Skip to main content

Event Notification Report for December 26, 2004

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
12/25/2004 - 12/26/2004

EVENT NUMBERS
4129441295

Power Reactor
Event Number: 41294
Facility: FERMI
Region: 3     State: MI
Unit: [2] [] []
RX Type: [2] GE-4
NRC Notified By: PATRICK FALLON
HQ OPS Officer: JOHN KNOKE
Notification Date: 12/26/2004
Notification Time: 09:32 [ET]
Event Date: 12/26/2004
Event Time: 09:18 [EST]
Last Update Date: 12/26/2004
Emergency Class: UNUSUAL EVENT
10 CFR Section:
50.72(a) (1) (i) - EMERGENCY DECLARED
Person (Organization):
LAURA KOZAK (R3)
MICHAEL JOHNSON (NRR)
PETER WILSON (IRD)
JEFF GRANT (R3)
DAN SULLIVAN (FEMA)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 N Y 100 Power Operation 100 Power Operation
Event Text
UNUSUAL EVENT DECLARED DUE TO LOSS OF CONTROL ROOM SAFETY SYSTEM ANNUNICATOR PANELS A&B

Fermi Unit 2 declared an Unusual Event at 09:18 EST when the computer software to all Safety System annunciators in the Control Room failed. The reactor was operating at 100% power in Mode 1. Control Room Operators monitored plant conditions by looking at applicable hardware gauges in the Control Room. No transient conditions within the plant occurred during this event. Licensee is investigating whether the periodic testing of the "Auto Start" on the DC Main Turbine LO Pump caused the software to malfunction. Course of action by Licensee to restore the annunciator system was to reboot the computers.

Licensee notified state and local agencies and NRC Resident Inspector.

*** UPDATE ON 12/26/04 AT 10:35 EST FROM P.FALLON TO J.KNOKE

"Reactor is stable at 100% power, safety related annunciators are operating normally on both normal and backup computers. A corrective action document is being submitted to investigate a connection between the DC Main Turbine LO Pump switch and the loss of annunciators."

At 10:29 EST the licensee terminated the Unusual Event with both normal and backup computers for the safety related annunciators operating normally.

Licensee informed the state/ local agencies and the NRC Resident Inspector. Notified R3DO (Kozak), NRR (Johnson), IRD (Wilson), FEMA (Sullivan), and DHS (Gomez).


Power Reactor
Event Number: 41295
Facility: ROBINSON
Region: 2     State: SC
Unit: [2] [] []
RX Type: [2] W-3-LP
NRC Notified By: HENRY CURRY
HQ OPS Officer: JANELLE BATTISTE
Notification Date: 12/26/2004
Notification Time: 12:48 [ET]
Event Date: 12/26/2004
Event Time: 09:04 [EST]
Last Update Date: 12/26/2004
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(xiii) - LOSS COMM/ASMT/RESPONSE
Person (Organization):
CAUDLE JULIAN (R2)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 N Y 100 Power Operation 100 Power Operation
Event Text
LOSS OF COMMUNICATIONS/RESPONSE CAPABILITY

"At 0804 hours EST, on December 26, 2004, at the H. B. Robinson Steam Electric Plant (HBRSEP), Unit No. 2, a partial loss of non-vital offsite power occurred causing the inoperability of the Emergency Response Facility Information (ERFIS) computer system for greater than one hour. The ERFIS computer system provides monitoring and communications capability for plant data systems including the Emergency Response Data System (ERDS), among others. At 0852, the remaining non-vital offsite power was lost resulting in the disabling of the primary Emergency Operating Facility (EOF). The off-site alternate EOF remained operational. Power to the primary EOF was restored at 0913 and the ERFIS computer system was restored to operable status at 1010 hours on December 26, 2004.

"As required by plant procedures, appropriate assessment of plant conditions, notifications, and communications could still have been made through alternate methods during the time that the ERFIS computer system was inoperable. This report is being made in accordance with 10 CFR 50.72(b)(3)(xiii), which is any event that results in a major loss of emergency assessment capability, offsite response capability, or offsite communications capability. As previously stated, alternate means remained available to assess plant conditions, make notifications, and accomplish required communications, as necessary."

The licensee notified the NRC Resident Inspector.