Event Notification Report for August 14, 2004

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
08/13/2004 - 08/14/2004

EVENT NUMBERS
4095240953409544095540956

!!!!! THIS EVENT HAS BEEN RETRACTED !!!!!
!!!!! THIS EVENT HAS BEEN RETRACTED !!!!!
Power Reactor
Event Number: 40952
Facility: GRAND GULF
Region: 4     State: MS
Unit: [1] [] []
RX Type: [1] GE-6
NRC Notified By: BRIAN BLANCHE
HQ OPS Officer: GERRY WAIG
Notification Date: 08/14/2004
Notification Time: 14:44 [ET]
Event Date: 08/14/2004
Event Time: 10:25 [CDT]
Last Update Date: 09/02/2004
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(v)(D) - ACCIDENT MITIGATION
Person (Organization):
LINDA SMITH (R4)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
Event Text
GRAND GULF STANDBY SERVICE WATER "C" AND HIGH PRESSURE CORE SPRAY DECLARED INOPERABLE

"During underwater inspection of the Standby Service Water 'C' system, four piping supports were found with considerable degradation. As a result, the Standby Service Water 'C' and High Pressure Core Spray systems were declared inoperable per Technical Specifications (TS). High Pressure Core Spray is a single - train system that performs a safety function."

The licensee entered the applicable sections of TS 3.7.2, High Pressure Core Spray Service Water System, and TS 3.5.1, High Pressure Core Spray.

The licensee has notified the NRC Resident Inspector.

* * * RETRACTION ON 9/2/04 AT 1610 EDT FROM MICHAEL LARSON TO ARLON COSTA * * *

"Reactor Plant Event Number 40952 was reported on August 14, 2004 at 1344 for an inoperable Standby Service Water 'C' and High Pressure Core Spray system due to degraded Standby Service Water 'C' lateral piping supports. This event is hereby retracted.

"The retraction is based on engineering evaluations and calculations performed that determined that the Standby Service Water 'C' and High Pressure Core Spray System were both OPERABLE and capable of performing their intended safety function. The engineering evaluation and calculations concluded that even without the degraded lateral piping supports, the Standby Service Water 'C' piping maintained its structural integrity and would have performed its intended safety function."

The licensee notified the NRC Resident Inspector.

Notified R4DO (W. Jones).


Power Reactor
Event Number: 40953
Facility: BRUNSWICK
Region: 2     State: NC
Unit: [1] [] []
RX Type: [1] GE-4,[2] GE-4
NRC Notified By: KEITH HANZ
HQ OPS Officer: JEFF ROTTON
Notification Date: 08/14/2004
Notification Time: 13:40 [ET]
Event Date: 08/14/2004
Event Time: 13:08 [EDT]
Last Update Date: 08/14/2004
Emergency Class: UNUSUAL EVENT
10 CFR Section:
50.72(a) (1) (i) - EMERGENCY DECLARED
Person (Organization):
CAUDLE JULIAN (R2)
CYNTHIA CARPENTER (NRR)
HO NIEH (IRD)
LINDA SMITH (R4)
CASTO (RA)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 A/R Y 68 Power Operation 0 Hot Shutdown
Event Text
NOTICE OF UNUSUAL EVENT EMERGENCY DECLARED DUE TO LOSS OF OFFSITE POWER

Licensee declared an Unusual Event at 1308 EDT on 08/14/04. Unusual Event was declared due to a Loss of Offsite Power which occurred due to a Lockout trip of the Station Auxiliary Transformer. All four emergency diesel generators started and loaded properly. On the reactor trip, all rods fully inserted. They received Group II, VI, and VIII PCIS isolations due to the loss of power. The MSIVs are closed and the licensee manually started RCIC for reactor level control and HPCI for reactor pressure control.

The licensee in activating the Emergency Response Organizations. No offsite assistance required.

The licensee notified the NRC Resident Inspector, State and local Emergency response organizations.

* * * UPDATE PROVIDED TO JEFF ROTTON FROM KEITH HANZ AT 1727 EDT ON 08/14/04 * * *

Licensee declared termination of the Unusual Event at 1713 EDT on 08/14/04 after restoring offsite power to the Station Auxiliary Transformer, BOP and Emergency Buses.

The licensee notified the NRC Resident Inspector.

Notified R2DO (Julian), R4DO (Smith), IRD (Nieh), NRR EO (Carpenter), DHS (Doyle), and FEMA (Sullivan)


Power Reactor
Event Number: 40954
Facility: BRUNSWICK
Region: 2     State: NC
Unit: [1] [] []
RX Type: [1] GE-4,[2] GE-4
NRC Notified By: DAVID JESTER
HQ OPS Officer: JEFF ROTTON
Notification Date: 08/14/2004
Notification Time: 15:47 [ET]
Event Date: 08/14/2004
Event Time: 12:59 [EDT]
Last Update Date: 08/14/2004
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(iv)(B) - RPS ACTUATION - CRITICAL
Person (Organization):
CAUDLE JULIAN (R2)
CYNTHIA CARPENTER (NRR)
HO NIEH (IRD)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 A/R Y 69 Power Operation 0 Hot Shutdown
Event Text
RPS ACTUATION DUE TO LOSS OF OFFSITE POWER

"On August 14, 2004, at approximately 1259 hours [EDT], the unit scrammed due to a loss of offsite power. The cause of the loss of power has not been determined at this time. The four emergency diesel generators started as required and properly aligned to the emergency buses. All control rods properly inserted.

"The initial safety significance of this condition is considered to be minimal. All safety systems function properly with the exception of 1 B Standby Gas Train. The 1 B Standby Gas Train tripped due to an overheat condition. Safety significance of this failure is minimal since the 1A Standby Gas Train operated properly and Reactor Building Ventilation System isolated. The plant is in a stable condition.

"Troubleshooting activities are in progress to determine the cause of the event and corrective actions."

Received Group II, VI, and VIII PCIS isolations due to the loss of power. The MSIVs are closed and the licensee manually started RCIC for reactor level control and HPCI for reactor pressure control.

The licensee notified the NRC Resident Inspector.


Power Reactor
Event Number: 40955
Facility: BRUNSWICK
Region: 2     State: NC
Unit: [1] [2] []
RX Type: [1] GE-4,[2] GE-4
NRC Notified By: DAVID JESTER
HQ OPS Officer: JEFF ROTTON
Notification Date: 08/14/2004
Notification Time: 19:05 [ET]
Event Date: 08/14/2004
Event Time: 12:25 [EDT]
Last Update Date: 08/14/2004
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(xiii) - LOSS COMM/ASMT/RESPONSE
Person (Organization):
CAUDLE JULIAN (R2)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 69 Power Operation 69 Power Operation
2 N Y 96 Power Operation 96 Power Operation
Event Text
LOSS OF SEVERAL OFFSITE EMERGENCY PREPAREDNESS SIRENS DUE TO ADVERSE WEATHER

"On August 14, 2004, at approximately 1225 hours [EDT], Brunswick began losing the function of several offsite emergency preparedness sirens as a result of adverse weather conditions associated with Hurricane Charley. There are a total of 36 sirens located in Brunswick and New Hanover Counties, NC. The total number of inoperable sirens peaked at 25. As of 1825 hours [EDT], all but 6 sirens located in Brunswick County have been returned to operable status. At present, all inoperabilities have been the result of loss of AC power. The Brunswick County Emergency Operations Center is aware of the condition of the sirens and maintenance activities are in progress to restore the siren capabilities. Other communications with local, state, and federal emergency response organizations have not been affected.

The initial safety significance of this condition is considered to be minimal. Unit 1 is currently in Mode 3 and Unit 2 is operating in Mode 1 under normal parameters. State and county emergency response officials are aware of the condition and compensatory measures are in place to provide warning to the affected areas if required.

The licensee has notified the NRC Resident Inspector.


Power Reactor
Event Number: 40956
Facility: SUSQUEHANNA
Region: 1     State: PA
Unit: [] [2] []
RX Type: [1] GE-4,[2] GE-4
NRC Notified By: RON FRY
HQ OPS Officer: JEFF ROTTON
Notification Date: 08/14/2004
Notification Time: 21:41 [ET]
Event Date: 08/14/2004
Event Time: 20:45 [EDT]
Last Update Date: 08/14/2004
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(xiii) - LOSS COMM/ASMT/RESPONSE
Person (Organization):
TODD JACKSON (R1)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 N Y 100 Power Operation 100 Power Operation
Event Text
LOSS OF SAFETY PARAMETER DISPLAY SYSTEM

At 2045 [EDT] on 08/14/2004, Computer Maintenance personnel discovered the Unit 2 SPDS computer was not updating properly. A review of history identified that the SPDS computer had stopped updating at 1109 [EDT] on 8/14/2004. The Control Room was notified. Computer Maintenance was successful in resetting the SPDS computer at 2100 [EDT], and it is now properly operating.

Since the Unit 2 SPDS computer system was unavailable for greater than 8 hours, this is considered a Loss of Emergency Assessment Capability and reportable under 10CFR50.72(b)(3)(xiii).

The licensee notified the NRC Resident Inspector.