Skip to main content

Event Notification Report for August 23, 2004

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
08/22/2004 - 08/23/2004

EVENT NUMBERS
4097740978

Power Reactor
Event Number: 40977
Facility: GINNA
Region: 1     State: NY
Unit: [1] [] []
RX Type: [1] W-2-LP
NRC Notified By: D. GOMEZ
HQ OPS Officer: JOHN MacKINNON
Notification Date: 08/23/2004
Notification Time: 17:20 [ET]
Event Date: 08/23/2004
Event Time: 13:22 [EDT]
Last Update Date: 08/23/2004
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(xiii) - LOSS COMM/ASMT/RESPONSE
Person (Organization):
EUGENE COBEY (R1)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
Event Text
EMERGENCY SIRENS DID NOT ACTIVATE

"At 1322 hours during routine testing it was discovered that Monroe County Emergency Sirens (24 of 96 total) did not activate from the Monroe County Emergency Command Center . The affected sirens were tested and restored to operable status from an alternate site at 1404 hours."

The NRC Resident Inspector was notified of this event by the licensee.


Fuel Cycle Facility
Event Number: 40978
Facility: HONEYWELL INTERNATIONAL, INC.
Region: 2     State: IL
Unit: [] [] []
RX Type: URANIUM HEXAFLUORIDE PRODUCTION
NRC Notified By: M. GINZEL
HQ OPS Officer: JOHN MacKINNON
Notification Date: 08/23/2004
Notification Time: 17:37 [ET]
Event Date: 08/23/2004
Event Time: 09:00 [CDT]
Last Update Date: 08/23/2004
Emergency Class: NON EMERGENCY
10 CFR Section:
40.60(b)(2) - SAFETY EQUIPMENT FAILURE
Person (Organization):
PAUL FREDRICKSON (R2)
GARY JANOSKO (NMSS)
Event Text
EMERGENCY DIESEL GENERATOR START FAILURE

The emergency diesel-driven backup power generator failed to automatically start during routine weekly testing. Production was shutdown in the Feeds Material Building while resolving the problem. The start failure was determined to be the result of a failed electronic card associated with the fuel supply solenoid valve. Because the solenoid can be over-ridden, the diesel generator remains capable of manual start.

The licensee notified NRC Region 2 (J. Hensen) and local NRC Inspector (B. Bartlett).