Skip to main content

Event Notification Report for January 24, 2004

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
01/23/2004 - 01/24/2004

EVENT NUMBERS
40474

Power Reactor
Event Number: 40474
Facility: DRESDEN
Region: 3     State: IL
Unit: [] [] [3]
RX Type: [1] GE-1,[2] GE-3,[3] GE-3
NRC Notified By: DAN DALY
HQ OPS Officer: DICK JOLLIFFE
Notification Date: 01/24/2004
Notification Time: 03:22 [ET]
Event Date: 01/24/2004
Event Time: 00:37 [CST]
Last Update Date: 01/24/2004
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(iv)(B) - RPS ACTUATION - CRITICAL 50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION
Person (Organization):
ROGER LANKSBURY (R3)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
3 A/R Y 96 Power Operation 0 Hot Shutdown
Event Text
AUTO REACTOR SCRAM DUE TO AUTO MAIN TURBINE TRIP

At 0322 EST on 01/24/03, Licensee reported that at 0037 CST on 01/24/03, the Unit 3 reactor auto scrammed from 96% power due to an auto main turbine trip while performing weekly main turbine testing. All control rods inserted completely. Steam is being dumped to the main condenser. PCIS Group 2 (Containment Ventilation System) and Group 3 (Shutdown Cooling System) isolated as expected due to reactor vessel level decrease following the scram. Reactor vessel level is being maintained at normal level (30 inches) with the reactor feedwater system. Reactor pressure is 900 psig and moderator temperature is 530 degrees F. All systems functioned as expected. Unit 3 is in Condition 3 (Hot Shutdown). The cause of the main turbine trip is under investigation. This event had no effect on Unit 2. The licensee notified the NRC Resident Inspector.