Skip to main content

Event Notification Report for June 12, 2004

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
06/11/2004 - 06/12/2004

EVENT NUMBERS
40811

Power Reactor
Event Number: 40811
Facility: SUMMER
Region: 2     State: SC
Unit: [1] [] []
RX Type: [1] W-3-LP
NRC Notified By: AMY MONROE
HQ OPS Officer: MIKE RIPLEY
Notification Date: 06/13/2004
Notification Time: 02:23 [ET]
Event Date: 06/12/2004
Event Time: 20:29 [EDT]
Last Update Date: 06/13/2004
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION
Person (Organization):
MARK LESSER (R2)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
Event Text
EMERGENCY DIESEL STARTED AND LOADED ON BUS UNDERVOLTAGE SIGNAL

"At 2029 on 6/12/2004, the normal incoming feed (1DA) to the plant opened on an undervoltage signal. At the time of the event a severe thunderstorm was in progress. The 'A' Emergency Diesel Generator started and loads sequenced on as designed. The 'A' Residual Heat Removal pump started but did not inject any water into the Reactor Coolant System. The 'A' Emergency Feedwater Pump started and ran for approximately seven minutes. Other plant equipment also responded as expected.

"The plant transferred back to offsite power at 2252. A follow-up LER will be provide in 60 days."

The licensee notified the NRC Resident Inspector.