Event Notification Report for June 27, 2002
U.S. Nuclear Regulatory Commission
Operations Center
EVENT REPORTS FOR
06/26/2002 - 06/27/2002
EVENT NUMBERS
3902739022390233902439033
Power Reactor
Event Number: 39027
Facility: HOPE CREEK
Region: 1 State: NJ
Unit: [1] [] []
RX Type: [1] GE-4
NRC Notified By: RITA BRADDICK
HQ OPS Officer: GERRY WAIG
Region: 1 State: NJ
Unit: [1] [] []
RX Type: [1] GE-4
NRC Notified By: RITA BRADDICK
HQ OPS Officer: GERRY WAIG
Notification Date: 06/28/2002
Notification Time: 13:43 [ET]
Event Date: 06/27/2002
Event Time: 18:00 [EDT]
Last Update Date: 06/28/2002
Notification Time: 13:43 [ET]
Event Date: 06/27/2002
Event Time: 18:00 [EDT]
Last Update Date: 06/28/2002
Emergency Class: NON EMERGENCY
10 CFR Section:
10 CFR Section:
Person (Organization):
MICHAEL MODES (R1)
MICHAEL MODES (R1)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 1 | N | Y | 24 | Power Operation | 24 | Power Operation |
LICENSED THERMAL POWER LIMIT EXCEEDED AT HOPE CREEK
The following is taken from a facsimile sent by the licensee:
"On May 26, 2002, an equipment failure related to the feedwater crossflow correction factor resulted in the Hope Creek Generating Station operating above its' Licensed Power Limit of 3339 megawatts thermal for a period of approximately 8 hours. Upon identification of an anomalous indication associated with the crossflow indication, operators conservatively lowered Reactor power to a value below the station's licensed limit pending evaluation of the condition. Subsequent detailed evaluation has since confirmed that a malfunction of the crossflow instrumentation correction factor caused an overpower condition. The event date and time coincide with the completion of the evaluation. Contrary to regulatory guidance for power maintenance, the facility operated at approximately 100.25% for greater than 2 hours. However, at no time did the station power level exceed 100.47%, nor was the shift average power level limit exceeded. This 24 hour report is being made for violation of the requirements contained in the Operating License (Hope Creek Operating License Number NPF-57, section 2.F, specifically Section 2.C (1)-exceeding the maximum power level of 3339 megawatts thermal.[)]"
The licensee notified the NRC Resident Inspector.
The following is taken from a facsimile sent by the licensee:
"On May 26, 2002, an equipment failure related to the feedwater crossflow correction factor resulted in the Hope Creek Generating Station operating above its' Licensed Power Limit of 3339 megawatts thermal for a period of approximately 8 hours. Upon identification of an anomalous indication associated with the crossflow indication, operators conservatively lowered Reactor power to a value below the station's licensed limit pending evaluation of the condition. Subsequent detailed evaluation has since confirmed that a malfunction of the crossflow instrumentation correction factor caused an overpower condition. The event date and time coincide with the completion of the evaluation. Contrary to regulatory guidance for power maintenance, the facility operated at approximately 100.25% for greater than 2 hours. However, at no time did the station power level exceed 100.47%, nor was the shift average power level limit exceeded. This 24 hour report is being made for violation of the requirements contained in the Operating License (Hope Creek Operating License Number NPF-57, section 2.F, specifically Section 2.C (1)-exceeding the maximum power level of 3339 megawatts thermal.[)]"
The licensee notified the NRC Resident Inspector.
Hospital
Event Number: 39022
Rep Org: MILFORD HOSPITAL
Licensee: MILFORD HOSPITAL
Region: 1
City: MILFORD State: CT
County:
License #: 0613611-01
Agreement: N
Docket:
NRC Notified By: STUART KORCHIN
HQ OPS Officer: FANGIE JONES
Licensee: MILFORD HOSPITAL
Region: 1
City: MILFORD State: CT
County:
License #: 0613611-01
Agreement: N
Docket:
NRC Notified By: STUART KORCHIN
HQ OPS Officer: FANGIE JONES
Notification Date: 06/27/2002
Notification Time: 10:00 [ET]
Event Date: 06/27/2002
Event Time: 00:00 [EDT]
Last Update Date: 06/27/2002
Notification Time: 10:00 [ET]
Event Date: 06/27/2002
Event Time: 00:00 [EDT]
Last Update Date: 06/27/2002
Emergency Class: NON EMERGENCY
10 CFR Section:
10 CFR Section:
Person (Organization):
MICHAEL MODES (R1)
DOUG BROADDUS (NMSS)
MICHAEL MODES (R1)
DOUG BROADDUS (NMSS)
HOSPITAL WASTE SET OFF TRASH DISPOSAL PORTAL ALARM
The Milford Hospital was contacted by the State of Connecticut Department of Environmental Protection (DEP) that a trash truck hauling trash from the hospital set off the portal alarm on entry at the disposal site at Bridgeport, Connecticut. DEP incident report number is 02-75. The truck was returned to the hospital and the contents checked, 0.025 millirem/hour was measured at the truck. Tc-99m was found contained in patient waste, which had been properly and legally disposed of. The trash will be held for decay at the hospital before being sent back to the waste disposal site.
The hospital will be contacting NRC Region 1.
The Milford Hospital was contacted by the State of Connecticut Department of Environmental Protection (DEP) that a trash truck hauling trash from the hospital set off the portal alarm on entry at the disposal site at Bridgeport, Connecticut. DEP incident report number is 02-75. The truck was returned to the hospital and the contents checked, 0.025 millirem/hour was measured at the truck. Tc-99m was found contained in patient waste, which had been properly and legally disposed of. The trash will be held for decay at the hospital before being sent back to the waste disposal site.
The hospital will be contacting NRC Region 1.
Power Reactor
Event Number: 39023
Facility: FT CALHOUN
Region: 4 State: NE
Unit: [1] [] []
RX Type: [1] CE
NRC Notified By: RANDY CADE
HQ OPS Officer: RICH LAURA
Region: 4 State: NE
Unit: [1] [] []
RX Type: [1] CE
NRC Notified By: RANDY CADE
HQ OPS Officer: RICH LAURA
Notification Date: 06/27/2002
Notification Time: 14:02 [ET]
Event Date: 06/27/2002
Event Time: 10:33 [CDT]
Last Update Date: 06/27/2002
Notification Time: 14:02 [ET]
Event Date: 06/27/2002
Event Time: 10:33 [CDT]
Last Update Date: 06/27/2002
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(i) - PLANT S/D REQD BY TS
10 CFR Section:
50.72(b)(2)(i) - PLANT S/D REQD BY TS
Person (Organization):
WILLIAM JOHNSON (R4)
WILLIAM JOHNSON (R4)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 1 | N | Y | 100 | Power Operation | 100 | Power Operation |
TS REQUIRED SHUTDOWN INITIATED DUE TO LOSS OF CONTROL ROOM AIR CONDITIONING
"At 10:21 the standby control room HVAC unit, VA-46A, was started due to rising Control Room (CR) temperatures. The running CR HVAC unit, VA-46B, was declared inoperable due to its inability to maintain CR temperature. TS 2.1.2 paragraph 2 was entered, 30 day LCO. At 10:33 it was determined that VA-46A was not cooling and it was declared inoperable. With both CR HVAC units inoperable, AOP-13-Loss Of Control room Air Conditioning, was entered and TS 2.0.1 was entered which requires 6 hours to be in Hot Shutdown. At 10:34 the electrical disconnect was reset on HVAC unit, VA-46B. Control Room temperature was verified to be lowering at 10:40, 78 degrees F. Highest temperature in Control Room was 79 degrees F. At 11:00, VA-46B was verified to be operating normally with Control Room temperature continuing to lower. VA-46B was declared operable with CR temperature 74 degrees F and lowering. TS 2.0.1 was exited with no power reduction occurring. AOP-13, Loss Of Control Room Air Conditioning Abnormal Operating Procedure was exited also. We remain in TS 2.12.2 for VA-46A (30 day LCO) with maintenance ongoing for VA-46A. Current CR temperature at 12:10 is 72 degrees F."
The NRC Resident inspector was notified.
"At 10:21 the standby control room HVAC unit, VA-46A, was started due to rising Control Room (CR) temperatures. The running CR HVAC unit, VA-46B, was declared inoperable due to its inability to maintain CR temperature. TS 2.1.2 paragraph 2 was entered, 30 day LCO. At 10:33 it was determined that VA-46A was not cooling and it was declared inoperable. With both CR HVAC units inoperable, AOP-13-Loss Of Control room Air Conditioning, was entered and TS 2.0.1 was entered which requires 6 hours to be in Hot Shutdown. At 10:34 the electrical disconnect was reset on HVAC unit, VA-46B. Control Room temperature was verified to be lowering at 10:40, 78 degrees F. Highest temperature in Control Room was 79 degrees F. At 11:00, VA-46B was verified to be operating normally with Control Room temperature continuing to lower. VA-46B was declared operable with CR temperature 74 degrees F and lowering. TS 2.0.1 was exited with no power reduction occurring. AOP-13, Loss Of Control Room Air Conditioning Abnormal Operating Procedure was exited also. We remain in TS 2.12.2 for VA-46A (30 day LCO) with maintenance ongoing for VA-46A. Current CR temperature at 12:10 is 72 degrees F."
The NRC Resident inspector was notified.
Power Reactor
Event Number: 39024
Facility: INDIAN POINT
Region: 1 State: NY
Unit: [2] [3] []
RX Type: [2] W-4-LP,[3] W-4-LP
NRC Notified By: MARK LEONE
HQ OPS Officer: RICH LAURA
Region: 1 State: NY
Unit: [2] [3] []
RX Type: [2] W-4-LP,[3] W-4-LP
NRC Notified By: MARK LEONE
HQ OPS Officer: RICH LAURA
Notification Date: 06/27/2002
Notification Time: 15:20 [ET]
Event Date: 06/27/2002
Event Time: 12:10 [EDT]
Last Update Date: 06/28/2002
Notification Time: 15:20 [ET]
Event Date: 06/27/2002
Event Time: 12:10 [EDT]
Last Update Date: 06/28/2002
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(xiii) - LOSS COMM/ASMT/RESPONSE
10 CFR Section:
50.72(b)(3)(xiii) - LOSS COMM/ASMT/RESPONSE
Person (Organization):
MICHAEL MODES (R1)
CHRIS GRIMES (NRR)
MICHAEL MODES (R1)
CHRIS GRIMES (NRR)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 2 | N | Y | 100 | Power Operation | 100 | Power Operation |
| 3 | N | Y | 100 | Power Operation | 100 | Power Operation |
OPERABLE EP SIRENS BELOW MINIMUM NUMBER AT INDIAN POINT
Two counties located in the emergency planning zone went below the minimum number of operable EP sirens. Westchester County had 12 sirens inoperable out of a total of 77 sirens. Orange County had approximately 8 sirens not working out of a total of 16. The minimum number operable criteria is 90% operating out of the total number in each county. The licensee attributed the inoperable sirens due to a storm that passed through the area yesterday. Compensatory measures were in place including route alerting.
The NRC resident inspector was notified.
*****UPDATE LEONE TO LAURA ON 6/28/02 AT 13:48*****
The licensee reported that Westchester County had greater than 90% of their sirens working by 18:20 on 6/27/02. All EP sirens in the 4 counties within the EPZ were working as of 11:28 on 6/28/02.
The NRC resident inspector was notified. Notified R1DO (M. Modes).
Two counties located in the emergency planning zone went below the minimum number of operable EP sirens. Westchester County had 12 sirens inoperable out of a total of 77 sirens. Orange County had approximately 8 sirens not working out of a total of 16. The minimum number operable criteria is 90% operating out of the total number in each county. The licensee attributed the inoperable sirens due to a storm that passed through the area yesterday. Compensatory measures were in place including route alerting.
The NRC resident inspector was notified.
*****UPDATE LEONE TO LAURA ON 6/28/02 AT 13:48*****
The licensee reported that Westchester County had greater than 90% of their sirens working by 18:20 on 6/27/02. All EP sirens in the 4 counties within the EPZ were working as of 11:28 on 6/28/02.
The NRC resident inspector was notified. Notified R1DO (M. Modes).
General Information or Other
Event Number: 39033
Rep Org: MARYLAND DEPT OF THE ENVIRONMENT
Licensee: NEUTRON PRODUCTS
Region: 1
City: ROCKVILLE State: MD
County: MONTGOMERY
License #: MD 3102501
Agreement: Y
Docket:
NRC Notified By: ALAN JACOBSON
HQ OPS Officer: JOHN MacKINNON
Licensee: NEUTRON PRODUCTS
Region: 1
City: ROCKVILLE State: MD
County: MONTGOMERY
License #: MD 3102501
Agreement: Y
Docket:
NRC Notified By: ALAN JACOBSON
HQ OPS Officer: JOHN MacKINNON
Notification Date: 07/01/2002
Notification Time: 08:16 [ET]
Event Date: 06/27/2002
Event Time: 08:00 [EDT]
Last Update Date: 07/01/2002
Notification Time: 08:16 [ET]
Event Date: 06/27/2002
Event Time: 08:00 [EDT]
Last Update Date: 07/01/2002
Emergency Class: NON EMERGENCY
10 CFR Section:
10 CFR Section:
Person (Organization):
MICHAEL MODES (R1)
FRED BROWN (NMSS)
MICHAEL MODES (R1)
FRED BROWN (NMSS)
RADIATION ALARM AT A WASTE TRANSFER STATION WAS ACTIVATED BY A TUCK CONTAINING REFUSE.
A truck containing a roll off refuse container set off the radiation monitor at the Montgomery County Waste Transfer Station located in Rockville, MD at 0800 hours on 06/27/02. The refuse container was searched and a bag containing paper towels and rags found to be contaminated with cobalt-60 with a radiation reading of 0.5 mr/hr. The load was rejected and sent back to Neutron Products Incorporated, Dickerson, MD. The load was evaluated and the radioactive material was removed and placed into storage with radioactive waste. Neutron Products was cited by the State of Maryland for improper disposal of radioactive waste and inadequate surveying and monitoring.
A truck containing a roll off refuse container set off the radiation monitor at the Montgomery County Waste Transfer Station located in Rockville, MD at 0800 hours on 06/27/02. The refuse container was searched and a bag containing paper towels and rags found to be contaminated with cobalt-60 with a radiation reading of 0.5 mr/hr. The load was rejected and sent back to Neutron Products Incorporated, Dickerson, MD. The load was evaluated and the radioactive material was removed and placed into storage with radioactive waste. Neutron Products was cited by the State of Maryland for improper disposal of radioactive waste and inadequate surveying and monitoring.