Skip to main content

Event Notification Report for December 04, 2004

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
12/03/2004 - 12/04/2004

EVENT NUMBERS
4124341244

Power Reactor
Event Number: 41243
Facility: FERMI
Region: 3     State: MI
Unit: [2] [] []
RX Type: [2] GE-4
NRC Notified By: P. FALLON
HQ OPS Officer: ARLON COSTA
Notification Date: 12/04/2004
Notification Time: 05:07 [ET]
Event Date: 12/04/2004
Event Time: 04:17 [EST]
Last Update Date: 12/04/2004
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(iv)(B) - RPS ACTUATION - CRITICAL
Person (Organization):
KENNETH O'BRIEN (R3)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 A/R Y 56 Power Operation 0 Hot Shutdown
Event Text
AUTOMATIC REACTOR SCRAM DUE TO AN AUTO VOLTAGE REGULATOR TRIP

"On December 4, 2004 at 0417 [EST], the Reactor Scrammed as the result of an AVR [Automatic Voltage Regulator] trip. AVR Channels A and B were both operating at the time. The AVR trip caused a Main Generator trip which caused a Main Turbine trip. The Main Turbine trip causes a direct Reactor SCRAM on Turbine Valve position. RPS functioned properly and all rods inserted [fully]. MSIVs remain open with Reactor Level being maintained in the normal band of 173 to 214 inches. Reactor Pressure is being maintained with the Main Turbine Bypass valves. Isolations expected for Reactor Level 3 occurred and have been reset."

Previous to the reactor scram, the AVR alarm was being monitored. All other safety systems functioned as required. Similar event occurred 09/04/04 (EN#41017).

The licensee notified the NRC Resident Inspector.


Fuel Cycle Facility
Event Number: 41244
Facility: PADUCAH GASEOUS DIFFUSION PLANT
Region: 2     State: KY
Unit: [] [] []
RX Type: URANIUM ENRICHMENT FACILITY
Comments: 2 DEMOCRACY CENTER
6903 ROCKLEDGE DRIVE
BETHESDA, MD 20817 (301)564-3200
NRC Notified By: ERIC WALKER
HQ OPS Officer: JOHN MacKINNON
Notification Date: 12/05/2004
Notification Time: 07:42 [ET]
Event Date: 12/04/2004
Event Time: 06:50 [CST]
Last Update Date: 12/05/2004
Emergency Class: NON EMERGENCY
10 CFR Section:
76.120(c)(2) - SAFETY EQUIPMENT FAILURE
Person (Organization):
PAUL FREDRICKSON (R2)
GARY JANOSKO (NMSS)
Event Text
HIGH PRESSURE TRANSMITTER FAILURE

"At 0650 on 12-04-04, the Plant Shift Superintendent (PSS) was notified of a failure of the C-333A Autoclave 1 North High Cylinder Pressure System (HCPS). During a normal cylinder heating cycle an operator noted that the cylinder pressure, read on a recorder in the Operations Monitoring Room (OMR), unexpectedly fell from 70 to 0 psia. The PSS declared the system inoperable and TSR LCO 2.2.4.14B actions were implemented to place the autoclave in Mode 2 (autoclave open, non-applicable mode). The High Cylinder Pressure System (TRS 2.2.4.14) is designed to minimize the potential of a primary system failure (cylinder rupture) during a pressure increase event by automatically isolating the steam supply to the autoclave prior to reaching the Maximum Allowable Working Pressure (MAWP) of the cylinder. The event is reportable as a 24 hour event, as required by 10 CFR 76.120(c)(2)(1); An event in which equipment is disabled or fails to function as designed when the equipment is required by a TSR to prevent releases, prevent exposures to radiation and radioactive materials exceeding specific limits, mitigate the consequences of an accident, or restore this facility to a preestablished safe condition after an accident. The equipment was required by TSR to be available and operable and no redundant equipment was available to perform the required safety function.

"The NRC Resident Inspector has been notified of this event."

PGDP Problem Report No. ATR-04-4819, PGDP Event Report No. PAD-2004-28.