Skip to main content

Event Notification Report for September 15, 2003

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
09/14/2003 - 09/15/2003

EVENT NUMBERS
401584015940160

Power Reactor
Event Number: 40158
Facility: PEACH BOTTOM
Region: 1     State: PA
Unit: [2] [3] []
RX Type: [2] GE-4,[3] GE-4
NRC Notified By: BRIAN OVERMILLER
HQ OPS Officer: JOHN MacKINNON
Notification Date: 09/15/2003
Notification Time: 03:06 [ET]
Event Date: 09/15/2003
Event Time: 02:39 [EDT]
Last Update Date: 09/15/2003
Emergency Class: UNUSUAL EVENT
10 CFR Section:
50.72(a) (1) (i) - EMERGENCY DECLARED
Person (Organization):
MOHAMED SHANBAKY (R1)
CORNELIUS HOLDEN (NRR)
DOUG WEAVER (IRO)
RANDY BLOUGH (R1)
HUB MILLER (R1RA)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 A/R Y 100 Power Operation 0 Hot Shutdown
3 A/R Y 91 Power Operation 0 Hot Shutdown
Event Text
DUAL UNIT REACTOR SCRAM. DISCRETIONAY UNUSUAL EVENT DECLARED

"A discretionary UE has been declared for PB (Peach Bottom) U/2 (Unit 2) and U/3 (Unit 3) due to a dual unit transient that has resulted in both unit's scramming with a Group 1 (Main Steam Isolation Valve closure) PCIS isolation.

"An electrical transient caused all 4KV emergency buses to be powered by the diesel generators. One diesel generator (E2) subsequently tripped leaving 6 of 8 (3 per unit) buses energized.

"Off-site power is available. Preparations for transfer back to off-site power is in progress. The U/3 (Unit 3) "D" SRV (Safety relief valve) opened and did not close until electrically deenergized. The SRV is closed at this time.'

Both reactors scrammed at 0132 EDT.

NRC Resident Inspectors, State and Local were notified by the licensee.

* * * Update 09/15/03 at 1055 EDT by McClellan to MacKinnon * * *

Unusual Event for Peach Bottom Nuclear Power Station Units 2 & 3 was terminated at 1046 EDT. Unusual Event was terminated because plant conditions have been stabilized, offsite electrical power has been restored to the plant and both plants being in cold shutdown in Mode 4. An investigation is in progress. State and Local will be notified by the licensee. R1DO (M. Shanbaky), NRR EO (C. Holden), DIRO Manager (Doug Weaver), FEMA (Jim Dunker), DHS (Mark Babb) & R4DO (T. Gody) notified.

The NRC Resident Inspectors are onsite and have been informed of the termination of the unusual event by the licensee.


Power Reactor
Event Number: 40159
Facility: SEABROOK
Region: 1     State: NH
Unit: [1] [] []
RX Type: [1] W-4-LP
NRC Notified By: JAMES PESCHEL
HQ OPS Officer: RICH LAURA
Notification Date: 09/15/2003
Notification Time: 16:40 [ET]
Event Date: 09/15/2003
Event Time: 00:00 [EDT]
Last Update Date: 09/15/2003
Emergency Class: NON EMERGENCY
10 CFR Section:
21.21 - UNSPECIFIED PARAGRAPH
Person (Organization):
CORNELIUS HOLDEN (NRR)
HAROLD GRAY (R1)
JACK FOSTER (NRR)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
Event Text
PART 21 ISSUE AT SEABROOK ON SPENT FUEL POOL TEST COUPONS

The licensee reported an apparent abnormality involving Boral spent fuel pool test coupons. Westinghouse built the spent fuel pool racks using Boral material manufactured by ARR Inc. Specifically, inspection of test coupons revealed bulging or blistering of the aluminum cladding. The information provided by the licensee does not include any other affected plants.


General Information or Other
Event Number: 40160
Rep Org: UTAH DIVISION OF RADIATION CONTROL
Licensee: UTAH VALLEY REGIONAL MEDICAL CENTER
Region: 4
City: PROVO   State: UT
County:
License #: UT2500129
Agreement: Y
Docket:
NRC Notified By: JULIE FELICE
HQ OPS Officer: RICH LAURA
Notification Date: 09/15/2003
Notification Time: 18:25 [ET]
Event Date: 09/15/2003
Event Time: 15:52 [MDT]
Last Update Date: 09/15/2003
Emergency Class: NON EMERGENCY
10 CFR Section:
Person (Organization):
ANTHONY GODY (R4)
PATRICIA HOLAHAN (NMSS)
Event Text
UTAH AGREEMENT STATE REPORT ON MEDICAL EVENT

"A patient was administered 15 millicuries of I-131 sodium iodide rather than 4 millicuries for a post-ablation scan. The administrative dosage differed from the prescribed dosage by more than 20% of the prescribed dosage."