Event Notification Report for October 29, 2006
U.S. Nuclear Regulatory Commission
Operations Center
EVENT REPORTS FOR
10/28/2006 - 10/29/2006
Power Reactor
Event Number: 42944
Facility: VERMONT YANKEE
Region: 1 State: VT
Unit: [1] [] []
RX Type: [1] GE-4
NRC Notified By: KEVIN MURPHY
HQ OPS Officer: BILL GOTT
Region: 1 State: VT
Unit: [1] [] []
RX Type: [1] GE-4
NRC Notified By: KEVIN MURPHY
HQ OPS Officer: BILL GOTT
Notification Date: 10/29/2006
Notification Time: 13:38 [ET]
Event Date: 10/29/2006
Event Time: 13:02 [EDT]
Last Update Date: 10/29/2006
Notification Time: 13:38 [ET]
Event Date: 10/29/2006
Event Time: 13:02 [EDT]
Last Update Date: 10/29/2006
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(xiii) - LOSS COMM/ASMT/RESPONSE
10 CFR Section:
50.72(b)(3)(xiii) - LOSS COMM/ASMT/RESPONSE
Person (Organization):
JAMES NOGGLE (R1)
JAMES NOGGLE (R1)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 1 | N | Y | 100 | Power Operation | 100 | Power Operation |
LOSS OF NOAA TRANSMITTER
The facility lost the Ames Hill NOAA transmitter due to weather conditions. Compensatory measures are in place and the vendor has been notified and is enroute to shift the power supply to back up.
The licensee notified the NRC Resident Inspector.
* * * UPDATE FROM K. MURPHY TO W. GOTT AT 1522 ON 10/29/06 * * *
The Ames Hill NOAA transmitter was restored at 1505.
The licensee will notify the NRC Resident Inspector. Notified R1DO (J. Noggle)
The facility lost the Ames Hill NOAA transmitter due to weather conditions. Compensatory measures are in place and the vendor has been notified and is enroute to shift the power supply to back up.
The licensee notified the NRC Resident Inspector.
* * * UPDATE FROM K. MURPHY TO W. GOTT AT 1522 ON 10/29/06 * * *
The Ames Hill NOAA transmitter was restored at 1505.
The licensee will notify the NRC Resident Inspector. Notified R1DO (J. Noggle)
Power Reactor
Event Number: 42945
Facility: COMANCHE PEAK
Region: 4 State: TX
Unit: [] [2] []
RX Type: [1] W-4-LP,[2] W-4-LP
NRC Notified By: EUGENE SKELTON
HQ OPS Officer: BILL GOTT
Region: 4 State: TX
Unit: [] [2] []
RX Type: [1] W-4-LP,[2] W-4-LP
NRC Notified By: EUGENE SKELTON
HQ OPS Officer: BILL GOTT
Notification Date: 10/29/2006
Notification Time: 18:02 [ET]
Event Date: 10/29/2006
Event Time: 15:20 [CST]
Last Update Date: 10/29/2006
Notification Time: 18:02 [ET]
Event Date: 10/29/2006
Event Time: 15:20 [CST]
Last Update Date: 10/29/2006
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(iv)(B) - RPS ACTUATION - CRITICAL 50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION
10 CFR Section:
50.72(b)(2)(iv)(B) - RPS ACTUATION - CRITICAL 50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION
Person (Organization):
JEFFREY CLARK (R4)
JEFFREY CLARK (R4)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 2 | M/R | Y | 80 | Power Operation | 0 | Hot Standby |
MANUAL TRIP DUE TO LOWERING STEAM GENERATOR LEVEL
"Unit 2 was operating in Mode 1 at 80% power following refueling holding for stabilization xenon in preparation for incore - excore calibration. An alarm condition for steam generator 2-03 indicating Steam - Feedwater flow mismatch was observed. Manual control of the feed regulating valve was taken, but operators were unable to control feed flow while steam generator 2-03 level continued to decrease. A manual reactor trip was initiated and the reactor was tripped. Auxiliary feedwater automatically started on low-low level in steam generators. All systems responded normally during and following the trip. Unit 2 is being maintained in Mode 3 pending the event investigation."
All control rods fully inserted. RCPs are in operation transferring decay heat to the steam generators. The MSIV's are open with the steam generators discharging steam to the main condensers using the steam dumps. AFW is maintaining steam generator water levels. Unit 1 was not affected.
The licensee notified the NRC Resident Inspector.
"Unit 2 was operating in Mode 1 at 80% power following refueling holding for stabilization xenon in preparation for incore - excore calibration. An alarm condition for steam generator 2-03 indicating Steam - Feedwater flow mismatch was observed. Manual control of the feed regulating valve was taken, but operators were unable to control feed flow while steam generator 2-03 level continued to decrease. A manual reactor trip was initiated and the reactor was tripped. Auxiliary feedwater automatically started on low-low level in steam generators. All systems responded normally during and following the trip. Unit 2 is being maintained in Mode 3 pending the event investigation."
All control rods fully inserted. RCPs are in operation transferring decay heat to the steam generators. The MSIV's are open with the steam generators discharging steam to the main condensers using the steam dumps. AFW is maintaining steam generator water levels. Unit 1 was not affected.
The licensee notified the NRC Resident Inspector.
Power Reactor
Event Number: 42946
Facility: SALEM
Region: 1 State: NJ
Unit: [] [2] []
RX Type: [1] W-4-LP,[2] W-4-LP
NRC Notified By: MARK FIOCCO
HQ OPS Officer: MARK ABRAMOVITZ
Region: 1 State: NJ
Unit: [] [2] []
RX Type: [1] W-4-LP,[2] W-4-LP
NRC Notified By: MARK FIOCCO
HQ OPS Officer: MARK ABRAMOVITZ
Notification Date: 10/30/2006
Notification Time: 01:10 [ET]
Event Date: 10/29/2006
Event Time: 20:11 [EST]
Last Update Date: 10/31/2006
Notification Time: 01:10 [ET]
Event Date: 10/29/2006
Event Time: 20:11 [EST]
Last Update Date: 10/31/2006
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION
10 CFR Section:
50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION
Person (Organization):
JAMES NOGGLE (R1)
JAMES NOGGLE (R1)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 2 | N | N | 0 | Hot Shutdown | 0 | Hot Shutdown |
AUTOMATIC START OF AUXILIARY FEEDWATER DURING MSIV TESTING
"This is an 8 hour notification being made to report that a valid ESF auxiliary feed actuation occurred. Salem Unit 2 is in Mode 4 with RHR providing shutdown cooling. 21, 22, and 23 reactor coolant pumps are in service providing forced circulation.
"While performing a main steam isolation valve stroke test for maintenance concurrent with main turbine valve surveillance testing, 22 steam generator narrow range level indication shrunk to 7%, which is below the low level trip setpoint of 14%, causing an automatic start of 21 and 22 auxiliary feedwater pumps. There was no other testing or evolutions in progress at the time of the event that contributed to the automatic start of the auxiliary feedwater pumps.
"Steam generator parameters at the time of the event where 0 psig and 223 degrees (T-cold). Main condenser vacuum was established.
"23 auxiliary feedwater pump was tagged for maintenance and did not start.
"22 steam generator level was restored to normal level and the 21 and 22 auxiliary feedwater pumps secured.
"There were no personnel injured."
During this event, the main turbine governor valves were off their closed seats when the MSIVs were stroked.
The licensee notified the NRC Resident Inspector.
* * * UPDATE PROVIDED BY STRAUBMULLER TO KOZAL ON 10/31/2006 AT 0146 * * *
"Subsequent to the initial notification, it has been determined that in addition to reporting the auxiliary feedwater pumps starting on low steam generator level, it is required to report that the reactor protection system opened the reactor trip breakers as designed. The reactor trip breakers were closed for surveillance testing of the main turbine. Actuation of the reactor trip breakers is reportable under [10 CFR] 50.72 (b)(3)(iv)(A) for this event."
The licensee notified the NRC Resident Inspector.
Informed R2DO (GRAY)
"This is an 8 hour notification being made to report that a valid ESF auxiliary feed actuation occurred. Salem Unit 2 is in Mode 4 with RHR providing shutdown cooling. 21, 22, and 23 reactor coolant pumps are in service providing forced circulation.
"While performing a main steam isolation valve stroke test for maintenance concurrent with main turbine valve surveillance testing, 22 steam generator narrow range level indication shrunk to 7%, which is below the low level trip setpoint of 14%, causing an automatic start of 21 and 22 auxiliary feedwater pumps. There was no other testing or evolutions in progress at the time of the event that contributed to the automatic start of the auxiliary feedwater pumps.
"Steam generator parameters at the time of the event where 0 psig and 223 degrees (T-cold). Main condenser vacuum was established.
"23 auxiliary feedwater pump was tagged for maintenance and did not start.
"22 steam generator level was restored to normal level and the 21 and 22 auxiliary feedwater pumps secured.
"There were no personnel injured."
During this event, the main turbine governor valves were off their closed seats when the MSIVs were stroked.
The licensee notified the NRC Resident Inspector.
* * * UPDATE PROVIDED BY STRAUBMULLER TO KOZAL ON 10/31/2006 AT 0146 * * *
"Subsequent to the initial notification, it has been determined that in addition to reporting the auxiliary feedwater pumps starting on low steam generator level, it is required to report that the reactor protection system opened the reactor trip breakers as designed. The reactor trip breakers were closed for surveillance testing of the main turbine. Actuation of the reactor trip breakers is reportable under [10 CFR] 50.72 (b)(3)(iv)(A) for this event."
The licensee notified the NRC Resident Inspector.
Informed R2DO (GRAY)