region: 3
City: ST. LOUIS   State: MO
County:
License #: 24-00794-03
Agreement: N
Docket:
NRC Notified By: ROBERT TURCO
HQ OPS Officer: BILL HUFFMAN
Notification Date: 12/07/2006
Notification Time: 11:25 [ET]
Event Date: 12/07/2006
Event Time: 07:30 [CST]
Last Update Date: 12/08/2006
Emergency Class: NON EMERGENCY
10 CFR Section:
20.1906(d)(1) - SURFACE CONTAM LEVELS > LIMITS
Person (Organization):
CHRISTINE LIPA (R3)
GREG MORELL (NMSS)
Event Text
EXTERNAL CONTAMINATION ON PACKAGE EXCEEDING SHIPPING LIMITS

The RSO for St. Johns Mercy Medical Center reported that a package was received at the facility with external and internal contamination. The package originated from a radiopharmaceutical company, GE- Healthcare, St. Louis and contained 400 microCi of I-123 and 5 milliCi of Tc-99. The package was surveyed upon receipt and found to have contamination levels of approximately 3100 dpm per square centimeter on both external and internal surfaces. This contamination is greater than the limits permitted in 49 CFR 173.443 and are therefore reportable. The contamination was analyzed in a multichannel analyzer and is believed to be Tc-99. The radiopharmaceuticals in the package were not damaged or leaking and the contamination does not appear to be from the contents of the shipment.

The GE-Healthcare, St. Louis facility was contacted and informed of the contamination. The driver and the vehicle used to transport the package have been surveyed and no contamination found. No other contamination has been found at the St. Johns Mercy Medical Center. The hospital plans to hold onto the shipping package until the Tc-99 decays before it is returned to GE- St. Louis.

* * * RETRACTION FROM TURCO TO HUFFMAN AT 1045 EST ON 12/08/06 * * *

Upon further investigation, the RSO for St. Johns has determined that the package was likely contaminated by the technician that performed the receipt inspection at the St. Johns Mercy Medical Center. The gloves of the technician performing the initial survey swipes were apparently contaminated by activities at the facility prior to receiving the package. Therefore, the licensee is retracting this event. NRC Region III (Piskura) was notified by the licensee.

R3DO (Lipa) and NMSS EO (Morell) have been notified.


!!!!! THIS EVENT HAS BEEN RETRACTED !!!!!
!!!!! THIS EVENT HAS BEEN RETRACTED !!!!!
Power Reactor
Event Number: 43038
Facility: SALEM
Region: 1     State: NJ
Unit: [] [2] []
RX Type: [1] W-4-LP,[2] W-4-LP
NRC Notified By: KENNETH FABER
HQ OPS Officer: JASON KOZAL
Notification Date: 12/07/2006
Notification Time: 21:51 [ET]
Event Date: 12/07/2006
Event Time: 17:28 [EST]
Last Update Date: 02/05/2007
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(v)(A) - POT UNABLE TO SAFE SD 50.72(b)(3)(v)(D) - ACCIDENT MITIGATION
Person (Organization):
MARVIN SYKES (R1)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 N Y 100 Power Operation 100 Power Operation
Event Text
LOSS OF SAFE SHUTDOWN CAPABILITY

"The Unit 2 Spray Additive System was isolated due to an identified crack on a weld at a 'tee' section of pipe upstream of a sample point. The crack was identified during a system release for an unrelated maintenance activity. Isolation of the crack for repairs requires isolation of the Containment Spray Additive system from both Containment Spray headers. This isolation was also completed to comply with ASME (Technical Specification Action Statement) 3.4.11.1. Therefore the Containment Spray Additive system is unable to perform its safety function. Salem Unit 2 remains in TS A/S 3.6.2.2 until repairs are complete."

TS A/S 3.6.2.2 is a 72 hour LCO (entered at 0503 on 12/07/06) and requires the plant to be in hot standby within 6 hours of the expiration of the LCO.

The licensee will inform the Lower Alloways Creek Township and has informed the NRC Resident Inspector.

* * * RETRACTION FROM ABBOTT TO HUFFMAN AT 2146 EST ON 2/05/07 * * *

"On December 7, 2006, PSEG made a non-emergency report in accordance with the 10 CFR 50.72(b)(3)(v)(A) and 10 CFR 50.72(b)(3)(v)(D) (event report 43038) regarding the Salem Unit 2 Spray Additive System.

"Upon further investigation, PSEG determined that the identified crack on a weld which resulted in a one drop per minute leak would not have caused a loss of system function. Therefore, based upon the guidance provided in NUREG 1022 that there is reasonable assurance that the weld would have remained intact and would have satisfactorily performed its intended function in the event of a CS system actuation (i.e., there was no loss of system safety function) this event report is being retracted.

"The NRC Resident Inspector was notified of this retraction."

R1DO (Cook) notified.