Skip to main content

Event Notification Report for July 22, 2004

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
07/21/2004 - 07/22/2004

EVENT NUMBERS
408914089340894

Power Reactor
Event Number: 40891
Facility: SALEM
Region: 1     State: NJ
Unit: [1] [2] []
RX Type: [1] W-4-LP,[2] W-4-LP
NRC Notified By: S. SAUER
HQ OPS Officer: ARLON COSTA
Notification Date: 07/22/2004
Notification Time: 13:15 [ET]
Event Date: 07/22/2004
Event Time: 07:10 [EDT]
Last Update Date: 07/22/2004
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(xiii) - LOSS COMM/ASMT/RESPONSE
Person (Organization):
JOHN KINNEMAN (R1)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
2 N Y 23 Power Operation 23 Power Operation
Event Text
LOSS OF POWER TO PRIMARY AND BACKUP OFFSITE SIREN SYSTEM

"At 0710 hrs on 7/22/04 it was discovered by the Salem County 911 Center dispatcher that the primary and backup Alert Notification System (offsite siren system) activation controllers (computers) had lost power. The Salem County Siren computers are the activation controllers for all 34 offsite sirens located in the New Jersey portion of tile 10-mile EPZ. The 37 Delaware Sirens wore not affected. As per instructions, siren technicians were notified at 0748 hours and responded to the 911 Center at 0815 hours. Power was restored to the primary computer at 0835 hours. Subsequent investigation and troubleshooting has determined the following:

"Exact time of power loss is unknown. Last know/verified computer availability was at 1104 on 7/21/04 when a biweekly siren test was successfully completed. An automatic siren poll scheduled for 0645 on 7/22 did not occur which indicates that the loss of power occurred sometime between 1104 on 7/21 and 0645 on 7/22/04.

"Cause of loss of power was determined to be a failed UPS unit that both the primary and backup siren computers were powered from. The failed UPS was removed and primary computer re-powered directly from 911-center normal 120-volt house power. A siren poll was done and. The siren system was declared back in service at 0835 hours on 7/22/04.

"Two separate UPS units will be connected to the Siren activation computers by the end of day today, 7/22/04."

The licensee notified State of New Jersey and the NRC Resident Inspector.


Power Reactor
Event Number: 40893
Facility: GINNA
Region: 1     State: NY
Unit: [1] [] []
RX Type: [1] W-2-LP
NRC Notified By: KEVIN McKAUGHIN
HQ OPS Officer: GERRY WAIG
Notification Date: 07/22/2004
Notification Time: 13:52 [ET]
Event Date: 07/22/2004
Event Time: 09:42 [EDT]
Last Update Date: 07/22/2004
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(ii)(B) - UNANALYZED CONDITION
Person (Organization):
JOHN KINNEMAN (R1)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
Event Text
GAP DISCOVERED IN CONTROL ROOM ENVELOPE

"During Control Room Boundary investigations a gap in the control room envelope was discovered that exceeded the assumptions of the plant toxic gas analysis. The assumptions for the control room radiological analysis were met with the consideration for the use of Kl. The gap size was determined to be approximately 103 square inches versus an analysis assumption of 58.9 square inches. The gaps were immediately repaired."

The licensee suspects that the gap has existed for 20 or more years and was discovered during a control room heating, ventilation, air-conditioning (HVAC) upgrade.

The license has notified the NRC Resident Inspector of this event.


General Information or Other
Event Number: 40894
Rep Org: NE DIV OF RADIOACTIVE MATERIALS
Licensee: STATE OF NE DEPARTMENT OF ROADS
Region: 4
City: LINCOLN   State: NE
County:
License #:
Agreement: Y
Docket:
NRC Notified By: JIM DeFRAIN
HQ OPS Officer: ARLON COSTA
Notification Date: 07/22/2004
Notification Time: 14:32 [ET]
Event Date: 07/22/2004
Event Time: 07:00 [CDT]
Last Update Date: 07/22/2004
Emergency Class: NON EMERGENCY
10 CFR Section:
Person (Organization):
TOM FARNHOLTZ (R4)
JOHN HICKEY (NMSS)
MATTHEW HAHN (TAS)
Event Text
NEBRASKA AGREEMENT STATE REPORT ON STOLEN TROXLER GAUGE

"The State of Nebraska - Department of Roads, reported that a Troxler Model 3400 Series, Serial No. 28779 portable gauge containing 9 millicuries of Cesium-137 and 44 millicuries of Americium-241:Beryllium was stolen from the licensee's vehicle parked at the licensee's facility. The gauge was in its original carrying case. At this time, it has not been confirmed if the gauge or the carrying case was locked at the time of the event. The gauge and its carrying case were removed from the licensee's pickup bed. The pickup bed did have a locked solid bed cover, and it appeared that the bed cover was pried open to gain access to and remove the gauge carrying case. The licensee also reported the stolen gauge to the Nebraska State Patrol (NSP) this morning between 07:00-07:30. The NSP is investigating the event. Follow-up information will be provided to NRC on the recovery of the stolen gauge and entered into NMED."