Event Notification Report for April 08, 2006

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
04/07/2006 - 04/08/2006

EVENT NUMBERS
42484

Power Reactor
Event Number: 42484
Facility: CALVERT CLIFFS
Region: 1     State: MD
Unit: [1] [] []
RX Type: [1] CE,[2] CE
NRC Notified By: TIM RITI
HQ OPS Officer: PETE SNYDER
Notification Date: 04/09/2006
Notification Time: 02:37 [ET]
Event Date: 04/08/2006
Event Time: 23:42 [EDT]
Last Update Date: 04/09/2006
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(i) - PLANT S/D REQD BY TS
Person (Organization):
PAT FINNEY (R1)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 M/R Y 1 Startup 0 Hot Standby
Event Text
CONTROL ELEMENT ASSEMBLY STUCK DURING PHYSICS TESTING

"During the performance of PSTP-2, Low Power Physics Testing on U-1 for Regulating Control Element Assemblies Group 2, CEA #21 was declared untrippable, Technical Specification 3.1.4.F, CEA Alignment, was entered and Plant shutdown to Mode 3 was commenced at 2342 on 4/8/06."

The reactor is shutdown in Mode 3. The licensee borated to maintain adequate shutdown margin. The reactor trip breakers were opened but CEA #21 remains not fully inserted into the core. The licensee is currently troubleshooting to determine the cause of the stuck CEA. Offsite power is stable and powers the safety buses. Emergency Diesel Generators are available. The licensee is currently at normal operating pressure and temperature with decay heat being removed by the steam generators steaming to the condenser.

The licensee notified the NRC Resident Inspector.