Skip to main content

Event Notification Report for September 10, 2004

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
09/09/2004 - 09/10/2004

EVENT NUMBERS
4103641119

Other Nuclear Material
Event Number: 41036
Rep Org: TRANSNUCLEAR, INC
Licensee: TRANSNUCLEAR, INC.
Region: 1
City: NEW YORK   State: NY
County:
License #:
Agreement: Y
Docket:
NRC Notified By: JOHN MANGUSI
HQ OPS Officer: JOHN MacKINNON
Notification Date: 09/12/2004
Notification Time: 11:37 [ET]
Event Date: 09/10/2004
Event Time: 17:00 [EDT]
Last Update Date: 09/14/2004
Emergency Class: NON EMERGENCY
10 CFR Section:
Person (Organization):
HAROLD GRAY (R1)
LARRY CAMPER (NMSS)
GREG PICK (R4)
Event Text
MISPLACED IMPORT RADIOACTIVE SHIPMENT

On September 4, 2004 a radioactive shipment, under a General Licensee, was flown into JFK Airport via Air France Flight # 6492 (flight arrived at 2345 hours). The radioactive shipment, 6 pound Bio Pack package with White Label 1 with a Transportation Index (TI) number of 0 , went through customs. On September 10, 2004 Transnuclear, Inc sent a freight truck to pick up the shipment at Air France. Air France personnel were unable to locate the package and they said that they had misplaced the package. The BioPack contains 4 sample tubes of uranium hexafluoride. The four sample tubes are LEU. Total is 0.038 kg of uranium hexafluoride of which 0.025 kg is LEU uranium. Transnuclear, Inc is supposed to ship the BioPack to Framatome ANP located in Richland, WA.

* * * Update on 09/14/04 at 0926 EDT by John Mangusi taken by MacKinnon * * *

Transnuclear,Inc. was notified by email that the package had been located at the JFK Air France Terminal. Transnuclear, Inc. will arrange to pick up the package and eventually deliver it to Framatone ANP located in Richland, WA.

NRC (John Wray) was notified of this by John Mangusi. NRC R1DO (Larry Doerflein), NRC R4DO (Dale Powers) & NMSS EO (M. Burgess) notified.


Power Reactor
Event Number: 41119
Facility: BEAVER VALLEY
Region: 1     State: PA
Unit: [1] [] []
RX Type: [1] W-3-LP,[2] W-3-LP
NRC Notified By: RONALD TIMOTHY GREEN
HQ OPS Officer: JEFF ROTTON
Notification Date: 10/14/2004
Notification Time: 14:40 [ET]
Event Date: 09/10/2004
Event Time: 17:30 [EDT]
Last Update Date: 10/14/2004
Emergency Class: NON EMERGENCY
10 CFR Section:
50.73(a)(1) - INVALID SPECIF SYSTEM ACTUATION
Person (Organization):
BRIAN MCDERMOTT (R1)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
Event Text
INVALID ACTUATION OF STEAM DRIVEN AUXILIARY FEEDWATER PUMP

"On September 10, 2004 at 1730 hours, one steam supply isolation valve (TV-1MS-105B) to the steam-driven Auxiliary Feedwater System Pump (FW-P-2) unexpectedly opened at Beaver Valley Power Station Unit No. 1, causing this pump to commence feeding all three steam generators. FW-P-2 functioned as designed with steam being supplied to the pump's steam-drive turbine. Neither of the other two Auxiliary Feedwater System motor-driven pumps were actuated at Beaver Valley Power Station Unit No. 1. This initially caused Steam Generator Water Level Deviations alarms on all three steam generators. The steam generator levels returned to their normal operating levels via the automatic level control system. After determining that there was no demand for this Auxiliary Feedwater System pump to be operating, the control room crew attempted to close TV-1MS-105B from the control room, without success. The upstream motor-operated isolation valve (MOV-1MS-105) to TV-1MS-105B was then closed to stop steam flow to FW-P-2, terminating the auxiliary feedwater flow to the steam generators.

"No maintenance or tests were ongoing with the Auxiliary Feedwater System at the time. Subsequent investigation determined that this event occurred due to a failure of an instrument card within the Solid State Protection System which caused TV-1MS-105B to inappropriately open. Therefore this actuation was not initiated by a valid actuation signal.

"This event is reportable pursuant to 10 CFR 50.73(a)(2)(iv)(A) since it involved an actuation of a PWR auxiliary feedwater water system train as per 10 CFR 50.73(a)(2)(iv)(B)(6). This pump start was not part of a pre-planned sequence and did not occur with this system properly removed from service.

"However, pursuant to 10 CFR 50.73(a)(1), this event is being reported via this telephone notification instead of submitting a written Licensee Event Report since the automatic actuation of the Auxiliary Feedwater System pump was not generated by a valid actuation."

The licensee notified the NRC Resident Inspector.