Event Notification Report for December 01, 2006
U.S. Nuclear Regulatory Commission
Operations Center
EVENT REPORTS FOR
11/30/2006 - 12/01/2006
EVENT NUMBERS
430174301843019430204309143061
Power Reactor
Event Number: 43017
Facility: CALLAWAY
Region: 4 State: MO
Unit: [1] [] []
RX Type: [1] W-4-LP
NRC Notified By: GREG BRADLEY
HQ OPS Officer: JOHN MacKINNON
Region: 4 State: MO
Unit: [1] [] []
RX Type: [1] W-4-LP
NRC Notified By: GREG BRADLEY
HQ OPS Officer: JOHN MacKINNON
Notification Date: 12/01/2006
Notification Time: 10:03 [ET]
Event Date: 12/01/2006
Event Time: 06:30 [CST]
Last Update Date: 12/01/2006
Notification Time: 10:03 [ET]
Event Date: 12/01/2006
Event Time: 06:30 [CST]
Last Update Date: 12/01/2006
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(xiii) - LOSS COMM/ASMT/RESPONSE
10 CFR Section:
50.72(b)(3)(xiii) - LOSS COMM/ASMT/RESPONSE
Person (Organization):
RUSSELL BYWATER (R4)
RUSSELL BYWATER (R4)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 1 | N | Y | 100 | Power Operation | 100 | Power Operation |
LOSS OF PLANT ACCESS
"At 0630 on 12-1-06, due to worsening road conditions from heavy snowfall, a determination was made that there is a loss of plant access for some individuals and some impairment of evacuation routes. This meets criteria for an Immediate Notification (8 Hour) per 10 CFR 50.72 (b)(3)(xiii). There is no impact on plant operation. The weather is improving, road crews are working and access concerns should be alleviated during the day today."
The NRC Resident Inspector was notified of this event by the licensee.
"At 0630 on 12-1-06, due to worsening road conditions from heavy snowfall, a determination was made that there is a loss of plant access for some individuals and some impairment of evacuation routes. This meets criteria for an Immediate Notification (8 Hour) per 10 CFR 50.72 (b)(3)(xiii). There is no impact on plant operation. The weather is improving, road crews are working and access concerns should be alleviated during the day today."
The NRC Resident Inspector was notified of this event by the licensee.
Power Reactor
Event Number: 43018
Facility: CLINTON
Region: 3 State: IL
Unit: [1] [] []
RX Type: [1] GE-6
NRC Notified By: BOB CARTER
HQ OPS Officer: JOHN MacKINNON
Region: 3 State: IL
Unit: [1] [] []
RX Type: [1] GE-6
NRC Notified By: BOB CARTER
HQ OPS Officer: JOHN MacKINNON
Notification Date: 12/01/2006
Notification Time: 10:12 [ET]
Event Date: 12/01/2006
Event Time: 06:30 [CST]
Last Update Date: 12/07/2006
Notification Time: 10:12 [ET]
Event Date: 12/01/2006
Event Time: 06:30 [CST]
Last Update Date: 12/07/2006
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(xiii) - LOSS COMM/ASMT/RESPONSE
10 CFR Section:
50.72(b)(3)(xiii) - LOSS COMM/ASMT/RESPONSE
Person (Organization):
LAURA KOZAK (R3)
LAURA KOZAK (R3)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 1 | N | Y | 96 | Power Operation | 55 | Power Operation |
LOSS OF EMERGENCY SIRENS
"At approximately 06:30 hours CST on December 1, 2006, it was discovered that greater than 25% of the Clinton Power Station (CPS) offsite sirens were out of service. 31 of 44 sirens are not available due to inclement weather.
"The licensee has notified DeWitt County Sheriff, Illinois Emergency Management Agency and the NRC Resident Inspector."
** UPDATE FROM JEANS TO KNOKE AT 17:00 EST ON 12/07/06 **
"As of December 7, 2006, there are less than 25% of the offsite sirens out of service (6 total). Repairs are continuing to restore power to the remaining sirens.
"The DeWitt County Sheriff, Illinois Emergency Management Agency, and the NRC Resident have been informed of this updated information.
"A press release is planned when all of the sirens have been restored."
Notified R3DO (Lipa).
"At approximately 06:30 hours CST on December 1, 2006, it was discovered that greater than 25% of the Clinton Power Station (CPS) offsite sirens were out of service. 31 of 44 sirens are not available due to inclement weather.
"The licensee has notified DeWitt County Sheriff, Illinois Emergency Management Agency and the NRC Resident Inspector."
** UPDATE FROM JEANS TO KNOKE AT 17:00 EST ON 12/07/06 **
"As of December 7, 2006, there are less than 25% of the offsite sirens out of service (6 total). Repairs are continuing to restore power to the remaining sirens.
"The DeWitt County Sheriff, Illinois Emergency Management Agency, and the NRC Resident have been informed of this updated information.
"A press release is planned when all of the sirens have been restored."
Notified R3DO (Lipa).
General Information or Other
Event Number: 43019
Rep Org: KANSAS DEPT OF HEALTH & ENVIRONMENT
Licensee: BOEING COMMERCIAL AIRPLANE GROUP
Region: 4
City: WITCHITA State: KS
County:
License #: 29-C064-01
Agreement: Y
Docket:
NRC Notified By: TOM CONLEY
HQ OPS Officer: JASON KOZAL
Licensee: BOEING COMMERCIAL AIRPLANE GROUP
Region: 4
City: WITCHITA State: KS
County:
License #: 29-C064-01
Agreement: Y
Docket:
NRC Notified By: TOM CONLEY
HQ OPS Officer: JASON KOZAL
Notification Date: 12/01/2006
Notification Time: 16:55 [ET]
Event Date: 12/01/2006
Event Time: 00:00 [CST]
Last Update Date: 12/01/2006
Notification Time: 16:55 [ET]
Event Date: 12/01/2006
Event Time: 00:00 [CST]
Last Update Date: 12/01/2006
Emergency Class: NON EMERGENCY
10 CFR Section:
10 CFR Section:
Person (Organization):
RUSSELL BYWATER (R4)
SCOTT MOORE (NMSS)
RUSSELL BYWATER (R4)
SCOTT MOORE (NMSS)
AGREEMENT STATE REPORT - LOST SOURCE
"The licensee reported a lost static air gun containing 10 millicuries of Po-210. The source is approximately 1 year old and the licensee believes the source was disposed of while attached to an air hose which was thrown away."
The State is continuing its investigation into this event and will provide updated information when it is available.
THIS MATERIAL EVENT CONTAINS A "LESS THAN CAT 3" LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks.
"The licensee reported a lost static air gun containing 10 millicuries of Po-210. The source is approximately 1 year old and the licensee believes the source was disposed of while attached to an air hose which was thrown away."
The State is continuing its investigation into this event and will provide updated information when it is available.
THIS MATERIAL EVENT CONTAINS A "LESS THAN CAT 3" LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks.
Power Reactor
Event Number: 43020
Facility: LASALLE
Region: 3 State: IL
Unit: [1] [2] []
RX Type: [1] GE-5,[2] GE-5
NRC Notified By: ROCKY HASTY
HQ OPS Officer: MARK ABRAMOVITZ
Region: 3 State: IL
Unit: [1] [2] []
RX Type: [1] GE-5,[2] GE-5
NRC Notified By: ROCKY HASTY
HQ OPS Officer: MARK ABRAMOVITZ
Notification Date: 12/01/2006
Notification Time: 17:06 [ET]
Event Date: 12/01/2006
Event Time: 11:42 [CST]
Last Update Date: 12/01/2006
Notification Time: 17:06 [ET]
Event Date: 12/01/2006
Event Time: 11:42 [CST]
Last Update Date: 12/01/2006
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(xiii) - LOSS COMM/ASMT/RESPONSE
10 CFR Section:
50.72(b)(3)(xiii) - LOSS COMM/ASMT/RESPONSE
Person (Organization):
LAURA KOZAK (R3)
LAURA KOZAK (R3)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 1 | N | Y | 100 | Power Operation | 100 | Power Operation |
| 2 | N | Y | 100 | Power Operation | 100 | Power Operation |
LOSS OF THIRTEEN EMERGENCY SIRENS
"A loss of power has disabled thirteen of the fifty EP sirens (26%). The sirens were lost at 11:42 CST and have not been restored.
"This meets the threshold of reportability based on the loss of a public notification system.
"Restoration of power is being scheduled to occur as soon as reasonably possible with the current winter weather conditions.
"Both units remain at full power and are unaffected by the loss of power."
The sirens do not have a battery backup.
The licensee notified the NRC Resident Inspector.
"A loss of power has disabled thirteen of the fifty EP sirens (26%). The sirens were lost at 11:42 CST and have not been restored.
"This meets the threshold of reportability based on the loss of a public notification system.
"Restoration of power is being scheduled to occur as soon as reasonably possible with the current winter weather conditions.
"Both units remain at full power and are unaffected by the loss of power."
The sirens do not have a battery backup.
The licensee notified the NRC Resident Inspector.
General Information or Other
Event Number: 43091
Rep Org: OHIO BUREAU OF RADIATION PROTECTION
Licensee: CLINTON MEMORIAL HOSPITAL
Region: 3
City: CLINTON State: OH
County:
License #: OH02300140000
Agreement: Y
Docket:
NRC Notified By: MARK LIGHT
HQ OPS Officer: JOHN KNOKE
Licensee: CLINTON MEMORIAL HOSPITAL
Region: 3
City: CLINTON State: OH
County:
License #: OH02300140000
Agreement: Y
Docket:
NRC Notified By: MARK LIGHT
HQ OPS Officer: JOHN KNOKE
Notification Date: 01/11/2007
Notification Time: 13:09 [ET]
Event Date: 12/01/2006
Event Time: 00:00 [EST]
Last Update Date: 01/11/2007
Notification Time: 13:09 [ET]
Event Date: 12/01/2006
Event Time: 00:00 [EST]
Last Update Date: 01/11/2007
Emergency Class: NON EMERGENCY
10 CFR Section:
10 CFR Section:
Person (Organization):
THOMAS KOZAK (R3)
JANET SCHLUETER (NMSS)
THOMAS KOZAK (R3)
JANET SCHLUETER (NMSS)
AGREEMENT STATE - OHIO - EQUIPMENT MALFUNCTION OF A COBALT TELETHERAPY DEVICE
On January 2, 2007, Ohio Bureau of Radiation Protection received a written report that an equipment failure of a Cobalt Teletherapy Device had occurred on December 1st while treating a patient. The sealed source did not return to the closed positron after completing treatment. The therapists immediately entered the room and returned the source to a safe configuration. The department requested additional information from the licensee on January 2 and received the additional information on January 9, 2007. It has been determined that the licensee did not perform a 24 hour notification as required in rule 3701-40-20 of the Administrative Code. The patient was exposed to less that thirty seconds exposure time and a determination was made from the additional information provided that a medical event did not occur. The unit was repaired by Neutron Products on December 8, 2006. The problem identified was an old air cylinder and detent pin which was replaced returning the unit to normal operation. The Department notified the NRC Operations Center on January 11, 2007 after determination of reporting requirements.
Teletherapy unit is a Theratron-80, s/n 2640986, which is manufactured by Neutron Products. The Co-60 sealed source is 1690 Ci or 62530 GBq, model number NPTY, s/n T-1444.
On January 2, 2007, Ohio Bureau of Radiation Protection received a written report that an equipment failure of a Cobalt Teletherapy Device had occurred on December 1st while treating a patient. The sealed source did not return to the closed positron after completing treatment. The therapists immediately entered the room and returned the source to a safe configuration. The department requested additional information from the licensee on January 2 and received the additional information on January 9, 2007. It has been determined that the licensee did not perform a 24 hour notification as required in rule 3701-40-20 of the Administrative Code. The patient was exposed to less that thirty seconds exposure time and a determination was made from the additional information provided that a medical event did not occur. The unit was repaired by Neutron Products on December 8, 2006. The problem identified was an old air cylinder and detent pin which was replaced returning the unit to normal operation. The Department notified the NRC Operations Center on January 11, 2007 after determination of reporting requirements.
Teletherapy unit is a Theratron-80, s/n 2640986, which is manufactured by Neutron Products. The Co-60 sealed source is 1690 Ci or 62530 GBq, model number NPTY, s/n T-1444.
Other Nuclear Material
Event Number: 43061
Rep Org: NATIONAL INSTITUTE OF HEALTH
Licensee: NATIONAL INSTITUTE OF HEALTH
Region: 1
City: BETHESDA State: MD
County:
License #: 19-00296-10
Agreement: Y
Docket:
NRC Notified By: ROBERT ZOON
HQ OPS Officer: BILL HUFFMAN
Licensee: NATIONAL INSTITUTE OF HEALTH
Region: 1
City: BETHESDA State: MD
County:
License #: 19-00296-10
Agreement: Y
Docket:
NRC Notified By: ROBERT ZOON
HQ OPS Officer: BILL HUFFMAN
Notification Date: 12/22/2006
Notification Time: 13:32 [ET]
Event Date: 12/01/2006
Event Time: 00:00 [EST]
Last Update Date: 12/22/2006
Notification Time: 13:32 [ET]
Event Date: 12/01/2006
Event Time: 00:00 [EST]
Last Update Date: 12/22/2006
Emergency Class: NON EMERGENCY
10 CFR Section:
20.2201(a)(1)(ii) - LOST/STOLEN LNM>10X
10 CFR Section:
20.2201(a)(1)(ii) - LOST/STOLEN LNM>10X
Person (Organization):
RAY POWELL (R1)
ROBERT PIERSON (NMSS)
RAY POWELL (R1)
ROBERT PIERSON (NMSS)
LOST VIAL CONTAINING PHOSPHORUS-32
"This is a report of the loss of licensed material in accordance with 10CFR20.2201.
"1. The licensed material consisted of a single packaged vial of Alpha-Adenosine Triphosphate (a-ATP) which contained 250 microcuries (9.25 MBq) of Phosphorus-32 (Half-life=14.3 days). The product is supplied by GE Healthcare, product number PT10160. The volume of the product was 25 microliters.
"2. On December 1, 2006 a box containing three separate shielded vials of the product described in (1) above was delivered to a technician in the Clinical Research Center, 5th floor, Room 3288. Some time later, the Authorized User [AU] unpacked the box, but only retrieved two of the three product packages from the dry ice within the Styrofoam chest, because the third package was below the remaining dry ice. The AU then defaced the radioactive materials labels on the delivery box and placed the box containing the remaining vial for pickup as regular trash. The AU did not discover the error until December 4, 2006, too late to attempt retrieval from the regular trash dumpster.
"3. The disposition of the material is to the regular trash stream through the Montgomery Country, MD refuse transfer station in Rockville, MD.
"4. We have no reason to believe that this loss of licensed material resulted in exposure to anyone. The P-32 labeled ATP is in a very small volume of liquid, shielded by a sturdy Lucite plastic vial shield, encased in a sealed vinyl plastic outer containment. Furthermore, that assembly was in a thick-walled Styrofoam box within the cardboard delivery box. It is highly unlikely that, during the process of transport to, and through the transfer station that the P-32 would have leaked out of containment.
"5. No action was taken to recover the material due the circumstances of loss and the time between loss and discovery of the loss.
"6. No procedures have been modified as a result of this incident. The package insert clearly delineated to the AU that there were 750 microcuries of Alpha-ATP-32 in the shipment, in accordance with what the AU ordered, indicating that three items should have been retrieved from the dry ice. The loss was the result of human error."
THIS MATERIAL EVENT CONTAINS A "LESS THAN CAT 3" LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks.
"This is a report of the loss of licensed material in accordance with 10CFR20.2201.
"1. The licensed material consisted of a single packaged vial of Alpha-Adenosine Triphosphate (a-ATP) which contained 250 microcuries (9.25 MBq) of Phosphorus-32 (Half-life=14.3 days). The product is supplied by GE Healthcare, product number PT10160. The volume of the product was 25 microliters.
"2. On December 1, 2006 a box containing three separate shielded vials of the product described in (1) above was delivered to a technician in the Clinical Research Center, 5th floor, Room 3288. Some time later, the Authorized User [AU] unpacked the box, but only retrieved two of the three product packages from the dry ice within the Styrofoam chest, because the third package was below the remaining dry ice. The AU then defaced the radioactive materials labels on the delivery box and placed the box containing the remaining vial for pickup as regular trash. The AU did not discover the error until December 4, 2006, too late to attempt retrieval from the regular trash dumpster.
"3. The disposition of the material is to the regular trash stream through the Montgomery Country, MD refuse transfer station in Rockville, MD.
"4. We have no reason to believe that this loss of licensed material resulted in exposure to anyone. The P-32 labeled ATP is in a very small volume of liquid, shielded by a sturdy Lucite plastic vial shield, encased in a sealed vinyl plastic outer containment. Furthermore, that assembly was in a thick-walled Styrofoam box within the cardboard delivery box. It is highly unlikely that, during the process of transport to, and through the transfer station that the P-32 would have leaked out of containment.
"5. No action was taken to recover the material due the circumstances of loss and the time between loss and discovery of the loss.
"6. No procedures have been modified as a result of this incident. The package insert clearly delineated to the AU that there were 750 microcuries of Alpha-ATP-32 in the shipment, in accordance with what the AU ordered, indicating that three items should have been retrieved from the dry ice. The loss was the result of human error."
THIS MATERIAL EVENT CONTAINS A "LESS THAN CAT 3" LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks.