Skip to main content

Event Notification Report for June 14, 2004

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
06/13/2004 - 06/14/2004

EVENT NUMBERS
40812408134081440815408164081740818

General Information or Other
Event Number: 40812
Rep Org: ILLINOIS EMERGENCY MGMT. AGENCY
Licensee: ADCO SERVICES
Region: 3
City: TINLEY PARK   State: IL
County:
License #: IL-0134701
Agreement: Y
Docket:
NRC Notified By: DAREN PERRERO
HQ OPS Officer: MIKE RIPLEY
Notification Date: 06/14/2004
Notification Time: 10:13 [ET]
Event Date: 06/14/2004
Event Time: 00:00 [CDT]
Last Update Date: 06/14/2004
Emergency Class: NON EMERGENCY
10 CFR Section:
Person (Organization):
PATRICK LOUDEN (R3)
ROBERTO TORRES (NMSS)
JIM WHITNEY (TAS)
Event Text
ILLINOIS AGREEMENT STATE REPORT - SOURCE MISSING IN SHIPMENT

One of five packages being shipped on 6/3/04 from Honeywell Corporation in Phoenix, AZ did not arrive at the licensee's facility as scheduled on 6/4/04. The package consisted of a 7-10 gallon steel drum containing 10 Curies of Pm-147 as sealed sources. The sources were removed from industrial gauging devices being disposed of.

* * * UPDATE ON 6/14/04 AT 1542 EDT FROM D. PERRERO TO A. COSTA * * *

Fed-Ex located the missing shipment in Pittsburgh and arrangements are being made to forward it to ADCO Services Inc, at Tinley Park, IL. Notified NMSS (Essig), R3DO(Louden) and TAS (Whitney).


Power Reactor
Event Number: 40813
Facility: GRAND GULF
Region: 4     State: MS
Unit: [1] [] []
RX Type: [1] GE-6
NRC Notified By: MIKE BEARD
HQ OPS Officer: MIKE RIPLEY
Notification Date: 06/14/2004
Notification Time: 10:56 [ET]
Event Date: 06/14/2004
Event Time: 06:26 [CDT]
Last Update Date: 06/14/2004
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(xiii) - LOSS COMM/ASMT/RESPONSE
Person (Organization):
DAVID GRAVES (R4)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
Event Text
FAILED DATA SERVER FOR EMERGENCY RESPONSE DATA SYSTEM

"At 0626 [CST] on June 14, 2004; the Plant Data System (PDS) data server for the NRC Emergency Response Data System (ERDS) link was found to have failed at 0204 on June 11, 2004. The data server was rebooted, PDS software initiated and ERDS capability restored at 0745 on 6/14/04. Total time out of service was 3 days, 5 hours and 41 minutes."

The licensee will notify the NRC Resident Inspector.


Power Reactor
Event Number: 40814
Facility: PALO VERDE
Region: 4     State: AZ
Unit: [] [2] []
RX Type: [1] CE,[2] CE,[3] CE
NRC Notified By: JIM MORELAND
HQ OPS Officer: BILL GOTT
Notification Date: 06/14/2004
Notification Time: 11:39 [ET]
Event Date: 06/14/2004
Event Time: 07:44 [MST]
Last Update Date: 06/14/2004
Emergency Class: ALERT
10 CFR Section:
50.72(a) (1) (i) - EMERGENCY DECLARED 50.72(b)(2)(iv)(B) - RPS ACTUATION - CRITICAL 50.72(b)(2)(xi) - OFFSITE NOTIFICATION 50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION
Person (Organization):
DAVID GRAVES (R4)
TERRY REIS (NRR)
DICK WESSMAN (DIRO)
ROY ZIMMERMAN (NSIR)
MIKE INZER (DHS)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 A/R Y 100 Power Operation 0 Hot Standby
Event Text
ALERT DECLARED - REACTOR TRIP DUE TO LOSS OF OFF SITE POWER

On June 14, 2004, at approximately 07:44 Mountain Standard Time (MST) all three units at the Palo Verde Nuclear Generating Station experienced automatic reactor trips coincident with a grid disturbance and loss of offsite power in the Palo Verde Switchyard. Unit 2 declared an ALERT Emergency Plan classification at approximately 07:54 due to a loss of AC power to essential buses reduced to a single power source for greater than 15 minutes such that any additional single failure would result in a station blackout. Subsequently, at 09:51 Unit 2 downgraded the Emergency Plan classification to a NOTIFICATION OF UNUSUAL EVENT when AC power was restored from a single essential bus to both essential buses. Units 1 and 3 declared a NOTIFICATION OF UNUSUAL EVENT at 07:53 MST due to a loss of offsite power to essential buses for greater than 15 minutes. The NOTIFICATION OF UNUSUAL EVENT was terminated for all 3 units at 12:07 MST.

Unit 1 and 2 manually initiated a Main Steam Isolation System ESF actuation by procedure. Unit 3 received an automatic Main Steam Isolation System ESF actuation.

Due to the loss of offsite power, the Emergency Plan Technical Support Center (TSC) was unavailable. The Unit 2 Satellite TSC was to be staffed by the Emergency Response Organization in response to the loss of assessment capability. Power to the TSC has since been restored.

The Emergency Plan ALERT declaration includes staffing of the Joint Emergency New Center to address expected media interest.

All three units were at normal operating temperature and pressure prior to the trip. All CEAs inserted fully into the reactor cores. All Emergency Diesel Generators (EDGs) (2 per unit) associated with each of the 3 units started as expected in response to the loss of offsite power to their safety buses. Unit 2's train "A" EDG started, but did not indicate volts or amps and was manually shutdown.

The offsite power grid had several perturbations for approximately one hour following the event but has been stable since. LCO 3.8.1, AC Sources - Operating, was entered in each unit as a result of this event. Heat removal is to atmosphere via atmospheric dump valves in natural circulation. Main steam safety valves may have lifted for a brief time. Restoration of forced reactor coolant circulation is pending assurance that the offsite power grid can reliably support the load. No major equipment was inoperable prior to the event that contributed to the event.

All 3 units are stable at normal operating temperature and pressure in Mode 3. The event did not result in any challenges to fission product barriers and there were no adverse safety consequences as a result of this event. The event did not adversely affect the safe operation of the plant


NRC Resident Inspector was notified.

FBI Jeff Muller and Mr. Rosales (Mexican National Commission of Nuclear Safety and Safeguards {CNSNS}) were notified.


* * * Update at 1815 @ 06/14/04 * * *

Notified Reg 4 RDO (Graves), NRR (Bateman), DHS (Lee), FEMA (Canupp), DOE (Sal Moroni), EPA (Stalcup), EPA (Crews), HSS (Davidson), and Mexico (Rosales)


NOTE: See events 40815, 40816 and 40818


Power Reactor
Event Number: 40815
Facility: PALO VERDE
Region: 4     State: AZ
Unit: [1] [] []
RX Type: [1] CE,[2] CE,[3] CE
NRC Notified By: JIM MORELAND
HQ OPS Officer: BILL GOTT
Notification Date: 06/14/2004
Notification Time: 11:39 [ET]
Event Date: 06/14/2004
Event Time: 07:44 [MST]
Last Update Date: 06/14/2004
Emergency Class: UNUSUAL EVENT
10 CFR Section:
50.72(a) (1) (i) - EMERGENCY DECLARED 50.72(b)(2)(iv)(B) - RPS ACTUATION - CRITICAL 50.72(b)(2)(xi) - OFFSITE NOTIFICATION 50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION
Person (Organization):
DAVID GRAVES (R4)
TERRY REIS (NRR)
DICK WESSMAN (DIRO)
ROY ZIMMERMAN (NSIR)
MIKE INZER (DHS)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 A/R Y 100 Power Operation 0 Hot Standby
Event Text
UNUSUAL EVENT DECLARED DUE TO REACTOR TRIP DUE TO LOSS OF OFF SITE POWER

On June 14, 2004, at approximately 07:44 Mountain Standard Time (MST) all three units at the Palo Verde Nuclear Generating Station experienced automatic reactor trips coincident with a grid disturbance and loss of offsite power in the Palo Verde Switchyard. Unit 1 declared a NOTIFICATION OF UNUSUAL EVENT at 07:53 MST due to a loss of offsite power to essential buses for greater than 15 minutes. The NOTIFICATION OF UNUSUAL EVENT was terminated at 12:07 MST.

Unit 1 manually initiated a Main Steam Isolation System ESF actuation by procedure.

Due to the loss of offsite power, the Emergency Plan Technical Support Center (TSC) was unavailable. The Unit 2 Satellite TSC was to be staffed by the Emergency Response Organization in response to the loss of assessment capability. Power to the TSC has since been restored.

The unit was at normal operating temperature and pressure prior to the trip. All CEAs inserted fully into the reactor cores. All Emergency Diesel Generators (EDGs) (2 per unit) associated with the unit started as expected in response to the loss of offsite power to their safety buses.

The offsite power grid had several perturbations for approximately one hour following the event but has been stable since. LCO 3.8.1, AC Sources - Operating, was entered as a result of this event. Heat removal is to atmosphere via atmospheric dump valves in natural circulation. Main steam safety valves may have lifted for a brief time. Restoration of forced reactor coolant circulation is pending assurance that the offsite power grid can reliably support the load. No major equipment was inoperable prior to the event that contributed to the event.

The Unit is stable at normal operating temperature and pressure in Mode 3. The event did not result in any challenges to fission product barriers and there were no adverse safety consequences as a result of this event. The event did not adversely affect the safe operation of the plant

NRC Resident Inspector was notified.

FBI Jeff Muller and Mr. Rosales (Mexican National Commission of Nuclear Safety and Safeguards {CNSNS}) were notified.


* * * Update at 1815 @ 06/14/04 * * *

Notified Reg 4 RDO (Graves), NRR (Bateman), DHS (Lee), FEMA (Canupp), DOE (Sal Moroni), EPA (Stalcup), EPA (Crews), HSS (Davidson), and Mexico (Rosales)

Note: see related events # 40814, 40816 and 40818


Power Reactor
Event Number: 40816
Facility: PALO VERDE
Region: 4     State: AZ
Unit: [] [] [3]
RX Type: [1] CE,[2] CE,[3] CE
NRC Notified By: JIM MORELAND
HQ OPS Officer: BILL GOTT
Notification Date: 06/14/2004
Notification Time: 11:39 [ET]
Event Date: 06/14/2004
Event Time: 07:44 [MST]
Last Update Date: 06/14/2004
Emergency Class: UNUSUAL EVENT
10 CFR Section:
50.72(a) (1) (i) - EMERGENCY DECLARED 50.72(b)(2)(iv)(B) - RPS ACTUATION - CRITICAL 50.72(b)(2)(xi) - OFFSITE NOTIFICATION 50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION
Person (Organization):
DAVID GRAVES (R4)
TERRY REIS (NRR)
DICK WESSMAN (DIRO)
ROY ZIMMERMAN (NSIR)
MIKE INZER (DHS)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
3 A/R Y 100 Power Operation 0 Hot Standby
Event Text
UNUSUAL EVENT DUE TO REACTOR TRIP DUE TO LOSS OF OFF SITE POWER

On June 14, 2004, at approximately 07:44 Mountain Standard Time (MST) all three units at the Palo Verde Nuclear Generating Station experienced automatic reactor trips coincident with a grid disturbance and loss of offsite power in the Palo Verde Switchyard. Unit 3 declared a NOTIFICATION OF UNUSUAL EVENT at 07:53 MST due to a loss of offsite power to essential buses for greater than 15 minutes. The NOTIFICATION OF UNUSUAL EVENT was terminated at 12:07 MST.

Unit 3 received an automatic Main Steam Isolation System ESF actuation.

Due to the loss of offsite power, the Emergency Plan Technical Support Center (TSC) was unavailable. The Unit 2 Satellite TSC was to be staffed by the Emergency Response Organization in response to the loss of assessment capability. Power to the TSC has since been restored.

The unit was at normal operating temperature and pressure prior to the trip. All CEAs inserted fully into the reactor cores. All Emergency Diesel Generators (EDGs) (2 per unit) associated with the unit started as expected in response to the loss of offsite power to their safety buses.

The offsite power grid had several perturbations for approximately one hour following the event but has been stable since. LCO 3.8.1, AC Sources - Operating, was entered as a result of this event. Heat removal is to atmosphere via atmospheric dump valves in natural circulation. Main steam safety valves may have lifted for a brief time. Restoration of forced reactor coolant circulation is pending assurance that the offsite power grid can reliably support the load. No major equipment was inoperable prior to the event that contributed to the event.

The Unit is stable at normal operating temperature and pressure in Mode 3. The event did not result in any challenges to fission product barriers and there were no adverse safety consequences as a result of this event. The event did not adversely affect the safe operation of the plant

NRC Resident Inspector was notified.

FBI Jeff Muller and Mr. Rosales (Mexican National Commission of Nuclear Safety and Safeguards {CNSNS}) were notified.

* * * Update at 1815 @ 06/14/04 * * *

Notified Reg 4 RDO (Graves), NRR (Bateman), DHS (Lee), FEMA (Canupp), DOE (Sal Moroni), EPA (Stalcup), EPA (Crews), HSS (Davidson), and Mexico (Rosales)

Note: see related events 40815 , 40814 and 40818


Power Reactor
Event Number: 40817
Facility: SURRY
Region: 2     State: VA
Unit: [1] [2] []
RX Type: [1] W-3-LP,[2] W-3-LP
NRC Notified By: RUSSELL DEANE
HQ OPS Officer: CHAUNCEY GOULD
Notification Date: 06/14/2004
Notification Time: 13:48 [ET]
Event Date: 06/14/2004
Event Time: 07:35 [EDT]
Last Update Date: 06/14/2004
Emergency Class: NON EMERGENCY
10 CFR Section:
26.73 - FITNESS FOR DUTY
Person (Organization):
MARK LESSER (R2)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
2 N Y 100 Power Operation 100 Power Operation
Event Text
FAILURE OF SUPERVISOR TO PASS A FITNESS FOR DUTY TEST

At 0735 on 06/14/04 a Dominion Virginia Power supervisor tested positive as a result of pre-access Fitness for Duty testing.


The NRC Resident Inspector has been notified.


Power Reactor
Event Number: 40818
Facility: SAN ONOFRE
Region: 4     State: CA
Unit: [] [2] [3]
RX Type: [1] W-3-LP,[2] CE,[3] CE
NRC Notified By: CLAY WILLIAMS
HQ OPS Officer: CHAUNCEY GOULD
Notification Date: 06/14/2004
Notification Time: 17:14 [ET]
Event Date: 06/14/2004
Event Time: 07:41 [PDT]
Last Update Date: 06/14/2004
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(v)(D) - ACCIDENT MITIGATION
Person (Organization):
DAVID GRAVES (R4)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 N Y 100 Power Operation 100 Power Operation
3 N Y 100 Power Operation 100 Power Operation
Event Text
LICENSEE DECLARED OFFSITE POWER INOPERABLE DUE TO DIP IN GRID FREQUENCY

"On June 14, 2004 at 0741 PDT, the offsite power grid connected to San Onofre experienced a system disturbance. Grid frequency dipped to about 59.7 Hz or slightly lower, and then recovered about three minutes later. Plant Operators declared offsite power inoperable. Southern California Edison is conservatively reporting this event in accordance with 10 CFR 50.72(b)(3)(v)(D). The diesel generators for both Units 2 and 3 were operable during this event. At the time of this report, Units 2 and 3 continue to operate at about 100% power."

The NRC Resident Inspector was notified.

NOTE: see events 40814, 40815 and 40816