Event Notification Report for April 09, 2004
U.S. Nuclear Regulatory Commission
Operations Center
EVENT REPORTS FOR
04/08/2004 - 04/09/2004
Power Reactor
Event Number: 40661
Facility: COLUMBIA GENERATING STATION
Region: 4 State: WA
Unit: [2] [] []
RX Type: [2] GE-5
NRC Notified By: DARIN RODABAUGH
HQ OPS Officer: BILL GOTT
Region: 4 State: WA
Unit: [2] [] []
RX Type: [2] GE-5
NRC Notified By: DARIN RODABAUGH
HQ OPS Officer: BILL GOTT
Notification Date: 04/09/2004
Notification Time: 17:14 [ET]
Event Date: 04/09/2004
Event Time: 12:30 [PDT]
Last Update Date: 04/09/2004
Notification Time: 17:14 [ET]
Event Date: 04/09/2004
Event Time: 12:30 [PDT]
Last Update Date: 04/09/2004
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(xi) - OFFSITE NOTIFICATION
10 CFR Section:
50.72(b)(2)(xi) - OFFSITE NOTIFICATION
Person (Organization):
BLAIR SPITZBERG (R4)
BLAIR SPITZBERG (R4)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 2 | N | Y | 100 | Power Operation | 100 | Power Operation |
OFFSITE NOTIFICATION OF CHEMICAL SPILL
"On 419/04 at 1230 hours, Energy Northwest contacted Washington State Emergency Management Division (1-800-258-5990) to report a spill of pHreeGuard-4500 (a water treatment scale inhibitor) at the Columbia Generating Station Circulating Water Pump House. Washington State Emergency Management Division assigned Incident No. 04-0721 to this report. It is estimated as much as 60 gallons of the water treatment chemical could have been released to the concrete tank pedestal, asphalt apron, and adjoining soil over a period of several hours from a leaking expansion joint at the tank outlet. The leak was detected at about 0830 hrs. The leaking material is captured and redirected to the Circulating water basin. Washington State Emergency Management Division is relaying the information to the on-call responder in the Washington State Department of Ecology's Central Region Office.
"This event is being reported under 10 CFR 50.72 (b)(2)(xi), any event or situation, related to the health and safety of the pubic or on-site personnel, or protection if the environment, for which a news release is planned or notification to other government agencies has been or will be made."
The Licensee notified the NRC Resident Inspector.
"On 419/04 at 1230 hours, Energy Northwest contacted Washington State Emergency Management Division (1-800-258-5990) to report a spill of pHreeGuard-4500 (a water treatment scale inhibitor) at the Columbia Generating Station Circulating Water Pump House. Washington State Emergency Management Division assigned Incident No. 04-0721 to this report. It is estimated as much as 60 gallons of the water treatment chemical could have been released to the concrete tank pedestal, asphalt apron, and adjoining soil over a period of several hours from a leaking expansion joint at the tank outlet. The leak was detected at about 0830 hrs. The leaking material is captured and redirected to the Circulating water basin. Washington State Emergency Management Division is relaying the information to the on-call responder in the Washington State Department of Ecology's Central Region Office.
"This event is being reported under 10 CFR 50.72 (b)(2)(xi), any event or situation, related to the health and safety of the pubic or on-site personnel, or protection if the environment, for which a news release is planned or notification to other government agencies has been or will be made."
The Licensee notified the NRC Resident Inspector.
Power Reactor
Event Number: 40662
Facility: CALVERT CLIFFS
Region: 1 State: MD
Unit: [1] [2] []
RX Type: [1] CE,[2] CE
NRC Notified By: ROBERT PACE
HQ OPS Officer: BILL GOTT
Region: 1 State: MD
Unit: [1] [2] []
RX Type: [1] CE,[2] CE
NRC Notified By: ROBERT PACE
HQ OPS Officer: BILL GOTT
Notification Date: 04/09/2004
Notification Time: 17:33 [ET]
Event Date: 04/09/2004
Event Time: 16:30 [EDT]
Last Update Date: 04/09/2004
Notification Time: 17:33 [ET]
Event Date: 04/09/2004
Event Time: 16:30 [EDT]
Last Update Date: 04/09/2004
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(xiii) - LOSS COMM/ASMT/RESPONSE
10 CFR Section:
50.72(b)(3)(xiii) - LOSS COMM/ASMT/RESPONSE
Person (Organization):
LAWRENCE DOERFLEIN (R1)
LAWRENCE DOERFLEIN (R1)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 1 | N | Y | 93 | Power Operation | 93 | Power Operation |
| 2 | N | Y | 100 | Power Operation | 100 | Power Operation |
LOSS OF POWER TO EOF
At 1630 on 4/9/04, it was discovered the Emergency Operating Facility had lost power. It is still without power. The cause was the backup facility diesel generator started and attempted to power the facility while normal offsite power was still applied. The electrical transfer switch was damaged. The time to repair is unknown. A space normally used as a media center is used as an alternate EOF.
The Licensee notified the NRC Resident Inspector.
At 1630 on 4/9/04, it was discovered the Emergency Operating Facility had lost power. It is still without power. The cause was the backup facility diesel generator started and attempted to power the facility while normal offsite power was still applied. The electrical transfer switch was damaged. The time to repair is unknown. A space normally used as a media center is used as an alternate EOF.
The Licensee notified the NRC Resident Inspector.
General Information or Other
Event Number: 40663
Rep Org: TEXAS DEPARTMENT OF HEALTH
Licensee: PSI CONSTRUCTION COMPANY
Region: 4
City: SAN ANTONIO State: TX
County:
License #: TX L04946
Agreement: Y
Docket:
NRC Notified By: JIM OGDEN
HQ OPS Officer: DICK JOLLIFFE
Licensee: PSI CONSTRUCTION COMPANY
Region: 4
City: SAN ANTONIO State: TX
County:
License #: TX L04946
Agreement: Y
Docket:
NRC Notified By: JIM OGDEN
HQ OPS Officer: DICK JOLLIFFE
Notification Date: 04/09/2004
Notification Time: 21:49 [ET]
Event Date: 04/09/2004
Event Time: 16:45 [CDT]
Last Update Date: 04/09/2004
Notification Time: 21:49 [ET]
Event Date: 04/09/2004
Event Time: 16:45 [CDT]
Last Update Date: 04/09/2004
Emergency Class: NON EMERGENCY
10 CFR Section:
10 CFR Section:
Person (Organization):
BLAIR SPITZBERG (R4)
C.W. (BILL) REAMER (NMSS)
MATTHEW HAHN (TAS)
VICTOR GONZALEZ (MEX)
BLAIR SPITZBERG (R4)
C.W. (BILL) REAMER (NMSS)
MATTHEW HAHN (TAS)
VICTOR GONZALEZ (MEX)
TEXAS AGREEMENT STATE EVENT - STOLEN TROXLER MOISTURE DENSITY GAUGE
At 2149 EDT on 04/09/04, the Texas Department of Health, Bureau of Radiation Control reported that between 1645 CDT and 1910 CDT on 04/09/04, a Troxler Moisture Density Gauge, Model #3430, Serial #24711, belonging to PSI Construction Company, San Antonio, TX was stolen from a 2003 Ford Ranger company pickup truck in San Antonio, TX. The stolen gauge contained an 8 millicurie Cs-137 source and a 40 millicurie Am-241:Be source. The gauge case was locked to the back of the truck but the gauge was not locked in its case. The company truck driver was suspended pending investigation. The theft was reported to the San Antonio Police Department. An announcement about the theft will be made on the local AM radio and the local TV Station tonight at 2200 CDT offering a $500 reward for the return of the gauge.
At 2149 EDT on 04/09/04, the Texas Department of Health, Bureau of Radiation Control reported that between 1645 CDT and 1910 CDT on 04/09/04, a Troxler Moisture Density Gauge, Model #3430, Serial #24711, belonging to PSI Construction Company, San Antonio, TX was stolen from a 2003 Ford Ranger company pickup truck in San Antonio, TX. The stolen gauge contained an 8 millicurie Cs-137 source and a 40 millicurie Am-241:Be source. The gauge case was locked to the back of the truck but the gauge was not locked in its case. The company truck driver was suspended pending investigation. The theft was reported to the San Antonio Police Department. An announcement about the theft will be made on the local AM radio and the local TV Station tonight at 2200 CDT offering a $500 reward for the return of the gauge.