Event Notification Report for October 03, 2004
U.S. Nuclear Regulatory Commission
Operations Center
EVENT REPORTS FOR
10/02/2004 - 10/03/2004
EVENT NUMBERS
41086
Power Reactor
Event Number: 41086
Facility: HATCH
Region: 2 State: GA
Unit: [] [2] []
RX Type: [1] GE-4,[2] GE-4
NRC Notified By: BARRY D. COLEMAN
HQ OPS Officer: JEFF ROTTON
Region: 2 State: GA
Unit: [] [2] []
RX Type: [1] GE-4,[2] GE-4
NRC Notified By: BARRY D. COLEMAN
HQ OPS Officer: JEFF ROTTON
Notification Date: 10/03/2004
Notification Time: 10:46 [ET]
Event Date: 10/03/2004
Event Time: 05:30 [EDT]
Last Update Date: 10/03/2004
Notification Time: 10:46 [ET]
Event Date: 10/03/2004
Event Time: 05:30 [EDT]
Last Update Date: 10/03/2004
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(v)(C) - POT UNCNTRL RAD REL
10 CFR Section:
50.72(b)(3)(v)(C) - POT UNCNTRL RAD REL
Person (Organization):
ROBERT HAAG (R2)
ROBERT HAAG (R2)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 2 | N | Y | 20 | Power Operation | 20 | Power Operation |
PRIMARY CONTAINMENT PENETRATION ISOLATION VALVES INOPERABLE
"During a review of outage clearances, it was discovered that a Caution tag out for Service Air to the Drywell was active and the valves were open. This rendered the valves inoperable and Technical Specification 3.6.1.3 action B for one penetration with two inoperable PCIVs was entered. The action was to isolate the penetration by closing one valve within one hour. The event was discovered at 0530 and the outboard valve was closed at 0655 . Since the one hour time limit was exceeded, Technical Specification 3.6.1.3 action E (Mode 3 in 12 hours and Mode 4 in 36 hours) was entered at 0630 and exited at 0655. Technical Specification 3.6.1.3 action A, which is the Tech. Spec. for one inoperable isolation valve will remain in effect. The plant entered Mode 3 at 1530 on 10/01/04. Mode 3 requires primary containment and all PCIVs to be operable. This condition of non-compliance existed from 1530 on 10/01/04 until 0655 on 10/03/04.
The licensee notified the NRC Resident Inspector.
"During a review of outage clearances, it was discovered that a Caution tag out for Service Air to the Drywell was active and the valves were open. This rendered the valves inoperable and Technical Specification 3.6.1.3 action B for one penetration with two inoperable PCIVs was entered. The action was to isolate the penetration by closing one valve within one hour. The event was discovered at 0530 and the outboard valve was closed at 0655 . Since the one hour time limit was exceeded, Technical Specification 3.6.1.3 action E (Mode 3 in 12 hours and Mode 4 in 36 hours) was entered at 0630 and exited at 0655. Technical Specification 3.6.1.3 action A, which is the Tech. Spec. for one inoperable isolation valve will remain in effect. The plant entered Mode 3 at 1530 on 10/01/04. Mode 3 requires primary containment and all PCIVs to be operable. This condition of non-compliance existed from 1530 on 10/01/04 until 0655 on 10/03/04.
The licensee notified the NRC Resident Inspector.