Skip to main content

Event Notification Report for February 16, 2004

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
02/15/2004 - 02/16/2004

EVENT NUMBERS
4052340524

Power Reactor
Event Number: 40523
Facility: GINNA
Region: 1     State: NY
Unit: [1] [] []
RX Type: [1] W-2-LP
NRC Notified By: JAMES WHITE
HQ OPS Officer: DICK JOLLIFFE
Notification Date: 02/16/2004
Notification Time: 02:58 [ET]
Event Date: 02/16/2004
Event Time: 02:25 [EST]
Last Update Date: 02/16/2004
Emergency Class: UNUSUAL EVENT
10 CFR Section:
50.72(a) (1) (i) - EMERGENCY DECLARED
Person (Organization):
JAMES TRAPP (R1)
JOHN HANNON (NRR)
SUSAN FRANT (IRO)
KEN SWEETSER (FEMA)
JOHN FROST (DHS)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
Event Text
UNUSUAL EVENT DECLARED DUE TO SERVICE AIR COMPRESSOR CONTROLLER EXPLODING

At 0225 EST on 02/16/04, the licensee declared an Unusual Event due to the instrument air/service air system service air compressor controller exploding due to an electrical fault. Instrument air compressor alarm #H-16 actuated. The backup 'A' and 'B' instrument air compressors auto started. The licensee immediately electrically isolated the service air compressor controller. The licensee declared the Unusual Event in accordance with EAL 8.3.2, an explosion or detection of explosion affecting plant equipment or structures within plant protected area boundaries. No other plant equipment or structures were affected. The plant is stable at 100% power. There is no indication of tampering or foreign objects inside the controller. The licensee is investigating the cause. The licensee notified the NRC Resident Inspector and State and Local Officials. The licensee does not plan to issue a press release.

* * * Update at 0425 EST on 02/16/04 from John White to Jolliffe * * *

At 0420 EST on 02/16/04, the licensee terminated the Unusual Event based on the service air compressor controller being electrically isolated and removed from service and the surrounding area secured. The licensee is continuing to investigate the cause of the electrical fault. Plant security personnel determined in accordance with their security tampering procedure that this event is clearly not security related. The licensee notified the NRC Resident Inspector and State and Local Officials of the termination of the Unusual Event. Notified R1DO James Trapp, NRR EO John Hannon, DIRO Susan Frant, TAS Hahn, FEMA Ken Sweetser, and DHS John Frost.


General Information or Other
Event Number: 40524
Rep Org: FAIRBANKS MORSE ENGINE
Licensee: FAIRBANKS MORSE ENGINE
Region: 3
City: BELOIT   State: WI
County:
License #:
Agreement: Y
Docket:
NRC Notified By: TODD COLLINS (FAX)
HQ OPS Officer: ARLON COSTA
Notification Date: 02/16/2004
Notification Time: 14:57 [ET]
Event Date: 02/16/2004
Event Time: 00:00 [CST]
Last Update Date: 02/16/2004
Emergency Class: NON EMERGENCY
10 CFR Section:
21.21 - UNSPECIFIED PARAGRAPH
Person (Organization):
MARK LESSER (R2)
TERRY REIS (NRR)
Event Text
PART 21.21 NOTIFICATION OF POTENTIAL SAFETY HAZARD ASSOCIATED WITH USE OF TURBOCHARGER

"On February 12, 2004, Fairbanks Morse Engine evaluation determined a potential safety hazard associated with the use of ABB turbocharger model VTC-304 on OP engines only.

"Torsional resonance has been found in the rotating assembly which is excited by exhaust pulses. The resonance manifests itself as either a bent or broken shaft, slipped compressor wheel, cracked compressor wheel or complete rupture of the compressor set. Once failure occurs, engine power cannot be sustained.

"This condition is corrected by machining the rotating assembly to tune the natural frequency away from operating conditions.

"The only affected site is Crystal River 3. (6) turbos have been shipped to this site. None of the turbos have been installed and all are in storage. The FM parts department will arrange to have the turbos returned to the factory to have the necessary machining performed."